FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Similar documents
Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental investigation of the performance of industrial evaporator coils operating under frosting conditions

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Performance Study of Triple Concentric Pipe Heat Exchanger

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

A study of Transient Performance of A Cascade Heat Pump System

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

The Effects of Hydrophilicity on Water Drainage and Condensate Retention on Air-Conditioning Evaporators

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Heat Transfer in Evacuated Tubular Solar Collectors

Purdue e-pubs. Purdue University

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Refrigerant Mass and Oil Migration During Start-up Transient

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

*Corresponding author;

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Design and Development of Water Cooled Condenser for Domestic Refrigerator

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

A STUDY OF HEAT PUMP FIN STAGED EVAPORATORS UNDER FROSTING CONDITIONS

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

2. HEAT EXCHANGERS MESA

Mathematical Simulation of Longan Fruit Drying

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Thermal Performance of a Loop Thermosyphon

Air-Cooled Heat Exchanger Performance for R410A

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

Fire Test Evaluation using the Kerosene and Aviation Fuel

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

Experimental Study on the Performance of Twisted Capillary Tube

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Performance of CO2 Cycles with a Two-Stage Compressor

Heat Exchanger Joule-Thomson Transient Cryogenic Refrigeration. Iranian Journal of Chemical Engineering Vol. 14, No. 3 (Summer 2017), IAChE

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Experimental Study on Frost Height of Round Plate Fin-Tube Heat Exchangers for Mobile Heat Pumps

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Transcription:

HEFAT2012 9 th International nference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE Kim K., Kim M.-H., and Lee K.-S.* *Author for correspondence School of Mechanical Engineering, Hanyang University, 222 Wangsimni-ro, Seongdong-gu, Seoul 133-791 KOREA E-mail: ksleehy@hanyang.ac.kr ABSTRACT In order to investigate characteristics of frost behavior according to rigerant flow type, plate fin-tube heat exchanger was operated under both cross-counter flow and cross-parallel flow conditions. The cross-counter flow heat exchanger showed more uniform frost formation than the cross-parallel flow heat exchanger in each row. Also, under a parallel flow condition, the heat exchanger exhibited more non-uniform frost formation at lower rigerant temperature condition ( =-12.0 C). At higher rigerant temperature condition ( =-9.5 C), difference of overall heat transfer rate according to the rigerant flow type was insignificant. However, at the lower rigerant temperature condition, the counter flow type showed higher overall heat transfer rate than the parallel flow type. INTRODUCTION Because the heat pumps used for cooling and heating show higher energy effectiveness than other instrument, demands of the heat pump is still increasing. Additionally, because heat pumps are designed primarily for cooling, they are operated under counter flow conditions (which is more efficient for cooling), and operate in the reverse cycle for heating. Under parallel flow conditions, a frost layer forms on the outdoor unit of a heat exchanger, blocking the air passage and creating additional thermal resistance. As a result, the performance of the heat exchanger is degraded. nsequently, it is very important to investigate frosting behaviour on heat exchanger. A number of studies have been conducted on frost formation according to rigerant flow type. Aoki et al. [1] conducted frosting experiments on a flat plate under both counter flow and parallel flow conditions and compared the properties of the frost layer in upstream and downstream regions of the plate. Nelson et al. [2] used numerical calculations to design a liquid overfeed heat exchanger and investigated its performance under counter flow and parallel flow conditions. Aljuwayhel et al. [3] investigated the air-side and rigerant-side temperatures of a liquid overfeed heat exchanger, using both numerical and experimental techniques. Also, the authors investigated performance of the heat exchanger under counter flow and parallel flow conditions with frosting. The authors of these studies reported that parallel flow type yielded better performance than counter flow type. However, Aoki et al [1] focused on flat plates rather than heat exchangers, and the studies [2,3] focused on heat exchangers used in liquid overfeed systems rather than air-source heat pumps. Liquid overfeed heat exchangers have different temperature characteristics between the air and rigerant with respect to air flow direction, compared to the heat exchangers used for air-source heat pumps. Theore, the characteristics of frost formation on the heat exchanger which used for air-source heat pump according to rigerant flow type are studied in the paper. Based on the investigation, variations of performance in heat exchangers under frosting conditions are discussed. NOMENCLATURE BR [%] Blocking ratio [-] Cross-counter flow type C P [kj/kg K] Specific heat at constant pressure L H [kj/kg] Latent heat of sublimation m a [kg/s] Mass flow rate of air [-] Cross-parallel flow type w a [kg/kg DA] Absolute humidity ratio Q [kw] Heat transfer rate Q a [m 3 /min] Air flow rate Subscripts a ave f fat sen t Air-side Average Frosting Latent heat transfer Refrigerant-side Sensible heat transfer Total heat transfer 1559

EXPERIMENT Figure 1 shows the experimental set-up for frosting and defrosting experiments of the plate fin-tube heat exchanger. The set-up is consisted of 5 parts [4,5]; a test section (where the heat exchanger was installed), a climate chamber (to maintain constant air temperature and humidity), a rigeration section (to regulate the temperature and flow rate of the rigerant for the frosting experiments), a defrosting section (to supply warm rigerant to melt the frost layer), and a recirculation section (to connect the other components and act as an air pathway). Bypass valves were installed at the inlet and outlet of the test section to alternately supply cold rigerant (frosting experiments) and warm rigerant (defrosting experiments). The rigerant used in the experiments was a solution of ethylene glycol as mass ratio of 1:1. Experimental data was recorded after given experimental conditions (air temperature, air humidity, air flow rate and rigerant temperature) reached a steady-state, at which point the frosting experiments were started. Figure 2 showed the plate fin-tube exchanger used in the experiments. The heat exchanger had 4 steps and 2 rows and height of the heat exchanger was 85 mm, width was 120 mm, and length was 36 mm. The aluminium fin surface was not coated (without condensation coating), fin pitch (collared fin length) was 1.81 mm, inner diameter of the tube was 7 mm, longitudinal pitch was 21 mm, and tube pitch was 18 mm. The measuring holes for observing the frost formation were drilled on the top of the test section, and the rigid-borescope which had 90º view direction and 4 mm inner diameter was inserted through the holes for capturing images of frost layer. Three points along the width and six points along the height of the heat exchanger were selected for the image capturing. The images of 18 points in 1 st row (front row) were captured from the front side of the heat exchanger, and the images of 18 points in 2 nd row (rear row) were captured from the rear side. The captured images were analyzed with NIS-element D software program. Uncertainties of the experiments were as follows [6]; average blocking ratio 3.6%, air-side pressure drop 3.3%, and heat transfer rate 3.9%. Flow nozzle Screen Blower Measured location Tube Side [T-S] Fin Side [F-S] 7 mm 36 mm T-S F-S 85 mm 120 mm Air flow Figure 2 Tested fin-tube heat exchanger Front row (1 st row) Rear row (2 nd row) Figure 3 Characteristics of frost growth on a fin tube heat exchanger according to position (t f =30 min) Recirculation Test section RESULT AND DISCUSSIONS To investigate the characteristics of frost formation on a heat exchanger according rigerant flow type, heat exchanger was operated under both the cross-counter and cross-parallel flow conditions. The heat transfer rate was calculated using following equations: Refrigerator Flow meter P p Pump H.X Honeycomb Air mixer Climate chamber Thermocouple & Thermopile P Humidity sensor Pressure tap Defrosting RTD Valve Figure 1 Experimental set-up Q t ( Q a Q )/2 (1) Q a ( Q sen Q lat)/2 m a Cp, a( Ta, in Ta, out ) m a Lh ( wa, in wa, out ) (2) Q m Cp, ( T, out T, in ) (3) Figure 3 shows typical frost formation behaviour on a fin tube heat exchanger at given experimental condition ( =3.0 C, 1560

T -9.5ºC (unter flow type) (rallel flow type) Front row (1 st row) Rear row (2 nd row) Front row (1 st row) Rear row (2 nd row) 100 75-12.0ºC BR ave,1 st [%] 50 Figure 4 Frost formation according to rigerant flow type and rigerant temperature (t f =40 min). 25 ) Q a (m3 /min) ( o C) 3.0 0.00367 2.0-12.0 Time 30 min 50 min (unter flow type) (rallel flow type) Front row (1 st row) Rear row (2 nd row) Front row (1 st row) Rear row (2 nd row) 0 100 75 (a) 1 st row ) Q a (m 3 /min) ( o C) 3.0 0.00367 2.00-12.0 Figure 5 Frost formation according to rigerant flow type and elapsed time ( =-12.0 C). w a =0.00367 Kg/Kg DA, =-9.0 C, Q a =2.0 m 3 /min). As indicated in Figured 2, the tube side (T-S) is located where the fin intersects the step-three tube, and the fin side (F-S) is located between the step-two and step- three tubes. Because the tube obstructed the air flow, thereby generating a flow disturbance, the boundary layer was thin around the tube side in the 1 st row of the heat exchanger. Also, because the temperature of the fin was lower as close to the tube, frost thickness was slightly higher at the tube side than at the fin side in the 1 st row. However, in the 2 nd row of the heat exchanger, air flow separation occurred when air passed the tube, and frost growth in the 2 nd row was less active at the tube side than at the fin side. In view of this non-uniform frost growth, an average blocking ratio (BR ave ) was introduced. Original definition of blocking ratio [7] was a parameter indicating the extent of the blockage of the air flow passage between the fins of a heat exchanger by frost layer. In this paper, the average blocking ratio was calculated as the average value of the 18 measured values in each row. Figure 4 presents captured images of the frost layer according to rigerant flow type (t f =40 min). These images were captured at the middle observation points relative to width, at the second step of the heat exchanger, in both the front and rear rows. To observe frost growth according to rigerant temperature, the rigerant temperature ( ) was set at -9.5ºC and -12.0ºC. At the relatively higher rigerant temperature condition ( =-9.5ºC), the counter flow () type heat exchanger exhibited insignificant difference of blocking ratio in BR ave, 2 nd [%] 50 25 0 (b) 2 nd row Figure 6 Average blocking ratio in each row according to rigerant flow type. each row, because the temperature differences between the air side and rigerant side in the 1 st and 2 nd rows were insignificant. However, the parallel flow () unit exhibited more active heat and mass transfer in the 1 st row than the 2 nd row, because the rigerant entered at the 1 st row distributor and exited at the 2 nd row distributor, so the 1 st row had a lower fin surface temperature. Also, due to the leading edge effect [8] of the heat exchanger, the blocking ratio was slightly higher in the 1 st row than in the 2 nd row. At the lower rigerant temperature ( =-12.0ºC), the counter flow type also exhibited insignificant difference in frost growth between the 1 st and 2 nd rows. However, on the parallel flow type, the air passage in the 1 st row was completely blocked by the frost layer, while an air passage still remained in the 2 nd row. The parallel flow type heat exchanger exhibited more nonuniform frost growth, especially at the lower rigerant temperature (-12.0ºC), for the following reason: at the rigerant temperature of -9.5ºC, the relative humidity was decreased due to frost growth, and the water in the air was condensed onto the fin surface, but the reduction in humidity was insufficient to affect frost growth in the 2 nd row. So, the 1561

100 80 ) Q a (m3 /min) 3.0 0.00367 2.0 0.18 0.15 =-9.5 o C p a [pa] 60 40 =-12.0 o C =-9.5 o C 20 Figure 7 Air-side pressure drop due to frost growth with different rigerant temperatures. relative humidity of the air in the 2 nd row was still adequate for frost growth, the effect of rigerant flow type was insignificant. However, at the rigerant temperature of -12.0ºC, due to the more active frost growth in the 1 st row, the reduction in humidity while passing through the 1 st row was considerable. Thus, the relative humidity of the air in the 2 nd row was inadequate for frosting, compared to the higher rigerant temperature case (-9.5ºC). Accordingly, the difference in frost growth between the 1 st and 2 nd rows was more significant at the lower rigerant temperature condition. Figure 5 shows the counter flow () and parallel flow () type units at rigerant temperature -12.0ºC, according to elapsed time. The counter flow type exhibited relatively uniform frost growth in each row, regardless of the time. The parallel flow type exhibited more active frost growth in the 1 st row, and a corresponding earlier complete blockage of the air passage. nsequently, flow resistance was increased, and air momentum was decreased due to the decreased air flow rate. In particular, after an experimental time of around 40 min, the air passage in the 1 st row was completely blocked, and frost growth in the 2 nd row had almost stopped. This finding indicates that the rapid air passage blockage in the 1 st row of the parallel flow type was another cause of non-uniform frost growth in each row. Figure 6 shows the average blocking ratio (BR ave ) for the 1 st and 2 nd rows when the rigerant temperature was -12.0ºC. The parallel flow heat exchangers () had slightly higher average blocking ratio than the counter flow heat exchanger in the 1 st row. As explained above, this can be attributed to the fact that the parallel type heat exchanger had greater temperature differences between the air side and the rigerant side in the 1 st row, and the fin surface temperature was lower in the 1 st row than in the 2 nd row. In contrast, the counter flow heat exchanger () had higher average blocking ratios in the 2 nd row. Figure 7 shows the air-side pressure drop due to frost growth for different rigerant temperatures. When the rigerant temperature was -9.5ºC, the difference in air-side pressure according to the rigerant flow type was insignificant. When the rigerant temperature was -12.0ºC, the parallel flow Q t [kw] 0.12 0.09 =-12.0 o C 0.06 ) Q a (m3 /min) 3.0 0.00367 2.0 0.03 Figure 8 Variation of heat transfer rate with different rigerant temperatures. type, which exhibited more active frost growth in the 1 st row, had a higher air-side pressure drop than the counter flow type, because the parallel flow type showed faster frost growth, and had earlier air passage blockage by the frost layer. Figure 8 shows the heat transfer rate for the tested heat exchangers at different rigerant temperatures. First, in terms of the rigerant temperature, and irrespective of rigerant flow type, the lower temperature condition ( =-12.0ºC) yielded a higher heat and mass transfer rate than the higher temperature condition ( =-9.5ºC), in the early stage. However, as time elapsed, reduction of the heat transfer rate was more rapid at the lower temperature, due to the faster frost growth. After an experimental time of 25 min, the higher rigerant temperature yielded a more active heat transfer rate, and the average heat transfer rate for the overall experiment (50 min) was 10% higher at -9.5ºC condition than at -12.0ºC condition, under the counter flow type. Next, in terms of rigerant flow type, the rigerant temperature of -9.5ºC yielded insignificant differences according to rigerant flow type. When the rigerant temperature was -12.0ºC, the counter flow type (which exhibited more uniform frost growth in each row) had 8% higher heat transfer rate than the parallel flow type for the overall experiment. This finding indicates that uniform frost growth in heat exchanger yield higher heat transfer. CONCLUSION This study focused on frost formation on a heat exchanger according to rigerant flow type. We investigated the air-side pressure drop and heat transfer rate due to frosting under both counter flow and parallel flow conditions. The difference of blocking ratio between the 1 st and 2 nd row was higher at crossparallel flow condition with lower rigerant temperature. The cross-counter flow type showed the more uniform frost growth and higher heat transfer rate than the parallel flow type. 1562

ACKNOWLEDGMENTS This work was supported by the Energy Efficiency & Resources of the Korea Institute of Energy Technology Evaluation and Planning (2010T100200475) grant funded by the Korea government Ministry of Knowledge Economy REFERENCE [1] Aoki K., Hattori M., Mizuno S., Difference in characteristics between parallel and counter flow type heat exchangers with frosting. Transaction of JSME, part B, Vol. 54, 1988, pp. 1754-1759 (in Japanese) [2] Nelson B., Design of evaporators for liquid overfeed systems. ASHRAE Transaction, Vol. 96, 1990, pp. 1309-1315 [3] Aljuwayhel N. F., Reindl D. T., Klein S. A., Nellis G. F., mparison of parallel- and counter-flow circuiting in an industrial evaporator under frosting conditions. International Journal of Refrigeration, Vol. 30, 2007, pp. 1347-1357 [4] Yang D. K., Lee K.-S., Dimensionless correlations of frost properties on a cold plate, International Journal of Refrigeration, Vol.27, 2004, pp. 89-96 [5] Kim K, Lee K.-S., Frosting and defrosting characteristics of a fin according to surface contact angle, International Journal of Heat and Mass Transfer, Vol. 54, 2011, pp. 2758-2764, [6] leman H.W., Steele W.G., Experimentation and uncertainty analysis for engineers, Wiley, New York, 1989 [7] Jhee S, Lee K.-S., Kim W. -S., Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger, International Journal of Refrigeration, Vol. 25, 2002, pp. 1047-1053 [8] Kim K., Kim J. S., Lee K.-S., Characteristics of frost formation on two-dimensional fins and its empirical correlations, International Journal of Heat and Mass Transfer, Vol. 53, 2010, pp. 2670-2675 1563