COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION

Similar documents
EFFECTS OF AIR VELOCITY AND CLOTHING COMBINATION ON HEATING EFFICIENCY OF AN ELECTRICALLY HEATED VEST (EHV): A PILOT STUDY

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Comparison of radiant and convective cooling of office room: effect of workstation layout

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Thermal Comfort with Convective and Radiant Cooling Systems

Can painted glass felt or glass fibre cloth be used as vapour barrier?

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Behaviour of an Intumescing System Subjected to Different Heating Conditions. Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan

Moisture permeability of some porous materials

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Delivering the Comfort and Performance Your Customers Demand

On the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard, Poul Henning

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

SilverScreen. The innovation in solar heat and light control

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

This document is a preview generated by EVS

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Impact of Air Distribution on Heat Transfer during Night-Time Ventilation

Studying Moisture Transport Trough Active Fabrics Using Humidity-Temperature Sensor Nodes

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Assessment of Domestic Evacuated Tube. Direct Solar Water Heater

Thermal Environment Evaluation in Commercial Kitchens of United States

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

An interdisciplinary approach to identify adaptation strategies that enhance flood resilience and urban liveability

Efficient Low Temperature Heating Systems

Maximum Obtainable Efficiency For Engines And Refrigerators Based On The Stirling Cycle

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Use of Adapted Energy Screens in Tomato Production with Higher Water Vapour Transmission

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Solar Drying Techniques And Performance Analysis: A Review

Wearable cooling system to manage heat in protective clothing

Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated Tubes

INTERNATIONAL STANDARD

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Comfort and health-indoor air quality

Figure 1: Overview of CO 2 evaporator types

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

More heat energy means more of what type of energy? Does the mass change? So, what must change? What is the same in both containers?

Hot-air heating of family houses with accumulation of energy in the floor

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Feasible Working Domains Decision Support for Heat Pump Projects

Optimum Room Acoustic ComfortTM (RACTM) can be achieved by using a selection of appropriate acoustic descriptors

Experimental study of space cooling using ceiling panels equipped with capillary mats

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

MINIMISING THE RISK OF WATER HAMMER AND OTHER PROBLEMS AT THE BEGINNING OF STAGNATION OF SOLAR THERMAL PLANTS- A THEORETICAL APPROACH

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Cooling load calculations of radiant and all-air systems for commercial buildings

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY

Connect North and South Korean Separated Families Higher Comfort Lower Energy

EXPERIMENTAL PERFORMANCE INVESTIGATION OF SWIRLING FLOW ENHANCEMENT ON FLUIDIZED BED DRYER

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

Design, Construction and Testing of Simple Solar Maize Dryer

APPROACH TO THE PREDICTION OF THERMOPHYSIOLOGICAL COMFORT

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

ENERGY EFFICIENCY BRIEF REPORT

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Heat Transfer in Evacuated Tubular Solar Collectors

DESIGN OF A SOLAR/LPG DRYER UNIT

Air and operative temperature measurements in a plus-energy house under different heating strategies

American Society of Heating, Refrigerating and Air-Conditioning Engineers

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Experimental Investigation of an Indirect Evaporative Cooler Consisting of a Heat Pipe Embedded in Porous Ceramic

Performance of an Improved Household Refrigerator/Freezer

APPLICATION OF MINI HEAT PIPES FOR THERMAL MANAGEMENT OF OPTO-ELECTRONIC INSTRUMENTS

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Design and Experimental Studies on Modified Solar Dryer

An experimental study of the impact of tunnel suppression on tunnel ventilation

2. HEAT EXCHANGERS MESA

1. COOL ROOFS. What is a Cool Roof

Induction heating with the ring effect for injection molding plates

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Jülich Solar Power Tower System Behavior During Downtime

Villa Bagatelle Technical Report

Cardinal Coated Glass Superior glass products for residential windows and doors G L A R E C O N T R O L G L A S S

WATER VAPOR IN THE FUNCTIONAL GAP OF WINDOW. MILAN PALKO, SLOVAK UNIVERSITY OF TECHNOLOGY IN BRATISLAVA, Faculty of Civil Engineering,

ISSN: [Agcaoili S. O., 7(3): March, 2018] Impact Factor: 5.164

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

PERFORMANCE TESTERS. Performance Textile Testing

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Transcription:

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION Kuklane, Kalev Published in: [Host publication title missing] Published: 2014-01-01 Link to publication Citation for published version (APA): Kuklane, K. (2014). COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION. In [Host publication title missing] Tampere University of Technology. General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal? L UNDUNI VERS I TY PO Box117 22100L und +46462220000

COOLED PLATE TESTS ON TEXTILE MATERIALS IN SIMULATED COCKPIT UNDER SOLAR RADIATION K. KUKLANE The Thermal Environment Laboratory, Division of Ergonomics and Aerosol Technology, Department of Design Sciences, Faculty of Engineering, Lund University, Lund, Sweden kalev.kuklane@design.lth.se Abstract This study investigated if clothing material with reflective properties has an effect on heat gain in pilot, specifically, under solar radiation. Two materials, conventional pilot suit material (Old) and material coated with coldblack (New, Schoeller Technologies AG, Switzerland) were tested over variety of underwear layers and in a box simulating cockpit. A hot plate was used to measure textile combinations insulation. Under the solar radiation simulation with a Thorn lamp (841 W/m 2 ) a water cooled plate was utilized. The insulation of New was slightly lower than in Old. New showed about 10 % lower heat transmission under solar radiation than Old. Textile surface temperature in New was several degrees lower than in Old. When placed in the box the heat transmission difference reduced to nothing. The new material has ability to reduce the heat load in the open space. In closed space the advantage disappears, i.e. the effect of the outer layer in cockpit scenario is marginal. Keywords: Pilot clothing, outer layer, solar radiation, cockpit ventilation, heat transmission, water cooled plate 1 Introduction In order to save energy for active systems under mission flights various solutions have been studied. Simultaneously, the solutions should not affect pilot performance negatively, e.g. through increased heat or cold stress. Therefore, improving pilot s thermal comfort by passive and/or less energy consuming means would allow saving energy for improving technical parameters for mission capacity. Some of the solutions could be using insulation paint for airplane surface, insulating inner surfaces of cockpit etc. One solution could be using heat reflective coating on pilot clothing outer surface. The aims of this pilot study were to investigate the differences in two materials, conventional suit material (Old) and material coated with coldblack (New, Schoeller Technologies AG, Switzerland), from insulation and material to skin heat transfer viewpoint. 2 Methods Both hot and cool plates were used in the investigation. Insulation measurements of the materials and the layering systems were carried out on hot plate following ISO 11092 (1993). Total thermal resistance of the material and air layer package (R t, m2k/w) measured with 0.41±0.08 m/s and with no solar simulation (Table 1). The textiles were always placed over the layer of the underwear shirt. All conditions were tested twice. The air temperature was kept at +20.2±0.1 C for textile measurements and at +5.4±0.1 C for condition Air gap. Textile material package insulation, R cl was acquired by subtracting air layer insulation from total insulation. Abbreviation AL Textile Plastic Air gap Table 1 Test conditions on hot plate Description Air layer resistance of a hot plate only is the same for both materials A textile layer on top of the layer of an underwear shirt A condition where a layer of bubble plastic was included as an additional layer to simulate any other possible layers and air gaps of the clothing system A situation where the textile is located in average about 15 cm above the plate, and forming the walls around the plate, thus, reducing the influence of air velocity close to plate surface While simulating the effect of solar radiation, however, the temperature of hot plate surface raised above +35 C and the heat loss recordings for comparison were not possible. Even if the chamber temperature was lowered to +5 C the plate surface stayed above +35 C (around +45 C for coldblack and about +57 C for conventional material). 1

Therefore, a water cooled cool plate was used under the solar load simulations to evaluate heat transmitted from radiation through textile package into the system. The method was developed at Lund University, the Thermal Environment Laboratory, and is described by Jögård (2004). Shortly, the system measures the inlet and outlet temperature of the water that is circulated at defined velocity in silicon tubing in/on an insulated material. Water tubing is covered by a thin aluminium plate for better heat distribution with a textile simulating human skin glued on it and avoiding reflection from the aluminium plate. As the textile or system insulation, and tubing and plate area are known, then transmission could be calculated based on the difference in water inlet and outlet temperatures. Water flow was created by a peristaltic pump (Gilson Minipulse, France). The average water flow was 0.158±0.018 g/s, and it was checked for each individual condition. Solar load was simulated by a Thorn lamp. That was placed 2.5 meters away from the material surface creating a load of 841 W/m 2 on the plate area. Tests were carried out in the air and in a box covered by glass simulating cockpit situation. Inside of the box was covered by the textile and the cooling plate was located under it in the bottom of the box. The box was positioned in a way that allowed lamp directly shining in it, and so that the sides were affected minimally. The box edges were covered by aluminium folium to diminish the heat input from the box warming (Figure 1a). The chamber temperature stayed at +19.7±0.1 C and air velocity 50 cm in front of the test setting was in average 0.47±0.08 m/s. a) b) Figure 1 a) Box and equipment position in the chamber. Right from the box can be seen peristaltic pump and water reservoirs. b) Position of the cooling plate in the box modified for additional tests with bubble plastic and fan. Textiles were placed on top of the plate. After the measurement series and preliminary discussions a set of additional tests in the box was carried out. Due to time constraints only 1 test per additional condition was performed. 1. A layer of bubble plastic was added between underwear shirt and the textile in order to simulate the other layers of the system (insulation was still lower than in full pilot clothing system (Kuklane and Holmér, 2012); 2. The same as above, however, a computer fan was added to the box to suck the air from the box (Figure 1b). Air inlet was located in the opposite wall to the fan, but also the openings in the box cover could allow some air flow in the box. The caption of tables should be above the table as shown below. The equivalent temperature for textile comparison was calculated according to Nilsson (2004): (1) where t eq is equivalent temperature of the uniform, homogenous environment ( C); t s is plate surface temperature ( C); q T is measured manikin heat loss during the actual conditions (W/m 2 ); and h teq is dry heat transfer coefficient, including clothing, determined during calibration (W/m 2 K). 3 Results and discussion Figure 2 show the total and the clothing insulation of the material package. In the Air gap condition the higher insulation from new material could be related to a larger textile piece that allowed diminishing leakage better, but also to a possibly higher air penetration resistance (lower air permeability) than the conventional material (not measured within the limits of this study, but the data should be available from 2

the manufacturer of the textiles). Otherwise, the differences in new and old material insulation (new had somewhat lower thermal resistance) were consistently independent from the combination of other layers. The differences were small, and would probably stay unnoticed by the users. a) b) Figure 2 a) Total thermal resistance of the material and air layer package (R t, m 2 K/W), and b) thermal resistance of clothing material package (R cl, m 2 K/W) measured with 0.41±0.08 m/s and no solar simulation. Old is the present material and New is material with coldblack finish. AL is air layer resistance of a hot plate only and is the same for both. The Textile was always measured over a layer of underwear. Plastic is a condition where a layer of bubble plastic was included as an additional layer to simulate any other possible layers and air gaps of the clothing system. Air gap is a situation where the textile is located in average about 15 cm above the plate, and forming the walls around the plate, thus, reducing the influence of air velocity close to plate surface Figure 3 Temperatures ( C) at various points of the system. In inlet temperature of water; Out outlet temperature of water; Skin temperature on textile skin in the centre of the plate under the tested material package; Textile temperature on textile at the centre of the plate facing the solar lamp; AmbAir air temperature in the chamber; In box air temperature in the box. Figure 3 shows 5 minute average stable state temperature values for each test condition. There seems to be no risk of skin injury due to heat with neither of the materials. As it can be seen then conventional textile absorbed more heat, however, in box the differences became less. In the open air where surrounding environment is minimally affected by the radiation there are significant differences between old and new textile reaching to over 70 W/m 2, and indicating superiority of the new material (Figure 4). With new material the heat transmission to skin is over 8 % less (Figure 5). Thus, when a pilot would stay in open space in the sun, then the heat load would be considerably lower corresponding to equivalent temperature difference of 6.5 K. If to consider a relatively moderate activity level (body own heat production) of 90 W/m 2 then the difference was close to 7 K. 3

The situation in the box differed drastically. The difference in transmission was only 1.5 % leading to reduced heat gain from new material only to 13 W/m 2 (Figures 6 and 7). Relating this information to temperature data in the box (Figure 3) it may be expected that considerable amount of heat was trapped in the box and was not reflected out (greenhouse effect). This affected the air temperature increase in the box by almost 4 degrees and that most probably did increase the heat transport into the plate. Thus, the textile surface temperatures in the box were relatively similar, although, the effect on textile skin was still stronger under the old material (point measurement in the centre of the plate in the strongest radiation area). Converting these differences into differences of the equivalent temperature we can see that in passive system the new material is better by 0.4 K, and considering internal heat production of working pilot (90 W/m 2 ) up to 0.9 K. Figure 4 Absorbed and transported heat (W/m 2 ) for Old (conventional) and New (coldblack ) textile in the air and in the box Figure 5 Transmission (%) of the simulated solar heat to the plate for Old (conventional) and New (coldblack ) textile in the air and in the box Based on the results up to this point the new material would give a very significant effect under direct solar radiation, while in closed spaces the positive effect was diminished. This was expected to be diminished even more by additional insulation layers of other clothing pieces in pilot clothing ensembles, but counterbalanced with ventilation of the box space that would remove the stored heat. Therefore, additional tests were carried out with layer of bubble plastic and ventilating the test box. The results can be seen in Figures 6 8. 4

Figure 6 Absorbed and transported heat (W/m 2 ) for Old_pl (conventional) and New_pl (coldblack ) textile in the box with additional insulation (bubble plastic) and with ventilation of the box Figure 7 Transmission (%) of the simulated solar heat to the plate for Old_pl (conventional) and New_pl (coldblack ) textile in the box with additional insulation (bubble plastic) and with ventilation of the box Figure 8 Temperatures ( C) at various points of the system under additional measurements in the box with additional insulation (bubble plastic) and with ventilation of the box. In inlet temperature of water; Out outlet temperature of water; Skin temperature on textile skin in the centre of the plate under the tested material package; Textile temperature on textile at the centre of the plate facing the solar lamp; AmbAir air temperature in the chamber; In box air temperature in the box. Figure 6 shows that the heat transmitted through textile package to cooled plate was in the case of the new material somewhat (7 W/m 2 ) higher than in the old material. This does draw the attention to the insulation results observed with condition of air gap (Figure 2). It indicates that the differences observed there may be 5

related even to some more important factors than just more material available for surrounding the sample. Due to that the transmitted energy through textile package and skin (simulated by textile) into the tissues (simulated by water filled silicone tubing) was also higher for new material. In such conditions the equivalent temperatures of the new and the old materials did differ neither with nor without ventilation, although, ventilation considerably affected the textile surface temperature difference (Figure 8). I.e. the earlier expected effect of the ventilation was not observed here. A difference in new material s favour was observed in the equivalent temperatures if internal heat production was added. Somewhat lower insulation (= higher heat transfer coefficient) would allow the 0.6 K difference in equivalent temperature. If we do not account for any considerable measuring errors (only 1 test per additional condition) then it seems that the old material does not function worse than the new one in cockpit scenario. 4 Conclusions The new material has an ability to reduce the heat load considerably in the open space that is exposed to solar radiation. In closed space the advantage is reduced to minimal or nothing, depending on the conditions. In this study the analysis was based on the whole surface exposure to the solar radiation. In reality the exposed surface is commonly less than half. This issue may diminish the observed effect. In this study the material properties differed. If coldblack is applied to the conventional material then the effect of insulation may not be observed at all. It has to be ensured that the finish will not increase the evaporative resistance of the outer layer, and thus, of the whole system. In hot conditions the major heat loss from human body takes place via evaporation and any positive effect of the reflective surface of the material may easily be cancelled by lower vapour permeability of that layer. Also, any ventilation system into the pilot suit would diminish the effect of the outer layer, as the cooling occurs closer to skin surface and anything happening on the outer layer has even smaller effect due to the insulation of the layers in between. Considering that the reflective effect of the outer layer in heat under solar load would improve the situation, while it would be a disadvantage in the cold where heat gain from the sun would act as a considerable positive effect then possibly two different outer layers for warm respective cold conditions may be required. Based on this study, however, the effect of the outer layer for cockpit scenarios is marginal. Acknowledgements Thanks to Aeronautics, Saab AB, Sweden for funding and support. Special thanks to Claes Zimmer. References [1] International Organization for Standardization (ISO): Textiles Physiological effects Measurement and watervapour resistance under steady state conditions (sweating guarded hotplate test) (Standard No. ISO 11092:1993), Geneva, Switzerland, ISO, (1993) [2] Jögård, H.: Solenergitransmission i textila material (Transmission of solar energy in textiles), in Swedish, Kandidatexamen vid institutionen Textilhögskolan, Högskolan i Borås, 2004:2:1, (2004) [3] Kuklane, K. & Holmér, I.: Pilot clothing system with a CBRN protective underwear, A report for Aeronautics, Saab AB. Thermal Environment Laboratory, Faculty of Engineering, Lund University, Lund, Sweden, (2012) [4] Nilsson, H. O.: Comfort climate evaluation with thermal manikin methods and computer simulation models, Doctoral thesis. Royal Institute of Technology, University of Gävle, National Institute for Working Life. Published in Arbete och Hälsa 2004:2, (2004) 6