Removing The Potential For Condensation In An Electronic Cabinet

Similar documents
Moisture Movement. By Ben Gromicko

32 Tips to Consider Before Purchasing an Electrical Enclosure Air Conditioner TABLE OF CONTENTS INTRODUCTION... 3 TECHNICAL FEATURES 4

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Guide To Troubleshooting INEFFICIENT COOLING FANS

COOLING FOR ELECTRONIC PROCESS CONTROL SYSTEMS IN HOSTILE FACTORY ENVIRONMENTS

Bert Phillips, P.Eng., MBA

CodeNotes. Solar Water Heating Systems Based on the 2015 International Solar Energy Provisions. Introduction. Solar Water Heating System Designs

KOOLTRONIC ENCLOSURE AIR CONDITIONER QUICK SHEET

Postharvest Storage. New Farmer Webinar. October 17, 2013

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Cooling Load Analysis and Computation Worksheet

Installation, Operation, and Maintenance Information

Submittal Data Performance Data Electrical Data

Moisture and Buildings. Moisture Damage

Installation and Operation Guide For

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

A/C Cooling Load calculation and measurement

L14 ENVIRONMENTAL CONTROL TECHNICAL DATA

Guardian/GuardianX Series NEMA 4 or 4X Rated Air Conditioners. Air Conditioners:

RDT Refrigeration Book

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

APC APPLICATION NOTE #109

TC-5231 Series, TC-5232, & TC-5241 Series

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Otherwise, you can continue reading the file on the following pages.

How Much Energy is Really Being Wasted?

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

Single Zone LCD Thermostat Operating Instructions

Dehumidification Strategies Application Note

Installation and Operation Guide For MCF-49FD, MCF-23FD MCR-49FD, MCR-23FD

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL

AIR TO AIR HEAT EXCHANGERS

TrilliumSeries Condenser 1 TRILLIUMSERIES CONDENSER 10 ECOFLEX CONTROLS 11 SELECTION AND PAYBACK ANALYSIS SOFTWARE 3 BENEFITS 8 MODES OF OPERATION

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

y Small dimensions. Easy to install in refrigerated counters or cold rooms

Air Conditioning Clinic

Vapor-Compression Refrigeration

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

User s Manual. i-warm Fluid Warmer

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

INSTALLATION & OPERATING INSTRUCTIONS. Roof Top Unit. Model. USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516

GEOTHERMAL DESIGN GUIDE

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY) CONTROL BOX KIT (12 VDC HEAT/COOL)

GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN August 1, 2002

INSTRUCTIONS OPERATING BLUETOOTH CAPACITIVE TOUCH THERMOSTAT MODEL COOL/FURNACE COOL/FURNACE/HEAT PUMP

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

NOREN Products. Compact Cabinet Coolers

The Art of Building Science

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

Closed Circuit Cooling Towers

Thermo-physical properties found on most psychrometric charts

When considering the purchase of a walk-in you most likely will be looking for the following things.

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

Water Leak Detector. Installation and Troubleshooting. Overview

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

RTP Technical Bulletin

INSTALLATION AND OPERATION MANUAL

Wall mount refrigeration systems available. PRS-2 SERIES Packaged Refrigeration Systems & Walk-in Combinations. KaTom Restaurant Supply, Inc.

RSES Technical Institute Training Manual 2 72 hours, 72 NATE CEHs, 7.2 CEUs

Air Conditioner Performance Upgrade

Atmospheric Moisture: Relative Humidity and Dew Point

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

HP50HA ABG Heat Pump

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Model 8191 & 8192 Ventilator with Dehumidification Installation and Operating Instructions

Thermostat KPU. Data sheet

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

APPLICATION DATA SHEET

Numerical study of heat pipe application in heat recovery systems

PACKAGED TERMINAL AIR CONDITIONER SOLUTIONS. New Construction Model. Model EGN Superior Sound Performance. High Efficiency

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes

UNDERCOUNTER REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

SECTION 9 DOMESTIC APPLIANCES UNIT 47 ROOM AIR CONDITIONERS

REFRIGERATED PREP TABLES Installation, Operation and Maintenance Instructions

Cold Box Design and Insulating for Better Performance. by N. Bruce Nelson, Glacier Bay, Inc. Oakland, California, USA

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

1 to 5 Ton Vertical Wall Mount Air Conditioners Models AVPA

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

FE1 Explosion-Proof Electric Air Heaters

Product Management, Rev 3 December 2009

Chapter 14, Problem 27.

Scotsman Technical Training. CU50 Cube Ice Machine

- TECHNICAL NOTES SUPPLEMENT TO PROJECT WORKSHEET -

ThermoSaver TM Hot Gas Defrost System

THE CAUSES & EFFECTS OF CONDENSATION IN BUILDINGS

Transcription:

Removing The Potential For Condensation In An Electronic Cabinet DDB Unlimited 8445 Highway 77 North Wynnewood, OK 73098 800-753-8459 405-665-2876 www.ddbunlimited.org sales@ddbunlimited.com

REMOVING THE POTENTIAL FOR CONDENSATION IN AN ELECTRONIC CABINET The age old problem of keeping condensation from forming has been exacerbated by current day micro electronics with devices and printed circuit lands that are so small that it takes a 100 power microscope to see them. The advantage to the system designer is that much more capability can be provided in a smaller space due to the reduction in equipment size and increased speed due to less transmission paths lengths between circuits and devices. Equipment that is designed for extreme environments typically has some type of conformal coating placed on the circuit cards to prevent condensation and containments from effecting the operation of the equipment. This is an expensive process since there are additional steps in the manufacturing process and additional design requirements since the transfer of heat from the circuit cards must be provided by heat sinks due to the fact that the devices are no longer cooled by convective air flow in contact with the devices. First we need to understand how condensation forms in its most basic form. Condensation is initially moisture in the air that is in a gas form just like air. When this air comes in contact with a surface that its temperature is at or below the dew point the moisture is converted to a liquid state which we refer to as condensation. Many people have the misconception that salt and fog filters will prevent moisture from entering an area and if you think about it for a minute it is obvious that the moisture is contained within the air itself. This same air freely flows through the filter. A NEMA 4 cabinet is water resistant and dust proof and is not an air sealed enclosure. Air will flow in and out of the enclosure depending on the inside vs. outside air pressures. The laws of physics govern how moist air reacts within various temperature conditions. The study of moist air properties is technically referred to as "psychrometrics." A psychrometric chart is used by professionals to determine at what temperature and moisture concentration water vapor begins to condense. This is called the "dew point." By understanding how to find the dew point, you will better understand how to avoid moisture problems in your system. Relative humidity (RH) refers to the amount of moisture contained in a quantity of air compared to the maximum amount of moisture the air could hold at the same temperature. As air warms, its ability to hold water vapor increases; this capacity decreases as air cools. For example, according to the psychometric chart, air at 68ºF (20ºC) with 0.216 ounces of water (H2O) per pound of air (14.8g H 2 O/kg air) has a 100% RH. The same air at 59ºF (15ºC) reaches 100% RH with only 0.156 ounces of water per pound of air (10.7g H 2 O/kg air). The colder air holds about 28% of the moisture that the warmer air does. The moisture that the air can no longer hold condenses on the first cold surface it encounters (the dew point.) If this surface is within a cabinet then condensation will form.

There are three basic methods of providing cooling in electronics equipment enclosures which are an Air Conditioner, Heat Exchangers and Direct Air Cooling (DAC). The first two methods are closed loop and essentially the air in the cabinet is isolated from the outside ambient air. AIR CONDITIONER: The Air Conditioner is probably the best method of preventing the formation of condensation. The Air Condition has an evaporator coil that is operated significantly below the dew point temperature and as the return air is presented to the evaporator coil moisture forms as condensation on the evaporator coil and is directed to a drip pan that is dumped outside the Air Conditioner. The humidity inside an Air Conditioned cabinet initially swings between 30 to 60 % with 30% when the compressor is on and 60% when the compressor is off. After three to four hours of operation the humidity will be in the range of 40 to 45%. Since this is a closed loop system the Air Conditioner will continue to remove moisture the longer it operates. HEAT EXCHANGER: With the heat exchanger the temperature inside the cabinet will always be above the ambient temperature outside the cabinet. This prevents the temperature inside the cabinet reaching the dew point. This does require that the internal heat load of the equipment is sufficient to maintain the temperature differential between inside and outside. The heat exchanger should have a thermostat or electronic control to prevent temperatures within the cabinet from reaching the critical dew point when the outside ambient conditions are extremely cold. DAC: The DAC method is open loop in that ambient outside air is drawn into the cabinet through a filter to provide cooling. This system requires the use of a thermostat to control the air flow into the cabinet. The equipment heat load is also a critical item in that the temperature inside the cabinet must be maintained above the dew point or condensation will form. Typically the internal cabinet temperature

of a DAC cooled system must be maintained between 95 to 104 degrees F to prevent the forming of condensation. The above chart depicts the relationship between air temperature and humidity. As you can clearly see at high levels of humidity the dew point temperature can easily be within 2 to 3 degrees F of the air temperature. This is why it is critical to maintain the cabinet temperature above the dew point. Keep in mind that the air temperature and the metal structures that make up the equipment can and most often are at lower temperatures than the free air temperature. This is due to the density of these materials. Also these materials are slow to change temperature due to their density. The DAC method of cooling has the greatest potential for the formation of condensation and is why the internal temperature must be maintained to a level sufficient to mitigate condensation formation. The Air Conditioner method of cooling is not as susceptible to condensation due to the evaporator coil in the air conditioner providing cool dry air to the enclosure. Operating the air conditioner when the door to the cabinet is open for an extended period is not recommended since this may cause excessive condensation that may freeze under certain conditions on the evaporator coil. Condensation in liquid form is essentially distilled water and as such has a resistance value far above 5000 ohms per centimeter so except for micro electronics density between pins is not a consideration for conduction between two electrical points. The combination of condensation and other containments such as sodium (salt) which is present in coastal areas and the salt from human hands that come in contact with equipment in the installation and maintenance of equipment, this now becomes a caustic component. This can attack power and data connectors as well as other equipment in the cabinet. Corrosion can lead to high resistance paths that over time can provide maintenance issues.

So the bottom line is that the system designer must consider the options to reduce or eliminate the potential for condensation. This can be caused by having to doors open during high humidity. Small amounts of condensation are inevitable during the servicing of the equipment in the cabinet and in many cases the equipment heat load or cabinet cooling will cause this condensation to evaporate in a short period of time and not cause a serious problem. Extended periods of condensation should be avoided.