Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november

Similar documents
ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

Container Refrigeration

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS REFRIGERATORS OPERATING INSTRUCTIONS

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

User Guide ems25plus. Page 1. Normal operation. Product interface

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

MODEL URS-1: FACTORY RETROFIT PROGRAM

ER52 - Evaporator Controller

Product Features Technical Training 2007

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

OPERATION AND MAINTENANCE MANUAL

OPERATING INSTRUCTIONS

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Unit Controller (UC8) Quick Reference Operation and Fault Diagnosis

AC&R Controller RWR Basic Documentation VR2002 for water to water heat pump units

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

MR3CCUHV Temperature/Defrost Control

Index. 1. General description of the application Types of units controlled Types of regulation Condensation...

GeneSys Air-Cooled Screw Compressor Chiller

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

ER65 - Mini Rack Controller Electronic Refrigeration Line

MLCFC HMI NAVIGATION MANUAL

Thermometers and temperature controllers

CONTROL PANEL INSTRUCTIONS RSQ-4

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

CWB CHILLERS. User Maintenance Manual Cooling Capacity from 40 to 160 tons Scroll compressors-r410 Refrigerant. CWB-R Air-cooled water chillers

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Precise Temperature Control; Compact Footprint

User manual CLIMATIC 50 - CHILLERS

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN

CAREL IR33+ CONTROLLER

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS OPERATING INSTRUCTIONS

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

TWLC - Tempered Water Logic Controller. The Intelligent Control

FX BLAST CHILLER ISO ISO 9001

User's Guide. CTS6000 control panel

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

Multi Boiler Guide. Kit #

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller

User Manual Ichill 200 L/D (Firmware version 1.7)

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

Air-condensed water chillers and heat pumps YLCA / YLHA 100, 120 and 150

AUDAX Air-water heat pumps reversible with inverter single and three-phase

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

All alerts are still logged as alarms and also show up in the current alarm list.

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

Refrigerated air dryers

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

Technicians Manual Single Compressor

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

MicroTech Series-200 Flooded Screw Chiller

Pre-Cool and Free- Cool Fan Control

Outstanding Performance; Application Flexibility

Water-Cooled Scroll Compressor Chillers

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

Air-Cooled Scroll Compressor Chiller

Water-Cooled Scroll Compressor Chillers

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Blue Box Epsilon Echos +

INSTALLATION & USER MANUAL

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

UNIT CONTROLLER 8 (UC8) Troubleshooting guide

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document

Controls manual. Central Air-Sourced Liquid Chiller & Heat Pump MODELS 3CA22 3CA65 3CA127 3CA32 3CA83 3CA147 3CA45 3CA97 3CA169 3CA53 3CA113 3CA203

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

DT90 DIGITAL ROOM THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Inverter scroll compressors VZH hybrid manifold

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Digital Precise Air Control - DPAC

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

NA G µair CONNECT 2

Scop Advance DCI

Air and Water cooled scroll chillers & heat pump

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

Water-Cooled Scroll Compressor Chillers

Transcription:

Service Manual Chiller unit MQH R 410A Release Date Rev Review Date november 2008 ----- -----

MQH R410A ELECTRONIC CONTROL CONTROL PANEL The control panel allows the user to carry out all the operations related to the use of the controller, in particular: To set the operation parameters To manage alarms To check the status 1 2 3 1 Display Display the status of the unit, entering/leaving water and ambient air temperatures, compressor discharge pressure, setpoint, running times, alarm code, alarm history etc. 2 Enter Key Select the display value or to program and modify system values 3 Scroll Key Scroll the menu 1 TECHNICAL CHARACTERISTICS 1.1 ELECTRICAL PERFORMANCE Maximum Rating Item Spec. Rated input voltage 24 V, Single-Phase, 50 Hz or 60 Hz. Protected with on board fuse Operating input voltage range 20.4 26.4 Vac No damage input voltage range 16 32 Vac Maximum current 0.5A @ 24Vac Minimum power factor 0.92 Power consumption in stand-by < 5W 2

1.2 GENERAL SPECIFICATIONS The control box is in compliance with European current standard about emissions and immunity (e.m.c ). The minicac control board mounted in a IP20 plastic case. The plastic is in compliance with UL94V0. Flash memory is used to store the program, enable redownload via 10 bit A/D converter in factory and at site. During power failure with a duration more then 40 msec, the control goes off and will random restart after power comes back according the dip 5 position. 1.3 COMPATIBILITY WITH OTHER PRODUCTS AND SYSTEMS 1.3.1 ELECTRICAL INTERFACES Analogue Input N Type B1 NTC B2 NTC B3 NTC B4 NTC/ratio B5 NTC/ratio Digital Input N Chiller ID1 Remote Unit Start/Stop ID2 Cooling/Heating mode selection ID3 Fan motor overload (or 2nd compressor protection) ID4 Compressor motor protection ID5 Flow switch - Water diff. pressure switch ID6 Low pressure switch ID7 High pressure switch ID8 Night Mode/Second setpoint Digital output N Chiller Type of relay Type (AC motor rating) 1C-O Compressor 2A @ 230Vac N.A 2C-O Fan high speed or 2nd comp 4A @ 230Vac N.A 3C-O Fans motor or low speed See note 1 TRIAC (see note 1) 4C-O Antifreeze heater 2A @ 230Vac N.A 5C-O Reversing valve 2A @ 230Vac N.A 6C-O Pump 4A @ 230Vac N.A 7C-O Unit alarm relay 2A @ 230Vac N.A 3

2 START-UP & OPERATING INSTRUCTIONS ABBREVIATIONS SYMBOL BMS C1 CP CSPT CDCO DEWT EP EWT EWTM FP FS HPC HSPT HDCO LO LOAT LSL LWTM LWT MCB NM OAT OD OFAN PGI RC RV SPT ST tc TH Eph td THC BYP EPCR EPIC EPCC OPEr LOAt DESCRIPTION Building management system Compressor Condensing pressure Cooling setpoint temperature Cooling compensation offset EWT derivative DEWT = (EWT(t) EWT(t-1))/dt C/min Evaporating pressure Entering water temperature Maximum entering water temperature Freeze protection (minimum LWT) Flow switch to detect sufficient water flow High pressure cut-out Heating setpoint temperature Heating compensation offset Low fan speed Low level of the external temperature Low speed limit Minimum leaving water temperature Leaving water temperature Main control board Night mode Outdoor air temperature Outdoor Outdoor fan Percent of glycol in the water Reverse cycle (heat pump) Reversing valve Setpoint temperature Standard model (cooling only) Comp timer Trace heater for frost protection Low pressure heating adjust Defrosting duration Coil heater TXV by-pass during defrost Evaporating Pressure Calculation (function of OAT) Evaporating Pressure Iced Coil EP Clean Coil Parameter for mode selection in standard parameter OAT limit valve for THC activation 4

2.1 PRELIMINARY CHECK The checks listed below shall be performed before starting the unit. 2.2 BEFORE START-UP Before you start-up the unit, you must check the DIP switch setup. Check the section of power supply and grounding cables; make sure that terminals are tightened and check the correct operation of contactors, with the master switch open. Check that any voltage and phase variation in the power supply dose not exceed the prefixed thresholds. Check that the components of the external water circuit (user equipment, filters, power supply tank and reservoir, if any) have been installed properly, and according to the manufacture s instructions. Check the filling of the hydraulic circuits, and make sure that the fluid circulation is correct, without any trace of leaks and air bubbles. Check that the direction of rotation of the pumps is correct, and that fluids have been circulating for at least 4 hours. Then, clean the filters on the suction side of the pumps. Adjust the liquid distribution network in such a way that the flow rate is within the specified range. Check that the water quality is up to the specifications. Check that oil heaters, if any, have been turned on at least 4 hours before (it is mandatory if the temperature is under 15 C). DIP SWITCH CONFIGURATION DIP NO. POSITION OFF POSITION ON FACTORY SETUP 1 U BMS MODBUS ON 2 Not used OFF 3 No auto restart Auto Restart after power failure OFF 4 No OAT compensation OAT compensation ON 5 Cooling only unit Heatpump unit ON 6 No auto fan Auto FAN OFF 7 Pump ON when unit is ON Pump always ON OFF 8 Refrigerant R 407C Refrigerant R 410A ON ** Turn ON the main switch of the power line. 5

Display C1 C1H DEIC OFF COOL HEAT Description When compressor is operating Compressor in heat mode defrost in operation Off mode Cool mode with no compressors on Heat mode with no heating on 2.3 STARTING AND USING THE UNIT To start/stop the unit press for 5 secs the SCROLL key. To remotely stop the unit, open the connection between No. 7 and No. 8 on the terminal board. During the normal operation, if the connection between No. 5 and No. 6 terminal is closed, the unit will operate in heating mode. When the connection is opened, the unit will operate in cooling mode. If connection 5-6 is open, then OPER mode can be selected by display. To modify operative mode or the setpoints, press both ^ and > keys at the same time for 5s, then the OPEr message appears on the display. The parameters are scrolled using the ^ button and selected using the > button. When selected, the values can be changed by using the ^ button to scroll from the present value to max then min and can be selected by pushing the > button. After selection the menu will return to the beginning of the same parameter change menu. If no button is pressed for 10s the display reverts back to normal mode. 6

TABLE LIST OF STANDARD PARAMETERS Display Meaning Min. value Max value Step Default value OPEr Cooling/Heating mode selection COOL HEAT --- COOL CSP Cooling Setpoint CSPL 23 0.5 12 HSP Heating Setpoint 20 47 1 40 gly Glycol % 0 30 10 0 nigh Night mode 1 4 1 2 COAL CSPT compensation low limit 10 30 2 20 COAH CSPT compensation high limit 20 36 2 30 CDCO CSPT compensation 0 8 1 6 HDCO HCSPT compensation 0 15 1 8 HOAL HCSPT compensation low limit -10 10 1-5 HOAH HCSPT compensation high limit 0 20 1 10 HPCE 1 auto reset for HPC alarm 0 1 1 0 ND Night mode differential 0 15 1 2 NFC Night mode fan change -4 4 1 2 Id Identification address 0 255 1 0 F0 Factory parameter 0 9 1 0 F1 Factory parameter 0 9 1 0 F2 Factory parameter 0 9 1 0 7

TABLE LIST OF FACTORY PARAMETERS (DEFAULT VALUES ACCORDING TO DIP 8 SELECTION) If you want to change the parameter value, you must get the password from the factory or your authorized service support. Display Meaning Unit Min. value Max value Step Default value R410A CSPL Minimum Cooling setpoint C -5 14 1 8 FL Fluid paremeter 0 2 0.5 0 CPL Condensing Pressure Limit bar 0 50 0.5 40 TC0 Min. condensing temperature C 0 100 1 20 TC1 Condensing temperature setpoint C 0 100 1 30 TC2 Max condensing temperature C 0 100 1 50 rpml Min. Triac output % 0 100 5 20 rpmh Max Triac output % 0 100 5 100 OAT1 Low OAT value in heating fan control C 0 50 1 15 OAT2 High OAT value in heating fan control C 0 50 1 30 LOL EP protection correction in cooling bar 0 1 0.2 0.4 EWTn EWTM max EWT (only in cooling) C 16 40 1 24 Eph Low pressure heating adjust bar 0 1 0.1 0.3 tde Defrost cycle maximum duration min 2 10 1 5 dd Delay time for defrost cycle min 10 60 5 35 OCTi OCT defrost start value C -10 10 1-3 OCTe OCT defrost exit value C 5 30 1 12 CPe CP defrost exit value bar 15 40 1 34 EPi EP defrost enter value bar 1.8 10 0.2 5.4 COF Off comp exiting defrost cycle flag 0 1 0 b4 B4 analog input type ntc rat none Ntc b5 B5 analog input type ntc rat none rat During normal operation the current value of entering water temperature is displayed flashing alternatively with the current status. To display other useful data, go to level 1, use the ^ button to scroll the menu, and use the > button to select the display value. 8

DISPLAY DATA PARA READING (PArA) HRS RUNNING HOURS (HRS) Code Parameter Meaning Code Parameter Meaning DE TO (Triac output) CSPT HSPT cooling setpoint enabled heating setpoint enabled C1 tc1 Compressor 1 running hours x 10 Compressor 1 running hours by the last reset td last defrosting time SENSOR READING (SEnS) Code Parameter Meaning EWT entering water temperature LWT leaving water temperature CP discharge pressure EP suction pressure CPS saturated discharge temperature EPS saturated suction temperature OAT room air temperature OCT sensor temperature in coil ALARM CODE READING Code Parameter Meaning ALARM see last alarm exhisting LOG LAST 10 ALARM (LOG) Code Parameter ALARM Code Parameter Meaning STATUS READING (STat) see alarm list Meaning C1 Compressor 1 on/off RV REVERSING VALVE Rv on = heating mode Rv off = cooling mode EH ON or OFF Pump Pump on/off OFAN Fan on/off deic defrost in operation MODE OFF or COOL or HEAT 9

If an alarm is occurred, the alarm code is displayed, but after 30, even if the alarm is still active, the display shows again the mode but Alarm message is displayed for 2 every 10 when an alarm is active. When we enter in Alarm list, the first alarm code displayed is the last occurred. ALARM SUMMARY Fault as on display ADC CPF EPF REF CPnc EPnc CFC1 EWTH EWTL LWTH LWTL OATH OATL OCTH OCTL HP HPC LP LO HI FS CF1 OF1 PF LOu ConF Fault description ADC error CP transducer failure, out of range EP transducer failure, out of range Refrigerant leak- low pressures CP transducer failure, no change error EP transducer failure, no change error CP and EP no change, compressor not operating (burn out or phase change) EWT entering water temperature sensor short circuited EWT entering water temperature sensor short disconnected LWT entering water temperature sensor short circuited LWT entering water temperature sensor short disconnected OAT outdoor air temperature sensor short circuited OAT outdoor air temperature sensor short disconnected OCT coil temperature sensor short circuited OCT coil temperature sensor short disconnected High pressure protection, automatic reset for first three times High pressure cut-out Low pressure limit, unit cut out Leaving water temperature below allowed limits EWT is too high Flow switch opens, low water flow CF1 input open, compressor 1 overload OF1 input open, outdoor fan overload PF input open, pump internal overload Low water volume Not allowed configuration 2.4 CHECKING THE OPERATION Check the following: The temperature of the water entering the evaporator. The temperature of the water leaving the evaporator. The level of the water flow rate in the compressor and in case of stabilized operation. The fan's current absorption. 10

Check that the condensing and evaporation temperatures, during operation at high and low pressure detected by the pressure gauges of the refrigerant, are within the following range: (on the units not provided with HP/LP pressure gauges for the refrigerant, connect a pressure gauge to the Schreader valves on the refrigeration circuit). HP LP side Approx. 13 to 18 C above the temperature of the air entering the condenser, for R 410a units. Approx. the difference between the temperature of the leaving water and saturated evaporating temperature must be in the 2-4 C for R 410a units. 2.5 SYSTEM DIAGNOSTICS AND OPERATION AT FAULT CONDITIONS FAULT RESPONSE LWT sensor failure If in cooling then stop machine EWT sensor failure Use EWT = LWT + 5 EWT & LWT failure together Stop machine OAT sensor failure Use OAT = 35 (cooling) 8 (heating). Variable speed in heating always in maximum speed CP sensor failure Fans to max speed when OAT > 20 C Fans to low speed when 15 C < OAT < 20 C If OAT < 15 C, stop the unit in cooling only Disable vs. In heating, end defrost only with OCT > OCTe or Td > Tde EP sensor failure In cooling mode, correct CSPT to CSPT > FP + 7 In heating, if OAT < 10 C start defrost routine every 40 mins and end defrost routine after 90 sec. OCT failure or CP & OCT failure In heating, if OAT < 10 C start defrost routine every 40 mins and end defrost routine after 90 sec. Variable speed in cooling: always in maximum speed. EP & CP failure Stop the unit 11