Air-Cooled Condenser. Installation Instructions. Revision Date: 12/21/98

Similar documents
Installation Instructions. Revision Date: 05/16/12

HE S Series TUBE-ICE MACHINE INSTALLATION & START-UP INSTRUCTIONS. Part Number: 12A4171S0702

10TA TUBE-ICE MACHINE

05TA TUBE-ICE MACHINE

Installation Instructions

REFRIGERANT PIPING SYSTEM

Installation Instructions

Condensing Unit Installation and Operating Instructions

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Owner s Manual Therma-Stor II Heat Recovery System

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Condensing Unit Installation and Operating Instructions

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

DUAL VOLTAGE ICE BOX CONVERSION SYSTEM 120 VOLTS A.C. & 12/24 VOLTS D.C. MODELS: SCQT-4408F-U1-L SCQT-4408F-U1-I OWNER'S GUIDE

Instruction Manual. Modular Crescent Cuber Models KM-901MAJ, MWJ, MRJ/3 KM-1100MAJ, MWJ, MRJ KM-1340MAJ, MWJ, MRJ/3 KM-1601MRJ/3. hoshizakiamerica.

Installation Instructions

WineZone Ceiling Mount Ductless Split 15

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

Hoshizaki America, Inc.

Air Cooled Condenser Installation and Operating Instructions

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Installation Instructions

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

FSW SECTION. Product guide. Thermostats, Pressure Switches & Fan Speed Controls. E SECTION For more information visit

RDT Refrigeration Book

49 Danfoss Thermostat Kits Ranco Varifix Kits

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

Instruction Manual. Modular Flaker Models FD-1001MAJ-C, MRJ-C F-1501MAH(-C), MWH(-C), MRH(-C) F-2001MWH(-C), MRH(3)(-C), MLH(-C) hoshizakiamerica.

Installation, Operation, and Maintenance Information

Hoshizaki America, Inc.

Hoshizaki America, Inc.

Instruction Manual. Modular Crescent Cuber Models KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3

OPERATING INSTRUCTIONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

APPLICATION DATA SHEET

DESIGN STANDARDS SECTION 15600

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Installation Instructions

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

Installation Instructions

R.A.S.E.R.S System. Installation Guide

INSTALLATION INSTRUCTIONS

Series 6, Vertical Floor-Mount Units

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

SECTION (15530) - REFRIGERANT PIPING

Danfoss Scroll for Refrigeration MLM / MLZ

Installation Instructions

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Installation Instructions

For more Parts Information:

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

INSTALLATION MANUAL. Series 322 Ice Cube Machine SPECIFICATIONS UNPACKING. Series 322 Ice Cube Machine Installation Instructions

INSTALLATION INSTRUCTIONS

Hoshizaki America, Inc.

Installation Instructions

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

C13-Series Engineering Guide

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

T P A 120 S 4 S N 1 Y

MODULAR CRESCENT CUBER

MINI SLIMLINE COOL VUY-A VUY-A

Instruction Manual. Stackable Crescent Cuber Models KMH-2100SWJ3, SRJ/3. hoshizakiamerica.com

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

Instruction Manual. Modular Crescent Cuber Models KM-340MAJ, MWJ KM-515MAJ, MWJ, MRJ KM-650MAJ, MWJ, MRJ. hoshizakiamerica.com

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

Residential Piping and Long Line Guideline

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION INSTRUCTIONS

38LB/38LF AIR COOLED CONDENSING UNIT

Installation Instructions

SECTION (15530) - REFRIGERANT PIPING

Service Step by Step Trouble-Shooting Check-List

Hoshizaki America, Inc.

Commercial High-Efficiency Condensing Units

PAJ3. Product Specifications

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Horizon Elite Ice Machine Installation Instructions for Remote Condensing Unit

SPXB-HW Series Single Package Vertical Unit Cooling with Hot Water Heat 1 through 2 tons, up to 47,800 BTUH Heating

Equipment Alert. P-Trap Must Be Installed to Exhaust or Warranty will be Voided. Refer to this Manual for installation Instructions

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

HEAT PUMP INSTALLATION MANUAL

Horizon Elite Ice Machine Installation Instructions for Remote Condensing Unit

Instruction Manual. Modular Cubelet Serenity Series. Models FS-1001MLH-C with SRC-10H FS-1022MLH-C with SRC-10H FS-1500MLH-C with SRC-14H

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Instruction Manual. Low-Profile Modular Crescent Cuber. Models KML-325MAJ, MWJ KML-500MAJ, MWJ KML-700MAJ, MWJ, MRJ. hoshizakiamerica.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Series 6, Vertical Floor-Mount Units

Hoshizaki America, Inc.

Installation Instructions

Transcription:

Air-Cooled Condenser Installation Instructions Revision Date: 12/21/98

! WARNING! These installation guidelines must be followed to obtain reliable operation from air-cooled ice machines. If these guidelines are not followed, the compressor warranty will not be honored.! WARNING! 1. Use only Vogt approved condensers. Any exceptions to this policy must be obtained in writing prior to installation and operation of the ice machine. 2. Outdoor condensers must be installed with vertical air flow. Indoor condensers used for heat recovery may be installed with either horizontal or vertical air flow. 3. The condenser must be mounted above the ice machine, with liquid refrigerant from the condenser outlet draining freely (1/4 per foot slope) in the direction of normal operating flow (back to the ice machine) with no traps in the liquid line. 4. Flooding head pressure controls such as Alco Headmaster are not to be used, since they cause excessive subcooling of the returned liquid refrigerant and interfere with reliable ice harvest. 5. The discharge and liquid lines must be insulated with 1/2 thick Armaflex insulation or equal. 6. Horizontal runs in the discharge line should slope 1/4 per foot in the normal direction of flow (away from the ice machine). 7. Traps must be installed in discharge lines at the base of all vertical risers. There should be no intentional traps in liquid lines. Trap volume should be kept to a minimum. Typical details are shown in FIGURE-10. Long vertical runs should have traps every 20 feet. 8. Use only ACR grade copper pipe, Type L. Recommended line sizes are shown in TABLE-3. 9. Distance between ice machine and condenser must not exceed 150 equivalent feet. Refer to Condenser Equivalent Line Size worksheet. (see TABLE-5) 10. Condensers must be provided with a cold weather valve kit per FIGURE-9A. These valves allow one-half of the condenser to be disabled in cold weather. Running the ice machine with one half the condenser in cold weather makes it easier to maintain minimum necessary condensing pressure, particularly in windy conditions. The coil thermostat should be set to close at 35?F. for multiple fan condensers or 50?F for single fan condensers. 11. Condensers with multiple fans must be provided with a thermostat to turn off unneeded fans in cold weather. Turning off unneeded fans reduces on-off cycling of the fan(s) and allows for a steadier condensing pressure. The fan thermostat should be set at 50?F. 12. When extreme cold conditions are expected or encountered (temperatures below 0?F and wind greater than 15 MPH), it may be necessary to install a protective enclosure around the condenser. Other apparatuses such as louvers may be used. Contact the factory for suggestions. 2

13. After installation, the field-installed lines are to be evacuated to a vacuum of 500 microns or less and held for at least one hour. Use ¼ access connection located on compressor discharge line and liquid return line (32). After the vacuum pump is removed, vacuum should hold at 500 microns or less for at least 5 minutes and the lines pressurized with R-22 to 25 psig minimum. 14. The volume of refrigerant supplied with the machine is sufficient to fill the condenser and condenser lines when length of pipe (one way) is 75 feet or less. When the length of lines is longer than 75 feet, additional refrigerant must be added as noted below. Instructions for adding refrigerant are included further in these instructions. Liquid Line Size 75 ft. 100 ft. 125 ft. 150 ft. 1/2 none None None 2 5/8 none 2 4 6 7/8 none 4 8 12 none 6 12 18 TABLE - 3 Pounds R-22 to Add Vs. Liquid Line Length 15. All piping must be done in accordance with applicable local and national codes. Such codes may include The Safety Code for Mechanical Refrigeration (ANSI B9.1), and The Code for Refrigerant Piping (ANSI B31.5). 16. The following installation guidelines are strongly suggested. While they do not affect the machine warranty, they may be required for safe operation, and to comply with all applicable electrical and mechanical codes. 17. Local electrical code must be checked for wiring method. 18. The installer must provide a lockable disconnect switch(s) adjacent to the condenser. The power is fused at the machine by a 15 amp breaker. 19. Electrical connections between the condenser and the Tube-Ice machine require minimum 12 ga. wire. See FIGURE-11 &12. 20. All electrical fittings and components exposed to the weather must be suitable for outdoor installation. The design total heat rejection for each Tube-Ice machine, the recommended air-cooled condenser, and condenser physical and electrical data are shown in TABLE-2. Only the condensers shown are UL listed with the ice machines. Other condensers may be individually UL listed, but are not UL listed with the Tube-Ice machines, and cannot be recommended by Vogt Tube-Ice. Catalog energy efficiency ratings of the ice machines are based on use of the recommended condenser. Condensers supplied by Vogt must be utilized. The use of non-vogt condensers will void the compressor warranty. For continuous operation at ambient above 105?F, consult the factory about using a larger condenser. 3

Ice Machine Model HE20 HE30 HE40 Recommended Condenser HDD-61 (HDD-101) HDD-101 (HDD-131) HDD-131 (HDD-191) Note: For continuous operation at ambients above 105 F, use larger condenser shown in parenthesis Total Heat Rejection: BTU/hr at 60 Hz. BTU/hr at 50 Hz. Fans: Number HP, Each Total, CFM Full Load Amps: 1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz Locked Rotor Amps: 1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz Weight, lbs.: Net Shipping Operating (maximum flooded) Condenser dimensions, inches: A (Width) B (Length) C (Height) D (Leg centerline) E (Leg centerline) F (Clearance below) Recommended Line Sizes, OD: Liquid (All lengths and orientations) Discharge Gas Vertical Up, All lengths Horizontal Or Down, < 75 ft. Horizontal Or Down, > 75 ft. Connections at Condenser: Liquid (ODC) Discharge Gas (ODC) Connections at Machine Liquid (ODC) Discharge Gas (ODC) 28,700 23,900 1 1/3 5,000 2.5 3.0 7 8.2 150 195 167 38-7/8 45-1/2 36-1/8 37-7/8 37 16-1/8 1/2 5/8 5/8 7/8 1/2 5/8 TABLE - 4 Air-Cooled Condenser Data 4 44,500 37,100 2 1/2 9,800 8.0 5.8 15 17.5 250 310 276 41-3/8 66 36-1/8 40-3/8 54 16-1/8 5/8 7/8 7/8 5/8 7/8 80,400 67,000 2 (3) 1/2 (1/2) 9,800 (15,500) 8.0 (12) 5.8 (8.7) 15 (23) 17.5 (27) 265 (370) 325 (440) 301 (405) 41-3/8 (41-3/8 ) 66 (105) 36-1/8 (36-1/8 ) 40-3/8 (40-3/8 ) 54 (94 ) 13-3/4 (13-3/4 ) 7/8 (7/8 ) () () 7/8 (7/8 ) (1-3/8 )

Ice Machine Model HE60 / P112F HE100 / P118F P18FXT Recommended Condenser HDD-231(HDD-261) HDD-311 (HDD-361) HDD-591 (HDD-661) Note: For continuous operation at ambients above 105 F, use larger condenser shown in parenthesis Total Heat Rejection: BTU/hr at 60 Hz. BTU/hr at 50 Hz. Fans: Number HP, Each Total, CFM Full Load Amps: 1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz Locked Rotor Amps: 1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz Weight, lbs.: Net Shipping Operating (maximum flooded) Condenser dimensions, inches: A (Width) B (Length) C (Height) D (Leg centerline) E (Leg centerline) F (Clearance below) Recommended Line Sizes, OD: Liquid (All lengths and orientations) Discharge Gas Vertical Up, All lengths Horizontal Or Down, < 75 ft. Horizontal Or Down, > 75 ft. Connections at Condenser: Liquid (ODC) Discharge Gas (ODC) Connections at Machine: Liquid (ODC) Discharge Gas (ODC) 122,000 101,700 3 (3) 1/2 (1/2) 15,000 (14,000) 6.0 (6.0) 2.7 (2.7) 6.0 (6.0) 3.0 (3.0) 19.8 (19.8) 9.9 (9.9) 19.8 (19.8) 9.9 (9.9) 400 (520) 475 (595) 436 (566) 41-3/8 (41-3/8 ) 105 (105 ) 36-1/8 (36-1/8 ) 40-3/8 (40-3/8 ) 94 (94 ) 13-3/4 (11-3/4 ) () () () () 1-3/8 (1-5/8 ) TABLE 4A Air-Cooled Condenser Data 5 181,200 151,000 5 (5) 1/2 (1/2) 22,500 (22,000) 10.0 (10.0) 4.5 (4.5) 10.0 (10.0) 5.0 (5.0) 33 (33) 16.5 (16.5) 33 (33) 16.5 (16.5) 610 (660) 700 (770) 667 (726) 28-3/4 (28-3/4 ) 180-1/8 (180-1/8 ) 41-5/8 (41-5/8 ) 27 (27 ) 147-5/8 (147-5/8 ) 14-5/8 (14-5/8 ) () 1-5/8 (1-5/8 ) (1-5/8 ) 1-5/8 (1-5/8 ) 1-3/8 249,900 278,250 5 (5) 3/4 (3/4) 33,000 (32,500) 17.0 (17.0) 8.5 (8.5) 17.0 (17.0) 8.5 (8.5) 60 (60) 30 (30) 60 (60) 30 (30) 1175 (1200) 1325 (1350) 1221 (1258) 57 (57 ) 180-1/8 (180-1/8 ) 45-5/8 (45-5/8 ) 55-1/4 (55-1/4 ) 147-5/8 (147-5/8 ) 14-5/8 (14-5/8 ) 1-5/8 (1-5/8 ) 2-1/8 (2-1/8 ) 1-3/8

FIGURE - 9 Condenser Dimensions (Condenser pictured: DD-101 or DD-131) Note: Dash lines indicate customer supplied piping. The Check Valve in the return line (labeled Output To Machine ) is supplied with the condenser. FIGURE 9A Condenser Field Piping 6

CONDENSER EQUIVALENT LINE SIZE WORKSHEET Discharge Gas Line O.D. Fitting Type Number Used Factor Total Globe Valve (open) Angle Valve (open) 45? Elbow 90? Elbow Feet of Straight Copper Used Total Fitting Factor Total Equivalent Feet Fitting Factors Copper Tube O.D. Type L 1/2 5/8 7/8 1 1/8 Globe Valve (open) 14 16 22 28 Angle Valve (open) 7 9 12 15 45? Elbow.5 1 1 1.5 90 Elbow 1 2 2 3 TABLE - 5 FIGURE - 10 Minimum Traps for Discharge Lines 7

Refrigerant Connections to Air-Cooled Condenser. MACHINE FRAME ANGLE HE20 HE40 ONLY TEFLON SEAL HE20 HE60 (both lines) P118 and P18XT (liquid return line) PART #: 12A 2600T01 (1 1/4 12 Threads) P118 and P18XT (discharge line) PART #: 12A2600T03 (1 3/4 12 Threads) ROTALOCK FIELD CONNECTOR ROTALOCK SPUD HE20 HE60 (both lines) P118 and P18XT (liquid return line) 1 1/4 12 Threads P118 and P18XT (discharge line) 1 3/4 12 Threads HE20 HE60 (both lines) P118 and P18XT (liquid return line) PART #: 12A 2396A0501 1 1/8 IDS X 1 1/4 12 Threads P118 and P18XT (discharge line) PART #: 12A2396A0601 1 3/8 IDS X 1 3/4 12 Threads FIGURE - 11 Field Attachment, Air Cooled Condenser Refrigerant Tubing FOLLOW THESE PROCEDURES TO MAKE A TIGHT JOINT 1. Solder or braze condenser tubing ends to the female Rotalock connectors. 2. Remove dust caps if used, making sure that component plastic seals are intact. 3. Wipe off connector and spud threaded surfaces with a clean cloth to prevent the inclusion of dirt, or any foreign material in the system. 4. Connector coupling nut should be screwed onto Rotalock spud using the proper amount of torque (See TABLE-6). Spud Size Amount of Torque 1/2 5/8 30-40 FT LBS 7/8 50-60 FT LBS 1 1/8 80-100 FT LBS TABLE 6 Torque Ratings 8

Wiring Connections to Air-Cooled Condenser. Air cooled condenser should be wired to terminals 20,21,22 and 23 (see FIGURE - 12). Main Power Main Power Connections Fan Motor (s) Condenser Connections Cold Weather Package (Hot) NOTE: All four wires must be run from the ice machine to the remote air cooled condenser. FIGURE - 12 Ice Machine Terminal Block Connections FIGURE - 13 Wiring For HDD-61 With Cold Weather Valve and Single Fan 9

Wiring Connections to Air-Cooled Condenser (Cont.) FIGURE - 14 Wiring For HDD-101 & HDD-131 With Cold Weather Valve And Dual Fans FIGURE - 15 Wiring For HDD-191, HDD-231 & HDD-261 With Cold Weather Valve And Three Fans 10

Wiring Connections to Air-Cooled Condenser (Cont.) FIGURE - 16 Wiring For HDD-311, HDD-361, HDD-591 & HDD-661 With Cold Weather Valve And Five Fans Solenoid Valve Condenser Description Valve Valve Rebuild Kit HDD-61 HDD-101 HDD-131 HDD-191 HDD-231 HDD-261 HDD-311 HDD-361 HDD-591 HDD-661 5/8 N.O. Solenoid 7/8 N.O. Solenoid 1 1/8 N.O. Solenoid 1 3/8 N.O. Solenoid 1 5/8 N.O. Solenoid Note: Sporlan Solenoid Valves 11 Replacement Coil Penn (fan) Thermostats Ranco (solenoid) 12A4200A0503 12A4199V42 12A2105C04 12A2117G05 12A4200A0704 12A4200A0902 12A4200A1102 12A4200A1104 12A4199V44 12A2105C04 12A2117G05 12A2117G06 12A4199V45 12A2105C04 12A2117G05 12A2117G06 12A4199V45 12A2105C04 12A2117G05 12A2117G06 12A4199V47 12A2105C04 12A2117G05 12A2117G06 TABLE 7 Kramer Cold Weather Kit Replacement Parts