Functionality Inspection of Interconnected Fire Protection Systems

Similar documents
Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Can painted glass felt or glass fibre cloth be used as vapour barrier?

Maximum Obtainable Efficiency For Engines And Refrigerators Based On The Stirling Cycle

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

On the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard, Poul Henning

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

An interdisciplinary approach to identify adaptation strategies that enhance flood resilience and urban liveability

Operation and maintenance service provision in uncertain times the case of the FLSmidth Group during the Arab Spring

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

Air and operative temperature measurements in a plus-energy house under different heating strategies

Structure Fires in Hotels and Motels

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

Riverside Fire Department

Villa Bagatelle Technical Report

Baseline Data Required for AS

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Management Practices: Fire Protection Impairments November 2015

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

Outline of Measures for Fire Prevention and Safety under the Laws and Regulations of Fire Fighting

a) Establishment of emergency procedures to be followed at the time of an emergency;

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977

Analysis of Availability of Fire Fighting Equipment in Selected Knitting Garment Factories in Bangladesh

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

JCI - Smoke Control Systems Overview 10/27/2016

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Public Benefits to A Smoke Alarm Performance Evaluation Scheme

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

ECONOMIC JUSTIFICATION FOR SPRINKLER SYSTEMS

Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

How design fires can be used in fire hazard analysis

The Macro Quallty Assurance System for Fire Safety Engineering

BULLETIN: Subchapter 4 Retrofit Requirements for Nightclubs

Performance Requirement for Building Fire Safety from the Viewpoint of Firefighting and Rescue Activity

FIR 3305, Fire Protection Structure and Systems Course Syllabus. Course Description. Course Textbook. Course Learning Objectives.

PART 3-O REQUIREMENTS FOR SPRINKLER SYSTEMS MAINTENANCE AND SUPERVISION. 3-O Introduction O.1 Scope of Maintenance and Supervision...

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

Fire alarm provisions for alerting the Fire Service

Fire protection documentation. CFPA-E Guideline No 13:2015 F

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Fire Safety Guidelines

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Households' energy use - which is the more important: efficient technologies or user practices? Gram-Hanssen, Kirsten

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

A Model of the Population of Fire Detection Equipment Based on the Geometry of the Building Stock

Protecting our future! Advanced fire protection for pupils, teaching staff and physical assets

What you need to know about. Maintaining essential safety measures in your building

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Fire Sprinklers Working Group Final Report

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

The Social Accountability International (SAI) Fire Safety Checklist

Sec False alarms.

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION. Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2

Cooling load calculations of radiant and all-air systems for commercial buildings

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

THE TOWNSHIP OF CRANBURY

STUDY ISSUE PAPER ON THE RESIDENTIAL SPRINKLER ORDINANCE

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

DS/EN DK NA:2011

Securing the operational readiness of fire control systems

(1135/2016) Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Economic Affairs and Employment, Finland

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Secretary of State determination under article 36 of the Fire Safety Order

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

Development of IFC based fire safety assesment tools

research highlight Canadian Housing Fire Statistics Findings

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

Local Rules: Fire Safety

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80

Fire Risk Assessment 2017

Aalborg Universitet. The physical impoverishment and decay of Danish villages causes and consequences Møller, Jørgen

Fire System Impairment Policy

Fire evacuation drill

CHAPTER I: INTRODUCTION

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Alarm System SECURE AS 302

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Overview of HEOA Fire Safety Requirements

RESEARCH ON THE MAIN CRITERIA OF DECISION-MAKING FACTORS THAT AFFECT CONSUMERS' PURCHASE OF RESIDENTIAL FIRE ALARMS

Fire Drill Policy. Facilities Manager DCD. Statutory. Principal. Staff. REVIEW DATE 20 th August Owner. Version Number: 8 Legal Sign:

U.S. STRUCTURE FIRES IN OFFICE PROPERTIES

Date and Time of Incident. Feb. 13, 1964 Breakout at15:33 (approx.) Noticed at 15:27 Notified by emergency call. Extinguished by 21:07

Title: BFST1505 Syllabus

City of Regina Alarm Bylaw

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

High Rise Floor Wardens

Transcription:

Downloaded from orbit.dtu.dk on: Feb 13, 218 Functionality Inspection of Interconnected Fire Protection Systems Kærup, René; Jomaas, Grunde Published in: Proceedings of the 1th International Conference on Performance-Based Codes and Fire Safety Design Methods Publication date: 214 Link back to DTU Orbit Citation (APA): Kærup, R., & Jomaas, G. (214). Functionality Inspection of Interconnected Fire Protection Systems. In Proceedings of the 1th International Conference on Performance-Based Codes and Fire Safety Design Methods General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim.

Functionality Inspection of Interconnected Fire Protection Systems ABSTRACT René Kærup 1, Grunde Jomaas 2 1 Aalborg Fire Brigade, 9 Aalborg, Denmark 2 Department of Civil Engineering, Technical University of Denmark 28 Kgs. Lyngby, Denmark After 24, where the Danish buildings code changed from prescriptive to performance based requirements for fire safety, the number of installed fire protections systems has increased with about 3 percent. Furthermore, fire safety strategies often call for combinations of active fire protection systems, such as a smoke detection system, sprinkler system, warning system and fire ventilation system. However, only smoke detections systems and sprinkler systems require inspection from an independent accredited company, whereas the other systems functionality is entirely up to the professionals that install them and the owner s maintenance schedule, both of which do not require any supervision from the authorities. Herein, 12 complex buildings, in which all fire protections systems were inspected by an independent accredited company, were studied to see whether or not the buildings adhere to the fire safety design in their operational phase. The results showed that the functionality of the interconnected fire protection systems was not as designed in the performance-based analysis. Furthermore, due to the lack of this functionality the fire safety level is not at high as the authorities demand, something which could have fatal consequences in the event of a fire. INTRODUCTION Active fire protection systems are all considered as one specific entity (such as sprinkler system, alarm system, and ventilation system), and designed after their own standards and guidelines. In Denmark, only two of the systems require inspection and approval from the authorities before the building is approved for use. The problem identified and discussed herein is that all of the fire protections systems in the building are not considered as one interconnected system, and therefore the interconnected fire protections systems are not inspected for combined functionality. On the contrary, the individual fire protection systems are tested without any reference to how they should interact with other systems in the case of a fire. On the other hand, the interconnected fire protection systems are considered as one entity in the performance-based design that is undertaken by the fire safety engineer and presented in the fire strategy report that has to be approved by the authorities having jurisdiction before the building can be commissioned. As such, the appropriate fire safety level can only be reached if all the systems work, both by themselves and in interplay with the other systems. This includes going to error mode when such interconnected systems are not receiving the appropriate input signals from the systems they are meant to interact with in an emergency situation. Without such an error mode reported to the controlling system, the operator in the control center at the fire brigade will not receive this error and will thus be unable to fix the cause of the error mode.

In Denmark, the building authority approves the performance-based analysis of the fire safety design. The process include a verification process to ensure that the standards that the fire engineer use for the fire safety design are the appropriate ones to reach the expected fire safety level in the building. The legislation is intended to demand a certain safety level [1], but these demands are not explicitly quantified in the Building Regulations (BR1) [2]. The detailed requirements are provided in the accompanying performance-based guidance document [3]. The legislation has one demand for the functionality of the fire safety system, which is that the systems should function in the entire lifetime of the building. However, there are no demands for any specific documentation for how the occupants or building owner should ensure this. In the operational phase, the fire brigade is allowed to make fire inspections in buildings covered by the Order on Operational Requirements, which is published by the Ministry of Defense and provides all the maintenance and inspection requirements for passive and active fire protection solutions [4]. Buildings that are constructed after performance-based analysis, which normally have several active fire protection systems installed, do not automatically require a fire inspection. Rather, an inspection will only take place if some part of or the entire building s occupancy type is covered by the operational regulations. Figure 1 provides a simplified overview of how the responsibility of the fire safety of a building changes from the design and construction phase to the operational phase. Legislator Operational Phase Operational Regulations [4] Building Regulations [2] Building Permit Fire Inspection Guidelines Standards Figure 1 Overview of the Danish Fire Safety Legislation System. Legislation for buildings is shown in green, whereas legislations for the fire brigade are shown in blue. Smoke Detection System Statistics Statistics from Aalborg for the period from 1996 to 212 show that there was a steady increase in the number of automatic fire alarm (ABA) systems in the municipality, as seen in Figure 2 [5]. These systems are installed after a guideline and inspected by an accredited inspection company every year [6]. In 212, the Aalborg Fire Brigade control center received 38 alarms from automatic fire alarm (ABA) systems. The causes that lead to activation of the alarm system were registered in the Aalborg Fire Brigade internal system, and are shown graphically in Fig. 3 [5]. Only in two of the ten fire cases had fire spread beyond the ignition object, and only those two fires needed action from firefighters to extinguish the fire. It can also be seen that it was mainly operational and behavioral actions that caused the activation of the smoke detections system.

227 of the recorded alarms were due to misbehavior, whereas the remaining 71 alarms were categorized as unknown. These were further subdivided into 59 alarms without known cause and 12 alarms caused by pressure drop in the sprinkler system without sprinkler activation. It should be noted that there is no tradition for further examination of the failures. Automatic Fire Alarm Systems installed 3 25 2 15 1 5 85 1 153 182 165 195 164 Figure 2 The number of automatic fire alarm systems in Aalborg municipality versus calendar year [5]. 164 1996 1997 1998 1999 2 21 22 23 24 25 26 27 28 29 21 211 Year 181 189 166 239 212 248 283 273 6 5 4 3 2 1 49 43 Cooking Fire alarm activated - no fire Workers Unknown 38 35 24 21 16 12 11 1 7 7 6 Technical 2 Steam 9 Smoke Machine Pressure drop sprinkler "Forgot" to deactivate at service Number of received alarms Fire Cleaning Heat from machine Smoking Smoke/dust/water Summarized onetime events Figure 3 Causes for the automatic fire alarms received by the Aalborg Fire Brigade in 212. The Danish Institute for Fire and Safety Technology (DBI) publishes the guidelines that are used for the majority of fire protection systems in Denmark. DBI is also one of the two accredited inspection companies for fire protection systems, and they publish an annual report that shows statistics from all their inspections [7]. The result for 211 (published in 212) report a reliability of 99.1% for smoke detection systems, which is rather remarkable given that the Aalborg Fire Brigade statistics [5] shows there only have been fires in 3.2% of the cases where the smoke detections system had been activated. As such, there is a discrepancy between reliability and performance that calls for further investigation. The Aalborg statistics from 212 [5] compares well with those from Vineland, New Jersey were statistics shows there only was a real fire in only 3 % of the causes were the Fire

Brigade was called out by activated smoke detection [8]. In the same study, it was documented that 7% of the 244 calls from smoke detections system in three high rise buildings were false alarms. The false alarms could be placed in 4 categories: i) Improper operation, ii) Building workers started without notifications, iii) System malfunctions and iv) Damage on the system. They succeeded in bringing the false alarms down with 5% by focusing on training/education, improved procedures and communication, and by investigating causes for false alarms [8]. As a final comparison, a Swedish study of the alarm failure problem concluded that there is only a fire in 6.4% of the cases where fire protections systems are activated [9]. METHOD The current study investigated the functionality of interconnected fire protections systems in 12 large buildings located across Denmark. In all off the cases, an inspection was required in the building permit, for all of the fire protections systems. The data in the cases are from accredited inspections firm, who agreed to provide these inspection reports from performance based building for the project. The inspected buildings were as shown in Table 1. Table 1 Overview of the different buildings studied herein. Case # Use Area [m 2 ] total/detached Occupancy Category BR1 [2] Inspection company and the respective journal nr. Installed fire protection system* 1 Shopping center 18,5/3, 1, 2 & 3 RMG-1357-3-212 ABA, AVS, ABV- 27, AVA-24. 2 Shopping center 21,5/3,5 1, 2 & 3 DBI-IF26/IG15 AVS, ABV-27, AVA-24. 3 Shopping center 25,/- 1, 2 & 3 RMG-29.1-12/PBN AVS, ABV-27, AVA-24. 4 School 4,5/- 2 & 3 BCA note/dbi-b146 AVS, ABV-27, AVA-24. 5 Sports complex 34,/7,5 3 Inspection date filibustered AVS, ABV-27, AVA-24. 6 Shopping center 36, 2 & 3 RMG-161-15-21 AVS, ABV-27, AVA-24. 7 School 2, 2 & 3 RMG-16744 ABV-27. 8 Water 9, 3 RMG-1569 ABA, AVS, ABV- amusement park 9 Pressurized stairways Highrise building 1 Pressurized stairways in Car park in basement/hotel. 27, AVA-24. - RMG-17987 ABA; DS/EN 1211-6. - RMG-18181 ABA, DS/EN 1211-6. 11 Nightclub - 3 RMG-12837-15-212 ABV-27. 12 Supermarket 7,25 3 RMG-1844-212 ABA, AVS, ABV- 27, AVA-24. *ABA = Automatic Smoke Detection System; AVS = Automatic Sprinkler System; ABV = Automatic Fire Ventilation System, 27 [1] or 27 [11] describes the standard the system is referring to; AVA = Automatic Warning System, 24 [12] or 24 [13] describes the standard the system is referring to.

Case #4 School Building For a building that is designed using performance-based design, the failures are registered when the fire systems were inspected after the buildings were reported as finished. The case, a high school with a floor area of approximately 4,5 m 2, was taken into use in the autumn of 212. Table 2 shows the connection between the fire systems, whereas Figure 4 details the failures registered in this building case. It is seen that the interdependency of the systems is not as desired due to an abundance of errors. Table 2 The interconnectivity of the systems in Case #4 School Building. Activation of Mechanical smoke ventilation Warning systems (Voice) Alarm transmission to Fire Brigade Atrium sprinkler Fire doors shut automatically upon detection Elevator goes to ground floor (ABA) smoke NO YES YES - YES YES detector Line/flame NO YES YES YES NO YES detector (AVS) sprinkler NO - NO PARTIAL NO - (ABV) Smoke NO - NO - NO - ventilation Fire call press - YES YES - NO YES Atrium sprinkler YES YES YES - NO - Mechanical Smoke Ventilation System (ABV) System documentation according to DBI-27 [1] Error transfer from ABVcentral. signal from supply-air (door). signal from supply-air (window). Automatic Sprinkler System (AVS) Atrium sprinklers were not activated due to malfunction of line detector. Automatic Warning System (AVA) System documentation according to DBI 24 [12] Documentation sound pressure report and understandable speech. signal from power failure of (AVA)-rack. Automatic Fire Alarm System (ABA) Escape Lights Due to water damage in central, malfunction all over. Documentation of the measurements of the light intensity output of the panic lights Other The self-closing fire doors in the basement malfunctioned. Smoke ventilation in staircase does not open on signal from smoke detector. Elevator goes to the ground floor. Figure 4 Example of the data collection and failure registration in Building Case #4. The white text represents activity with unwanted functionality, whereas the yellow text represents activity with wanted functionality.

Categorization of s The categorization of the observed failures was performed according to the required protocol as provided in the guidelines by The Danish Institute for Fire and Safety Technology [14]. This method is used by accredited inspection companies during their inspections. During the first inspection, up to two C-failures are allowed. Systems with a single occurrence of an A- or B-failure cannot be approved. The defects are categorized as follows: A: Significant deficiencies that can result in a non-functional system. B: Deficiencies that can result in a situation where parts of the system will be non-functional. C: Minor deficiencies, which could ultimately result in a situation where the system or parts thereof will not provide the expected protection. D: Correct functionality Using this method, it was possible to categorize the systems as Approved, Conditionally Approved and Not Approved. Conditionally approved means that the found failure should be fixed and the fire system re-inspected within 3 months. RESULT AND DISCUSSION Observed s in the Inspection Cases Figure 5 provides an overview of the categorization of the observed failures of the automatic smoke ventilation system for the 12 inspection cases in the current study. 12 1 A- B- Count 8 6 C- D - Satisfactory Performance 4 2 Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Case 7 Case 8 Case 9 Case 1Case 11Case 12 Figure 5 categorization (A-, B- or C-failure or D Satisfactory Performance) of the automatic smoke ventilation system for all cases in this study. Note that some of the buildings did not have such a system. In 64% of the inspected buildings, there was an A-failure, and in all of the inspected buildings B-failures were recorded (Case #5 is excluded from this). Actually, in 72% of the inspection cases more than one B-failure was registered. Only a few C-failures were recorded during the inspections, something which may come as a result of the large number of A- and B-failures. It is perceived that, as a result of the abundance of these graver errors, the inspector did not bother to concentrate on the minor details, as it was clear that further work on the systems were needed for approval. It is concerning that the capacity of the smoke ventilation systems were found to be insufficient (as compared to the design capacity from

the fire safety strategies) in 4% of the investigated cases. In one case, only 33 % of the needed capacity, as calculated by the fire safety engineer, and this would quite clearly have a significant effect on the fire safety level. In 83% of the investigated systems, there was no transmission signal from errors arising from the doors or windows that serve as openings for supply air for the smoke ventilation to function according to design. If the right amount of supply air is not brought into the building, the smoke venting capacity may not be sufficient, or worse yet, the smoke flow direction may be reversed. In 89% of the investigated cases there was no signal from errors that occurred in the smoke ventilation system central. The consequence of this would be that the maintenance personnel need to detect the error manually during inspections according to the maintenance protocol. As a result, the system is significantly less likely to function as prescribed during an emergency event. Figure 6 provides an overview of the categorization of the observed failures of the automatic smoke ventilation system for the 12 inspection cases. The total absence of C-failures is noteworthy, as it is completely against common reliability theory. 4 3 A-failure Count 2 1 B-failure C-failure D - Satisfactory Performance Case 1 Case 2 Case 3 Case 4 Case 6 Case 8 Case 12 Figure 6 categorization of the automatic warning systems in this study. Note that some of the buildings did not have such a system. Table 3 presents the total count and score for each of the failure categories for both the smoke ventilation system and the warning system for all the inspections. Table 3 Total score for A-, B- and C-failures for both smoke ventilation and warning system for all cases. Total failure count for the smoke ventilations system Total failure count for the warning systems Type of A B C D (Satisfactory Performance) 2 39 4 6 11 16 3 Figure 7 is a radar-diagram showing A-, B-, and C-failures along with D Satisfactory Performance. Clearly, A- and B-failures are the ones with strongest representation, whereas

there is a low population of C-failures, which is probably due to the large count of A- and B- failures, as discussed above. The figure also shows that there are significantly more failures for the smoke ventilations systems (ABV) than for the warning systems (AVA). This is in line with results presented by Klote and Milke, who reported that ventilation systems often can have a low reliability due to the fact that consist of a large number of components [15]. 4 A-failure 3 2 D-satisfactory Performance 1 B-failure ABV - Smoke Ventilation AVA - Warning System C-failure Figure 7 Radar-diagram showing A-, B-, and C-failures, as well as Satisfactory Performance (D), for smoke ventilation and warning systems. Overall Results of the Investigated Cases Figure 8 shows that the functionality of the interconnected fire protections systems is not satisfactory. That is, the functionality is not as designed in the performance-based analysis, which means that the fire safety does not match the one demanded by the authorities having jurisdiction. Such a reduction in the safety can obviously lead to fatal consequences in the case of a fire. Given that the smoke detection system and sprinkler system is under accredited inspections, the problems are transferred to the smoke ventilation system and warning system, and apparently there are challenges associated with installing these systems according to the guidelines/standards. Percent 8 7 6 5 4 3 2 1 73 27 Approved Not approved Conditionally approved Figure 8 Overall results for all the interconnected fire protection system, categorized according to the required protocol for an accredited inspection firm.

The results presented in percent are showing a trend, but due to the small investigated population, this could not be considered as well documented as individual occurrences can dominate the total outcome. Results for the Smoke Ventilation Systems In 1% of the investigated cases there was not the system documentation as demanded in the guideline [1, 11]. Only 6 % of the investigated cases had the needed flow capacity, and the fire resistance of the fan was only documented as sufficient in 4% of the cases. No error was transferred to the controlling system in 83% of the cases for failures associated with the supply air (doors/windows). In 89% of the cases, an error with origin in the ABV-central was not transferred to the controlling system (ABA). Percent 1 9 8 7 6 5 4 3 2 1 System documentation is according to DBI 27[9]/27[1] OK Figure 7 Results for the system failures that were found for the smoke ventilation systems. The OK is only labeled once, but applies to the other columns with the same color. Results for the Warning Systems Correct flow capacity None of the investigated cases had system documentation and drawings that verified that the interconnected system has a built-in redundancy. This is to ensure that if one system were to fail, the other will still be able to function. Even though the requirement is that all systems are composed of certificated components, this was not always the case, as cases of use of nonstandard parts were detected. The error transfer to the controlling system failed in 85 % of the investigated cases. Another significant problem occurred in all of the cases, which was that the noise associated with the operation of the mechanical smoke ventilation system was so loud that it was impossible to hear the sounding from the warning system in that zone. Error transfer from failure in supply air openings Error signal transfer from failure on ABVcentral Documentation for fire resistance of fan

Percent 1 9 8 7 6 5 4 3 2 1 System documentation according to DBI 24[11]/24[12] OK Documentation of sufficient sound level OK Documentation of understandable speech Figure 8 Results for system failures found for warning systems. OK Error transfer to controlling system at power supply failure Soundable warning signal before mecahnical smoke ventilation starts Figure 9 shows the overall outcome of the study (left) and the inspection statistics from The Danish Institute for Fire and Safety Technology. Although the system types are not the same, the discrepancy of the results calls for a different and more thorough inspection in order to create appropriate statistics, as there is a difference between working and working according to the fire safety strategy. That is, simply starting the system for a short period does not account for a proper inspection, as all components and system interdependencies have to be check for appropriate performance and dimensioning. The full details of all the observations in each of the cases are presented in a report by Kærup [17]. ABV, Smoke Ventilation NOT APPROVED A-failure: 7% of the cases B-failure: 1% of the cases AVS, Sprinkler System RELIABILITY: 95.4% [16] Is the fire safety level in the building sufficient? AVA, Warning System NOT APPROVED A-failure: 1% of the cases B-failure: 1% of the cases ABA, Smoke Detection RELIABILITY: 99.1% [7] Figure 9 The overall results for each fire protection system in the building.

CONCLUSIONS The results from the series of in-depth system inspections in buildings with interconnected fire safety systems presented herein are quite disconcerting. The inspections revealed that, even though all the systems that are mentioned in the fire strategy report are installed and are operable, their interdependency and their functionality are often not according to the prescribed design. This means that a lot of effort and money is put into the fire safety design in vain. Furthermore, as there are no inspection procedures or guidelines that require an inspection of the overall functionality of the interconnected fire protections systems, it appears to have a low priority, as it is then perceived to only have a cost associated with the inspection and no visible gain. The lack of inspections in the construction phase, upon commissioning and in the operational phase leads to a lack of information about the fire protection systems, something which in turn makes it close to impossible for the maintenance personnel to secure the correct interconnectivity of these systems. Obviously, there is a challenge ahead when published reports show that the reliability of the certain automatic alarm systems is as high as 99.1%, whereas the statistics from the Aalborg Fire Brigade show that only approximately 3% of alarms were due to fire. The statistics show that approximately 8% of the reasons for the detection of the smoke detection system are due to attitude behavior, where instructions, training and education is one way of reducing the reasons for false alarms. In Denmark, fines have also been introduced for false alarms, both as an incentive to work towards fewer false alarms, but also to recover some of the costs associated with this unnecessary use of the fire brigades. It is emphasized that this is not a critique of the reports published by DBI, but rather a call for a change in the inspection requirements, so that the reliability of the interconnected systems can be as high as for the individual systems. The results also show that we need to consider all the interconnected fire protection systems as one (1) system that has a huge influence on the fire safety level in the building. Still, each different fire protection system should be inspected according to the relevant standard/guideline. In addition, there should also be undertaken an overall inspection that focus on the functionality of the systems, as described by the fire safety engineer in the fire strategy report. REFERENCES 1. Nystedt F., Rantatalo T., and Micheelsen C., Quantifying the Safety Level in the Danish Building Fire Regulations, 4th International Conference on Performance- Based Codes and Fire Safety Design Methods: Proceedings, SFPE, Melbourne, Australia, March 22 2. Danish Energy Agency, Building Regulations, 212 3. Danish Energy Agency, Information on Fire Safety Design (in Danish), April 24 4. Ministry of Defense, Operational regulations for hotels, care facilities, meeting rooms, classrooms, day care centers and shops (in Danish), Order number 212, March 28 5. Aalborg Fire Brigade, Statistics for active fire protection systems, 214 (continuous) 6. Danish Institute for Fire and Safety Technology, DBI Guideline 232: Automatic Fire Alarm Systems, March 29 7. Danish Institute for Fire and Safety Technology, The reliability of automatic smoke detection systems (in Danish), 212 8. National Fire Protection Association, Unwanted Fire Alarms, April 211

9. Brännbäck K., Automatic Fire Safety Systems Safe or False Safety? (in Swedish), Luleå Technical University, November 211 1. Danish Institute for Fire and Safety Technology, DBI Guide 27: Smoke ventilation, 27 11. Danish Institute for Fire and Safety Technology, DBI Guideline 27: Smoke ventilation systems, June 212 12. Danish Institute for Fire and Safety Technology, DBI Guideline 24: Warning systems, May 27 13. Danish Institute for Fire and Safety Technology, DBI Guideline 24: Warning systems, May 211 14. Danish Institute for Fire and Safety Technology, DBI Guideline 4: Automatic Fire Alarm Systems Commissioning, Inspections and Approvals, July 29 15. Klote J.H. and Milke J.A., Principles of smoke management, American Society of Heating, Refrigerating And Air-Conditioning Engineers, Inc., 22. 16. Danish Institute for Fire and Safety Technology, Reliability of automatic sprinkler systems, 212 17. Kærup R., Functionality Inspection and Analysis of Interconnected Fire Safety Systems (in Danish), Technical University of Denmark, Master in Fire Safety Thesis, 213