AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

Similar documents
AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Research on Waste Heat Recovery System for Residential Gas Engine-Driven Heat Pump

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Study on water conservation by water saving fixtures

Enlightened Fresh Air For a Healthy House

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

STUDY ON THE EFFECTIVENESS OF AIR-CONDITIONING AND VENTILATION SYSTEMS BY CFD ANALYSIS IN HOUSES

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

Survey on Cooling Costs and Related Factors for Apartments in an Urban. Area of Osaka

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

A study of 4 liter toilet with new flushing technology

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Challenges and Methods of Estimating a Conceptual HVAC Design

THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND TO THE PATHFINDER SOFTWARE

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

SPRAY DRYING INVESTIGATIONS ON MEDICINAL PLANT BASED PHARMACEUTICAL PRODUCTS

Comparative Study of Technological Trend between DAIKIN and Panasonic in the Field of Air Conditioner

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

Thermal Comfort with Convective and Radiant Cooling Systems

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Efficiency of Non-Azeotropic Refrigerant Cycle

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

EVALUATING LOOP HEAT PIPE PERFORMANCE IMPROVEMENT USING CIRCUMFERENTIAL GROOVES. Nadjara dos Santos, Roger R. Riehl

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

DEVELOPMENT OF A KILN DRIED WOOD SYSTEM USING HEAT PUMP TECHNOLOGY

TABLE OF CONTENTS. Part I Administrative... 1

OCCUPANT INTERACTION WITH VENTILATION SYSTEMS 7th AIC Conference, Stratford-upon-Avon, UK

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

Development of Bionic Air Cooler Used in High Temperature Coal Mine

EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Ventilation Strategies for Healthy IEQ and Energy Efficiency

Solar Drying Techniques And Performance Analysis: A Review

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

about your house Choosing a Dehumidifier

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Operation of a Two-Phase Reverse Loop Thermosyphon

SIMULATION STUDY ON A NET-ZERO ENERGY HOUSE WITH SOLAR AIR COLLECTORS

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

The Use Of Attic Space For Cooling and Dehumidification

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034

Performance test of a helium refrigerator for the cryogenic hydrogen system in J-PARC

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Knowledge Objectives (2 of 2) Fuel Gas Systems. Skills Objectives. Introduction. Fuel Gas Systems (1 of 6) 12/20/2013

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS

The Effect of ph from Simulated Acid Rain on Multi- Element Contents of Leaves, Stems and Roots of the Crops

Assessing the Impact of Wash Water Temperature, Detergent Type and Laundering Platform on Basic Clothing Attributes. Abstract.

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

ACOUSTICAL DESIGN OF THE CONCERT HALL OF PÉCS CONFERENCE AND CONCERT CENTRE

Building and Safety Division Civic Center Dr, Bellflower, CA, (562) x

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

MAKING YOURSELF AT HOME

Residential Building Walls and Environment in Amman, Jordan

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Effect of Interaction of Object Color and Lighting Color on a Person s Impression of Interiors

A Study on the Effects of Urban Landscape on Citizen s

IMPORTANT SAFETY INSTRUCTIONS

Leakage of Mildly Flammable Refrigerants into a Room

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Simulation Of Pneumatic Drying: Influence Of Particle Diameter And Solid Loading Ratio

Study on Fire Detection at Cultural Assets Buildings with Botanical Roofs

Inspector Gadget Homes

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Uniform Dwelling Code 2017 Updates SPS 323

Moisture Movement. By Ben Gromicko

Variable far infrared radiation (VFIR) technique for cubic carrot drying

Transcription:

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM K. Yokoo 1, S. Tanabe 1, Y. Aizawa 2, K. Inagaki 2, D. Kawamata 2, H. Amai 1, K. Watanabe 1, and T. Nishimasu 1 1 Waseda University, Dept. of Architecture, Tokyo, Japan 2 Tokyo Gas Co.Ltd. ABSTRACT In recent years, the aspect and behavior inside a bathroom and an appurtenant changing room have been changing. With these changes, the thermal insulation quality of a dwelling has improved, so it seems that the amount of moisture generated in a dwelling has changed. In this study, amount of moisture produced in a bathroom and a changing room was surveyed in order to grasp the thermal and humid environment in bathroom and a changing room. From the result of the survey, it was found that the amount of moisture in bathing was bigger than before. It was considered that the amount of adhesion moisture was depended on the way of bathing, and the balance of exhausted moisture by ventilation and remaining moisture in the atmosphere was depended on of ventilation rate. The survey was conducted in two different size bathrooms (12 16, 16 16). Influence of a bathroom size was deliberated. INTRODUCTION In recent years, the humidity and thermal environment of the bathroom has changed dramatically with the diversification of bathroom equipment, increasingly higher level of insulation, high airtight homes. With the shifts in perspectives and objectives of bathing, bathing behavior has also changed (Such as increase of bathing frequency and establishing of showering). However there are few researches of moisture production inside a bathroom which depend on a modern Japanese life style. (Nagai et al. 23, Ito et al. 23, Ito et al. 24, Otani et al. 26) To exhaust the moisture produced inside a house efficiently, appropriate ventilation plan, which includes an understanding of the source and the amount of moisture production, is necessary. The objectives of this paper are to survey the humidity and thermal environment of modern conditions of bathing and to examine the size of bathroom on humidity and thermal environment and the moisture production. METHOD OF EXPERIMENT Summary of laboratory Summary of laboratory is shown in Table 1. The experiment was performed in two of different size bathrooms and changing rooms that are located in a controlled artificial climate room. The walls of the unit type bathroom are composed of plastic boards, which do not absorb moisture, a section of empty space, insulation and composite material. The ceiling and walls of the changing room are insulated and the material of floor is wood. The dimensions of the T-1216 laboratory are width 115mm, depth 16mm, and height 2mm and of the changing room are width 12mm, depth 12mm, height 23mm. The dimensions of the Y-1616 are width 16mm, depth 16mm, and height 21mm and for the changing room are width 16mm, depth 16mm, height 24mm. There are four vents in the lower part of the folding door to the bathroom in T-1216 laboratory. And there are one vent in the lower part of the sliding door to the bathroom in Y-1616. Both laboratories have a bathroom dryer on a ceiling of bathroom. Corresponding Author: Tel: + 3 5292 583, Fax: + 3 5292 584 E-mail address: yoko@tanabe.arch.waseda.ac.jp

Table 1 Summary of laboratory T-1216 Y-1616 Volume of bathroom 3.6 [m 3 ] 5.8 [m 3 ] Floor space of bathroom.8 [m 2 ] 1.2 [m 2 ] Volume of changing room 3.3 [m 3 ] 5.8 [m 3 ] Ventilation rate High 119 [m 3 /h](33 [ACH] ) 13 [m 3 /h] (22 [ACH] ) Low 65 [m 3 /h] (18 [ACH] ) 95 [m 3 /h] (16 [ACH] ) Measurement items and ventilation quantity Schematic of test bathrooms and measurement positions is shown in Figure 1, and the measurement items and methods are shown in Table 2. The vertical distribution of the temperature and humidity in the upper and lower areas of both the bathroom and changing room were measured at 3 positions. The temperature of the ceiling and each of the walls and the humidity below the ceiling of both the bathroom and changing room were also measured. The temperature and humidity in a vent in the doors of the bathroom was measured in assuming that the temperature and humidity of the air entering the bathroom and the air leaving the changing room was same. The temperature and humidity of the air leaving the bathroom was measured in the exhaust duct connected to the ventilation fan. During the experiment, the windows were sealed to minimize the amount of air flowing in and out through any openings besides exhaust duct and bents in the doors. The amount of air flow for the ventilation located on the ceiling can be switched from 119 m 3 /h in high ventilation to 65 m 3 /h in low ventilation in T-1216 laboratory, and from 13 m 3 /h in high ventilation to 95 m 3 /h in low ventilation in Y-1616 laboratory. These values were checked by exploratory experiment (Watanabe et al. 26). 3 W1 115 W4 T-1216 W3 W2 2 12 1 3 W4 16 16 W1 W2 W3 Y-1616 16 12 16 1 16 Temp. (FL+.1,.6,1.1,1.7),Humid. (T-1216:FL+.1,.6,1.7, Y-1616:FL+.1,.6,1.1,1.7) Temp. and humid. of inlet-outlet air Surface temp. Temp. and humid. of exterior Temp.and humid. on ceiling Figure 1 Schematics of test bathrooms and measurement positions 2 Table 2 Measurement items and methods Contents Measurement points and remarks Temperature distributions 3 points in both rooms. Humidity distributions 3 points in both rooms The point's data hit against hot water during bathing was deleted. Surface temp. 4 points in bathroom and changing room. 1point on the ceiling Temp. and humid. of exterior 1 point in artificial climate room Temp. and humid. of inlet-outlet air 1 point in exhaust duct, 1 point in a vent of bathroom door, 1 point in a vent of changing room door Volume rate of supply water Setting flow meter at the header of boiler Volume rate of exhaust water Measuring weight of tank filled with exhaust water Moisture attached to wall Measuring weight of paper used for wiping water left on surface of wall

Computational method of the amount of moisture produced The amount of moisture produced was calculated by summing up the amount of moisture that was contained in air and was adhered to the wall. The amount of moisture adhered to the wall was wiped off with kitchen papers and was measured by the weight change of the papers. The amount of moisture in air was calculated by the amount of moisture that remained in the bathroom and exhausted by ventilation. The amount of moisture exhausted by ventilation was calculated by amount of ventilation and air temperature and humidity at supply and exhaust openings. Method of experiment and experiment cases The bathing participants were total of 14 healthy men in 2 s and each bathed under various cases as shown in Table 3. After maintaining a fully steady condition previous to the experiment, the bathing participants entered the bathroom and bathed. To prevent any differences by participant, instructions on how to open/close the door and the use of bathroom equipment were explained to the participants. Ventilation during bathing was set in three levels, High, Low and Off. In cases of High and Low ventilation the strength of ventilation was kept same both during and after bathing. In the case of Off, the fan was switched on to the High, immediate after moving out to a changing room. Despite the strength of ventilation, the fan was on for 2 minutes after moving out to the changing room. The time used to open and close the door was 8 seconds in standard, and set the four type of length (4, 8, 2, 4 seconds). Quantity of moisture moved into changing room was calculated by summing up the amount of moisture that remained in the changing room and exhausted by ventilation. Table 3 Experiment cases Laboratory Bathing style Temp and humid of exterior Ventilation during bathing Length of opening a door [s] 28 75% High, Low, Off 8 High, Off 4 2 5% Showering Low 8 High 4 1 3% Low, Off 8 T-1216 28 75% High, Low, Off 8 High, Off 4 Bathing in 2 5% Low 8 tub High, Off 4 1 3% Low 8 High, Low 4, 8, 2, 4 Showering Off 8 Y-1616 2 5% Bathing in High, Low 4, 8, 2, 4 tub Off 8 Bathing style As shown in Figure 2,3 the scheduling and two styles of bathing (showering and bathing in tub) were decided by using the investigated summertime average (A society for the study of bathing culture,1999, 2). During the experiment, participants were not allowed to change the flow rate and the temperature of hot-water for shower. Since the relative humidity of the bathroom was below 9% after the ventilation during 2 min, it was decided to enter the bathroom to measure the water adhered to the ceiling, walls, and floor. For showering, body washing was performed in an upright standing position for 1 min. For bathing in the bath tub, the water in the tub was not reheated and the cover for the bath tub was opened right after the experiment participant entered the bathroom. The participant was to run the shower for 9 minutes and stay in the bath tub for 7 minutes. The participant was to wash in a seated position and to rinse with a shower after leaving the bath tub. Then, participant closed the cover for the bath tub. The water in the bath tub was drained after measuring the moisture attached to the bath tub.

(1) ( (2) )( ) (3) ( ) ((2) ) ((4) ) ((5)(2)(6)(7) )( )( ) ( ) (8) ( ) 1 2 11 12 2 22 19 21 [min] 42 (1) Supplying hot water in tub (7) Wiping body, exit [1min] (2) Enter changing room. (8) Wiping body, putting off clothes [1min] putting on clothes [3min] (3) Report [1min] (9) Ventilation [2min] (4) Showering [9min] (1) Wiping water attached (5) Bathing in tub [7min] on surface (6) Showering [1min] Figure 2 Schedule for bathing in tub style (1) ( (2) )( ) (3) ( ) ((2) )( (6)(7) )( ) ((8) ) 13 [min] 1 2 12 14 17 34 (1) Supplying hot water in tub (7) Wiping body, exit [1min] (2) Enter changing room. (8) Wiping body, putting off clothes [1min] putting on clothes [3min] (3) Report [1min] (9) Ventilation [2min] (4) Showering [9min] (1) Wiping water attached (5) Bathing in tub [7min] on surface (6) Showering [1min] Figure 3 Schedule for showering style RESULTS ANALYSIS AND DISCUSSION Thermal environment and humidity in the bathroom and changing room The results of the average of all points measured for the temperature and the humidity inside the bathroom and changing room, in case of bathing in tub, are shown in Figure 4. The blue colored area in the figures shows time period of showering. The red colored area shows time period of staying in the changing room. During bathing, the relative humidity of the bathroom reached 1% right after opening the cover for the bath tub and letting the shower run, regardless of the operation for the ventilation and the condition of the exterior. After the bathing, relative humidity of changing room rose with the moving of participant to the changing room in every case. The humidity of changing room increased the most in Off and then following in Low and in High. Increase of temperature and humidity in a bathroom and changing room was less quickly and declination was more quickly in Y-1616 than T-1216. The temperature in the T-1216 bathroom of the cases of bathing in tub was 2 C higher in High, 8 C higher in Low than Y-1616, and about the same in Off. And the temperature in the T-1216 bathroom of the cases of showering was 7 C higher in Low than Y-1616, and about the same in High and Off. But the increase of temperature in a changing room in the cases of T-1216 was greater than Y-1616.

Humid. of bathroom Humid. of bathroom Temp. of bathroom Temp. of bathroom 4 1 Temperature [ C ] 35 3 2 High 75 5 Relative humidity [ % ] 1 2 3 4 Time [min.] Humid. of bathroom Humid. of bathroom Temp. of bathroom Temp. of bathroom 4 1 Temperature [ C ] 35 3 Low 75 5 Relative humidity [ % ] 2 1 2 3 4 Time [min.] Humid. of bathroom Humid. of bathroom Temp. of bathroom Temp. of bathroom 4 1 Temperature [ C ] 35 3 Off 75 5 Relative humidity [ % ] 2 1 2 3 4 Time [min.] Figure 4 Temperature and Humidity inside the bathroom and changing room Quantity of moisture attached to surface Measurement results for the quantity of moisture attached to each surface, in the cases of bathing in tub, are shown in Figure 5. Comparing T-1216 with Y-1616, the amount of moisture attached to the surfaces in T-1216 was greater than Y-1616. Because of the difference of floor material, there was difference of amount of moisture attached to floor between T-1216 and Y-1616. So the result of calculating of the amount of moisture attached to floor of Y-1616 supposed to consist of the same material of T-1216 (the tint part of the figure), was that the amount of moisture attached to floor of Y-1616 was increased to 2g more and greater than T-1216. Measurement results for the sum of quantity of moisture attached to the surfaces, in two styles of bathing, are shown in Figure 6.The amount of moisture attached to the surfaces of T-1216 were 45-68g, while Y-1616 were 2-43g. The amount of T-1216 was g greater than Y-1616.

Amount of moisture attached to surface[ g ] 3 2 1 TB-H(N=2) TB-L(N=1) TB-O(N=2) YB-H(N=1) YB-L(N=6) YB-O(N=1) Floor Bath W1 W2 W3 W4 Ceiling Region Figure 5 Amount of moisture attached to each surface Amount of moisture attached to surface[ g ] 12 9 6 3 High Low Off High Low Off TB YB TB TS YS TS 1 C 2 C 28 C 1 C 2 C 28 C Experiment cases Figure 6 Amount of moisture attached to surface TB:T-1216,Bathing in tub YB:Y-1616,Bathing in tub TS:T-1216.Showering YS:Y-1616,Showering H:High L:Low O:Off Quantity of moisture production during bathing The calculated total quantity of moisture production and each value of moisture production by bathing style, exterior conditions and ventilation conditions are shown in Figure 7. The quantity was 9-13g (the average was 11g) regardless of the cases. It was greater than 43g which is a previous data from literature (Nagai et al. 23), because a previous data wasn t calculated the amount of moisture exhausted by ventilation. In Y-1616 the amount of moisture released through ventilation occupied 7% of the quantity of moisture production, while it occupied 5% in T-1216. If the floor of Y-1616 is supposed to consist of the same material of T-1216 (the amount of moisture attached to floor becomes 2g greater), the quantity of moisture production of Y-1616 is about the same amount of T-1216. Attached to surface Remaining in air Released through ventilation 15 Amount of moisture production [ g ] 12 9 6 3 TB YB TB TS YS TS H L H L H L H L H L H L H L H L 1 C 2 C 28 C 1 C 2 C 28 C Figure 7 The calculated total quantity of moisture production TB:T-1216,Bathing in tub YB:Y-1616,Bathing in tub TS:T-1216.Showering YS:Y-1616,Showering H:High L:Low O:Off

Quantity of moisture moved into changing room The calculated amount of moisture moved into changing room in the cases of Y-1616 was shown in Figure 8. Amount of moisture moved into changing room was calculated by the sum of the amount of moisture released through ventilation of changing room after leaving a bathroom and the amount of moisture remaining in changing room air. The amount of moisture moved into the changing room was 2-5g. It was within 35-1g, the range of a previous simulated data (Otani et al.26).the amount in the bathing in tub style was more than in the showering style, especially in the case of 8 seconds used to open and close the door. The length of the time used to open and close the door became longer, the amount of moisture moved into changing room became greater. Amount of moisture moved into changing room [ g ] Bath-High Shower-High Bath-Low Shower-Low 6 45 3 15 4 8 2 4 Length of opening a door [s] Figure 8 Amount of moisture moved into changing room CONCLUSION The objective of this paper was to understand the thermal environment and the humidity around the bathroom, in consideration of actual modern lifestyles. The influence of the size of bathroom and the bathing style and the use of the ventilation to thermal environment and humidity around the bathroom was considered. The results are follows, 1) During bathing, the relative humidity of the bathroom reached beyond 1% right after opening the cover for the bath tub and letting the shower run. After the bathing, relative humidity of a changing room rose with the moving of participant out to the changing room in every case. It seems that the size of bathroom doesn t influence much to the temperature in the bathroom. But the increase of temperature in the changing room in the cases of T-1216 was greater than Y-1616. 2) The amount of moisture attached to the surfaces of T-1216 were 45-68g, Y-1616 were 2-43g. Comparing T-1216 with Y-1616, the amount of moisture attached to the surfaces in T-1216 was greater than Y-1616, because of the difference of surface material. 3) The quantity of moisture production during bathing was 9-13g (the average was 11g) regardless of the cases. It was greater than 43g which is a previous data from literature. In Y-1616 the amount of moisture released through ventilation occupied 7% of the quantity of moisture production, while it occupied 5% in T-1216. 4) The amount of moisture moved into changing room was 2-5g. It was within the range of a previous data. As the length of the time used to open and close the door became longer, the amount of moisture moved into changing room became greater. REFERENCES 1. Nagai Y. A Study on Movement of Moisture Generated in Bathroom ( part 1 ) Measurement of Moisture Generation by Bathing and Drying Process of Bathroom Proceedings of Annual Meeting of AIJ, 23, pp.413-414 2. Ito Y. A Study on Movement of Moisture Generated in Bathroom ( part 2 ) Analysis on Drying Process of Bathroom Proceedings of Annual Meeting of AIJ, 23, pp.415-416 3. Ito Y. A Study on Movement of Moisture Generated in Bathroom ( part 3) A Relation between

Ventilation and Evaporation Rate in Drying Bathroom Proceedings of Annual Meeting of AIJ, 24, pp.435-436 4. Otani T. A study on effect of water generation in bathroom Analysis on changes in temperature and humidity of bathroom and moisture flux from bathroom to other rooms Proceedings of Annual Meeting of AIJ, 26, pp.355-356 5. Watanabe K. Basic Unit of Amount of Moisture Produced Inside a Bathroom and Appurtenant Dressing Room Proceedings of Healthy Buildings 26, vol.4, p.35-38 6. A society for the Study of Bathing Culture (1999) A study on the investigation of consciousness and actual situation in bathing 7. A society for the Study of Bathing Culture (2) Bathing conditions of the modern people, actual condition survey in summer