New generation FPA-5000/1200 Kristof Vandenberghe 1
Table of content New panel controller Modifications FSP-5000-RPS Uninterruptible acoustic notification 2
New panel controller General information: New hardware: MPC-5000-C replaces MPC-5000-B Coulered touch screen Two ethernet ports New Firmware: V2.8 IP panel network Downwards compatible with MPC-5000-B Mixed networks with C & B series NEW! 3
New panel controller Quality display with sharp contrast Excellent readability of display information 4
New panel controller Bright collared messages Fast and secure identification of the messages 5
New panel controller Bright collared messages Fast and secure identification of the messages 6
New panel controller Find the differences 7
New panel controller IP-ethernet connection: offers more possibilities New Increased network speed Faster donwload of configuration and firmware Advantage Safe time and money Additional network topologies Flexible tailor made solutions Double redundant network trough CAN and IP Operational security also at cable interruption Longer distance between nodes Cover large areas with one system 8
New panel controller MPC-5000-05 has intergraded switch with 2 ports EN54-13 only allows Ethernet-network trough fibre optics Dedicated fibre is needed to guarantee bandwidth Maximum distance between 2 nodes: Multi-mode: 2km Single-mode: 40km Netwerk can exist of: CAN-bus and ethernet MPC-5000-B and MPC-5000-C Maximum limits: sensors / panel: 2048 sensors / system: 32512 nodes / system: > 32 (final number is currently being tested in the lab) IP 9
New panel controller Different network topologies Redundancy via closed loop configuration CAN IP 10
New panel controller Different network topologies OPC-Server CAN IP Backbone CAN CAN 11
New panel controller Different network topologies Double redundancy via CAN-bus and Ethernet CAN IP 12
New panel controller New Advantage Colared touch screen Enhanced usability Ethernet Network Improved flexibility and scalability 13
Table of content New panel controller Modifications FSP-5000-RPS Uninterruptible acoustic notification 14
Modifications FSP-5000-RPS GUI which support new network topologies 15
Modifications FSP-5000-RPS Auto synchronisation time/date of all nodes with PC 16
Modifications FSP-5000-RPS Consolidate all history files into one file 17
Modifications FSP-5000-RPS 1 clear overview of the complete system Logical filters: Time / date Type of event Logical address Search function Export functionality towards: *.CSV *.PDF 18
Modifications FSP-5000-RPS New dialog for configuration of multiple elements at once 19
Table of content New panel controller Modifications FSP-5000-RPS Uninterruptible acoustic notification 20
Uninterruptible acoustic notification Current way of working: Addressable sounders are connected to the LSN-bus Sound pattern and volume are configured in the panel 21
Uninterruptible acoustic notification Current way of working: 1 st short circuit Sounder are temporary deactivated, when panel isolates the short circuit. Afterwards sounders reactivates. Maximum delay according VdS3536 = 5s 22
Uninterruptible acoustic notification Current way of working: 2 nd short circuit Peripherals between the short circuits doesn t work anymore. DANGER: no notification in this part of the building! 23
Uninterruptible acoustic notification Current way of working: 2 nd short circuit Peripherals between the short circuits doesn t work anymore. DANGER: no notification in this part of the building! SOLUTION: uninterruptible notification with battery backup 24
Uninterruptible acoustic notification SOLUTION: uninterruptible notification with battery backup Base sounder and standalone version available 25
Uninterruptible acoustic notification New way of working: 1 st short circuit Sounders remain active due to battery backup While the short circuit is isolated No delay solution is better than demanded by VdS3536 26
Uninterruptible acoustic notification New way of working: 2 nd short circuit Peripherals between the short circuits doesn t work anymore. Exception for the sounders: battery backup guarantees uninterruptible notification of 1/2h. Also for stubs 27
Uninterruptible acoustic notification Questions concerning the battery Question Is it required to measure the battery voltage during maintenance? When do we need to exchange the battery? What s the battery autonomy when the sounder is active? Answer No, the battery is tested by the system every 24h The panel will generate a specific message The time span for battery placement is 4 weeks Half an hour guaranteed! Even during the 4 weeks time span. Is it difficult to replace the battery? No, it s plug & play What s the average life span of the battery? 10 years in stand-by mode. How much does it costs? Battery: BLP 9,75 pp (multi pack 20pcs) Additional cost: BLP 15,- (battery included) 28
Uninterruptible acoustic notification A FNM - 420 - BS B WH RD Fire Notification Multitone LSN improved A: indoor B: outdoor Base Sounder WH: white RD: red 29
Uninterruptible acoustic notification Uninterruptible! A FNM - 420 U - BS B WH RD Fire Notification Multi tone LSN improved A: indoor B: outdoor Base Sounder WH: white RD: red 30