Application Guideline

Similar documents
ICP Inverter Air Conditioner Application Guideline

ICP Inverter Heat Pump Application Guideline

Attractive. Selling a higher form. (up)selling Guide. Infinity 18VS heat pump & Infinity 19VS air conditioner

Advance Product Data

Infinity 18VS. Heat Pump with Variable-Speed Technology. Variable-Speed, High-Efficiency Heat Pump with up to 18.0 SEER and up to 11.

Relentless efficiency. Real savings.

Infinity 19VS. Air Conditioner with Variable-Speed Technology. Variable-Speed, High-Efficiency Air Conditioner with up to 19.

Infinity Series Air Conditioners

3- to 24-Ton Models. Commercial Packaged Rooftop Units. The most energy-efficient rooftop unit in the industry *

What you need to know about residential furnaces, air conditioners and heat pumps if you re NOT an HVAC professional

Advance Product Data

TECHNICAL SPECIFICATIONS

RSG16**S1M. Split System Air Conditioner 16 SEER

Product Data. S Up to 20.5 SEER / 15.5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound

Infinity 20. Heat Pump with Greenspeed Intelligence. Variable-Speed, Ultra High-Efficiency Heat Pump with up to 20.0 SEER and 13.

Geothermal. Comfort Systems

Geothermal Comfort Systems

cool and comfortable Air Conditioners

A heat pump that redefines comfort and efficiency.

Up to 16.1 SEER, Up to 14.3 EER and Up to 15.4 IEER

An air conditioner that redefines comfort and efficiency.

Infinity 16. Air Conditioner. Energy-Efficient Air Conditioner with up to 16.0 SEER

Introduction. Motor Types

Owner s Information Manual

complete comfort Heat Pumps

Residential Split System Air Conditioners and Heat Pumps Using R-22 Refrigerant

Geothermal Comfort Systems

The Benefits of a Complete Heating and Cooling System.

AND WORRY-FREE PERFORMANCE

Infinity 19 Heat Pump with Puron Refrigerant

Table A-4...Professional and Do-It-Yourself Improvement Expenditures by Homeowner Characteristics: 2007

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Infinity 19 Heat Pump with Puron Refrigerant

Air-Conditioning Buying Guide

2018 LIGHT COMMERCIAL ROOFTOP UNITS. Industry-leading efficiency and innovation to meet your needs

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

The most energy-efficient commercial split system* Commercial Air Conditioners and Heat Pumps SSB/SPB Models

GUTS GUIDE EVOLUTION V AIR CONDITIONER POUND FOR POUND IT DOESN T WEIGH THAT MANY POUNDS

L E N N O X MINI-SPLIT SYSTEMS THE SOLUTION THAT WORKS WHERE OTHERS WON T.

Things to Consider Before You Buy

Infinity 16 Heat Pump with Puron Refrigerant

complete comfort Heat Pumps

EXHIBIT 1. Washington Home Energy Savings Program Measures, Incentives, and Qualifications

Lennox Mini-Split Systems Year-Round Comfort and Performance

Infinity 21 Air Conditioner with Puron Refrigerant

Evolution Extreme Heat Pump

16.0. High-Efficiency Heat Pump Designed with Your Comfort in Mind. Performance Series Heat Pumps with Puron Refrigerant

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Table W-4...Total Improvement Expenditures by Homeowner Characteristics:

Product Data. Fig. 1 - Unit 50VR -A

Performance 14 Packaged HYBRID HEAT Dual Fuel System with Puron Refrigerant

complete comfort Heat Pumps

Product Data. 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS

incomparably cool XC21 The most quiet and efficient central air conditioner you can buy*

XP21 The most quiet and efficient heat pump you can buy*

PRECISION INVERTER-DRIVEN. We Thought of Everything... And Then Some.

WEATHERMAKER INFINITY 58MVP

Product Data. 224ANS PREFERREDt SERIES HEAT PUMP WITH PURONr REFRIGERANT 1-1/2 TO 5 NOMINAL TONS INDUSTRY LEADING FEATURES / BENEFITS

YORK AFFINITY VARIABLE CAPACITY RESIDENTIAL SYSTEMS

Product Data. 50ZPB Single---Packaged Air Conditioner System With R---410A Refrigerant Single Phase 2 to 5 Nominal Tons (Sizes )

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Increase your flexibility.

HIGH EFFICIENCY WEATHERMAKER 38TPA

Premier Dealer Collection Dealer Guide. Trane American Standard. The ADP Advantage...

COLEMAN ECHELON VARIABLE CAPACITY RESIDENTIAL SYSTEMS

perfectly efficient SLP98V The most efficient and quietest furnace you can buy.*

HEAT PUMPS. Efficient Comfort For Every Season

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Series. Heat Pumps. Two-Stage, Extra-Efficient Heat Pumps with up to 19.0 SEER and up to 9.5 HSPF. Infinity

Infinity 15 Packaged Heat Pump System With Puron Refrigerant

Promoting quality installation of central AC (and heat pump) systems

LONG LINE SET APPLICATION R-410A

Product Data. PA4Z SINGLE -PACKAGED AIR CONDITIONER SYSTEM WITH PURONr (R -410A) REFRIGERANT SINGLE PAHSE 2 TO 5 NOMINAL TONS (SIZES )

GEOTHERMAL COMFORT SYSTEMS

complete comfort Heat Pumps

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

The XP21 raises the bar for efficiency and comfort.

Owner s Information Manual

That s why we call it Smarter from the Ground Up.

4HP15L PRODUCT SPECIFICATIONS HIGH EFFICIENCY SPLIT HEAT PUMP SYSTEM UP TO 15 SEER & 9.0 HSPF COILS COMPONENTS COMPRESSOR WARRANTY CABINET DESIGN

K sin. Mini Split Air Conditioners and Heat Pump

Product Data OBM/OVM. MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH THE LATEST IN OIL FURNACE TECHNOLOGY

InverterFlex SERIES InverterFlex Systems condition up to five rooms

Air Handlers and Indoor Coils Up to 20 Tons. CB* and C* Models. True performance and rugged durability

THE WORLD S MOST EFFICIENT HEAT PUMP

Product Data. Fig. 1 - Unit 50XL -A

Installation Instructions

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Xc21 air conditioner up to seer Xc21

DUCTLESS FULL LINE CATALOG

Infinity ICS Gas Furnace with IdealComfort Technology

Product Data. Fig. 1 - Unit 50VG -A

Product Data INDUSTRY LEADING FEATURES / BENEFITS. BH13NA SINGLE -STAGE HEAT PUMP WITH PURONr REFRIGERANT. Efficiency S S Reliability S

The XC21 delivers the ultimate in comfort.

Performance and Reliability. CB*, C* and TA* Models

Ductless Mini-Split Systems. Comfort... where you need it, when you need it

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

JS5BD-K(A,B) Series High Efficiency Air Conditioner 13+ SEER Residential System Ton Capacity

Transcription:

24NA9 Infinityr 19VS Variable Speed Air Conditioner with Puronr Refrigerant Application Guideline The Infinity 19VS variable speed air conditioner provides a flexible alternative to high priced variable speed systems on the market today, as well as 2 stage products currently being offered. Its highly efficient, smaller and lighter design offers many benefits to dealers and homeowners alike. This document outlines the recommended application parameters and differences from other products. Overview The Infinity 19VS is an inverter driven variable speed air conditioner designed for the ducted residential market. Its size and weight advantage makes it easier for dealers to handle and stock, and allows for high-efficiency installations in tighter spaces than previously possible. It is designed to complement the dealer s product offering by adding a new, unique variable speed air conditioner to compete in this expanding market. Benefits of Variable Speed Variable speed systems provide several benefits to the homeowner. The capacity range of the system allows it to more closely match the home s needs as conditions change. This increases indoor comfort by running longer comfort cycles at lower speeds thus eliminating up and down temperature swings. Longer cycles at lower speeds also translate into higher efficiency, and lower overall sound levels both indoors and outside. The wide capacity range also improves zoning and dehumidification capability compared to 2 stage and 1-stage systems.

Comparison to Infinity 17 SEER 2-stage Air Conditioner Systems With the introduction of the Infinity 19VS heat, you now have a variable speed option in a straight-cool product. This new model offers several benefits compared to two-stage systems. Below is a comparison of the new 19VS compared to the Infinity 17 twostage model: Infinity 19VS with Touch Control 24VNA9 Infinity 17 two-stage 24ANB7 SEER Up to 19 Up to 17 EER Up to 12.5 Up to 13.3 Compressor Variable-speed Rotary 2-stage Scroll Type Compressor 5 stages as low as 25% 2 stages as low as 70% Stages Line length Up to 100ft equivalent length Up to 250ft equivalent length Fan motor Compact ECM(Brushless DC) Standard PSC No module attached Inverter driven Ambient range Cool: 40º-115ºF communicating (4.4º-46.1ºC) Cool: 55º-115ºF non-communicating (12.8-46.1ºC) Cool: 55º-125ºF (12.8º-51.7C) Low ambient cooling capable with Infinity Control or kit Not initially qualified for Low ambient cooling Sound 56dBA 72 dba 67dBA 72 dba Basepan sizes 2 and 3 ton - 23 x23 2 ton - 31.25 x 31.25 4 and 5 ton 31.25 x 31.25 3-5 ton - 35 x35 Infinity Communicating indoor for full 5-stage functionality with Touch Control Touch Control AHRI Ratings with Performance 2-stage indoor for 2- stage functionality with 2-stage noncommunication thermostat Infinity Communicating indoor for 2-stage functionality with Performance 2-stage indoor for 2-stage capability with 2- stage non-communicating thermostat

Infinity 19VS System matching This air conditioner unit provides the most customer benefit and highest efficiency when installed as a complete Infinity system including Infinity Touch Control. Acceptable system combinations will be listed in the AHRI and in My Carrier Ratings database on HVACpartners. For increased system flexibility, and increased replacement opportunities, this outdoor unit is also designed to work with standard non-communicating thermostat inputs. Combination ratings are available with some non-communicating 2-stage indoor units such as the FV4C fan coil and 2-stage furnace/coil combinations. When utilizing this type of indoor unit, a standard non-communicating 2-stage thermostat is required, and the system will operate with 2-stage functionality. Compatibility with existing indoor equipment (also see attached flowchart) Because this unit is designed to work with communicating or standard thermostat inputs, it opens up opportunities for replacement applications. However, the indoor components must be of suitable size and configuration. Existing Infinity communicating indoor equipment The 19VS is backward compatible with all Infinity communicating indoor equipment. However, the old style Infinity wall control is not compatible with the 19VS unit in communicating mode (See Figures 1 and 2). The software in the old style control will not recognize the outdoor unit. For full system capability with older indoor equipment, the wall control must be upgraded to the Infinity Touch control with appropriate software. Figure 1. Old style control Figure 2. Touch control Old style control Not compatible with 19VS Touch Control Compatible with 19VS Check ratings for system matches with FE fan coil. These ratings can be applied to old and new FE fan coils units.

For existing furnace applications, the furnace must have a suitable blower size. Furnace coils built in 2006 or newer can be straight matched to the outdoor unit tonnage or one size larger*. A Puron refrigerant TXV is required on the furnace coil. Furnace coils built between 2005 and 1992 may be straight matched, one or two tonnage sizes larger than the outdoor unit tonnage*. A Puron refrigerant TXV must be added to the indoor coil. Existing 2-stage indoor equipment The 19VS is capable of operating with a standard 2-stage thermostat and noncommunicating 2-stage indoor equipment. In this case, the outdoor unit will be wired as a 2-stage system, and will operate as a 2-stage system. Combination ratings will be available with some furnace/coil and FV4C fan coil combinations. These ratings will apply to both new and existing equipment of like model numbers. An older FV4(A,B) of like size may be used. Unlike the 18VS heat pump, the model plug in the outdoor unit does not need to be changed in straight-cool applications. An older FK or 40FK fan coil may be used with the addition of a Puron refrigerant TXV. The model plug in the outdoor unit does not need to be changed in straightcool applications For existing furnace applications with the 19VS, the furnace must have a suitable blower size and staging capability. Furnace coils built in 2006 or newer may be straight matched to the outdoor unit tonnage or one size larger*. A Puron refrigerant TXV is required on the furnace coil. Furnace coils built between 2005 and 1992 may be straight matched, one or two sizes larger than the outdoor unit tonnage*. A Puron refrigerant TXV must be added to the indoor coil. * Examples Straight matched to outdoor unit tonnage 3-ton 19VS unit with 3-ton furnace or fan coil One size larger indoor 3-ton 19VS with 3.5 ton furnace or fan coil 2 sizes larger indoor 3-ton 19VS with older 4 ton furnace coil

Existing 1-stage indoor equipment The 19VS will work with a 1-stage thermostat as a 1-stage system with suitable indoor coil and fan until the indoor components can be upgraded to provide full variable speed functionality. If the indoor furnace coil was built in 2006 or after, it may be straight matched or one size larger than the outdoor unit tonnage*. If the furnace coil was built between 2005 and 1992, the furnace coil may be straight matched, one or two sizes larger than the outdoor unit tonnage*. A Puron refrigerant TXV is required on the indoor coil. In existing fan coil applications, if the unit was built in 2006 or after, it may be straight matched or one size larger than the outdoor unit tonnage*. If the fan coil was built between 2005 and 1992, it may be straight matched, or one size larger tonnage than the outdoor unit tonnage*. A Puron refrigerant TXV is required on the indoor coil. Line set limitations The 19VS is qualified for line sets up to 100ft. equivalent length Lift limitations: Outdoor above indoor: 100 ft. Outdoor below indoor: 2 ton 3 ton 4 ton 5 ton 80ft 80ft 70ft 60ft See Product Data for line set diameter requirements Sound The 19VS uses a pressure equalizer valve (see Figure 3). It is designed to equalize pressures across the rotary compressor in the off-cycle to ensure easier starting. During the equalization process, a hissing sound may be heard by customers. This sound is normal, but the customer should be made aware to avoid nuisance callbacks. Figure 3. Pressure Equalizer Valve *Examples Straight matched to outdoor unit tonnage 3-ton 19VS unit with 3-ton furnace or fan coil One size larger indoor 3-ton 19VS with 3.5 ton furnace or fan coil 2 sizes larger indoor 3-ton 19VS with older 4 ton furnace coil

EER Rating vs. Equipment payback The published EER rating represents efficiency of cooling products at peak load, or 95ºF (35ºC). This rating is driven by utility companies that are concerned with power consumption at peak demand periods. In most locations, peak load is experience for a very short time during a year (see charts below). The Infinity 19VS system is designed for high efficiency at lower load conditions, which represents the vast majority of the cooling season. This is why the SEER ratings are high, but the EER is not as high on all sizes as other highefficiency products. Focusing on SEER allows the smaller unit design, and competitive price compared to high EER variable speed products. Some incentives and local rebates contain an EER requirement, while others do not. A cost payback analysis should be done to compare benefit of a rebate with higher EER component vs. initial cost and energy savings. Things to consider regarding rebates containing EER requirements: (Cost of qualifying EER equipment) (rebate amount) = Cost of Infinity 19VS equipment = Yearly operating cost of qualifying EER equipment using Opcost calculator = Yearly operating cost of 19VS equipment using Opcost calculator = (Difference in system cost) /( yearly operating cost of 19VS yearly operating cost from high EER equipment) = The end number above represents number of years for payback of the additional investment for equipment to achieve the rebate. Avg. Percent of Hours 95 F and Above 27.00% 2.22% 0.18% 0.08% 6.25% 0.72% 7.83% 1.22% 1.47% 0.42% St Louis, MO Baltimore, MD Orlando, FL Phoenix, AZ Dallas Ft Worth, TX Minneapolis, MN Sacramento, CA Portland, OR Richmond, VA Atlanta, GA Avg. Percent of Cooling Hours 70 to 90 F 97.8% 99.8% 99.9% 73.0% 93.7% 99.3% 92.2% 98.8% 98.5% St Louis, MO Baltimore, MD Orlando, FL Phoenix, AZ Dallas Ft Worth, TX Minneapolis, MN Sacramento, CA Portland, OR Richmond, VA

1992-2005 Straight Match or one size larger than outdoor tonnage Puron Refrigerant TXV required Straight match, 1, or 2 sizes larger than outdoor unit tonnage Puron Refrigerant TXV required Infinity 19VS Air Conditioner System Matching with Existing Indoor Equipment Multi-Stage See ratings for FV4C, FE matches 5 stages with FE and Touch Control 2 stages with FV and 2-stage stat Puron refrigerant TXV required on indoor 2006 Present Multi-Stage or Single Stage? Single-Stage One stage of operation with stat until indoor can be upgraded Straight match or one size larger indoor Puron refrigerant TXV required on indoor Wire as single stage unit. Set airflow to 350-400 cfm/ton 2006-Present or 1992-2005? 1992-2005 Multi-Stage or Single Stage? Multi-Stage See ratings for FE matches Model plug change not required for FV4B/FK/ 40FK indoor in cooling only applications FV/FK - match size same as current FV Puron refrigerant TXV required on indoor 2 stages with FV/FK and 2-stage stat Before 1992 Not Compatible Single-Stage One stage of operation until indoor can be upgraded Indoor straight matched or one size larger than outdoor Puron refrigerant TXV required on indoor Wire as single stage unit. Set airflow to 350-400 cfm/ton Infinity 19 VS AC w/ Existing Indoor System or Furnace? Furnace Variable Speed Communicating Backward Compatible to any Infinity Capable furnace Infinity Touch Required for Communicating Operation Infinity Touch SW Update may be required Full functionality with Infinity Touch Control 2006 Present VS, 2-Stage N.C., or Single Stage? Single Stage 1-Stage Operation until Indoor can be upgraded 1-Stage Operation with 1-Stage Thermostat Set airflow to 350-400 cfm/ton Indoor Coil 2006-Present or 1992-2005? * Examples Straight matched to outdoor unit tonnage 3-ton 19VS with 3-ton furnace or fan coil 1 size larger indoor 3-ton 19VS with 3.5 ton furnace or fan coil 2 sizes larger indoor 3-ton 19VS with older 4 ton furnace coil 2-Stage Non-Communicating 2-Stage Operation with 2-Stage Thermostat Check AHRI Ratings for current furnaces High Speed Airflow; 350-400 cfm/ton Low Speed Airflow; 70-80% of High Stage Before 1992 Not Compatible

Copyright 2016 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 05/16 Catalog No. 24VNA9---01AG Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New