Installation, operation & service manual. AlarmScout 961/962 loop powered

Similar documents
Installation, operation & service manual. AlarmScout 961/962 line powered

Terminal Automation Solutions

Enraf Servo Gauge 854 XTG

Enraf Servo Gauge 854 ATG

Terminal Automation Solutions SmartRadar FlexLine Global Experience. Locally Applied.

Instruction manual 640 Securiterre

Sensepoint XCL Fixed Gas Detector

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Installation and Operating Instructions

Installation guide 864 MTT Multi Thermo sensor Thermometer

OPTIMIZING YOUR TECHNOLOGY INVESTMENT WITH SERVICE AND SUPPORT

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Installation Guide SmartRadar FlexLine

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Dräger Polytron 5720 IR Toxic Gas Detection

ECHOTEL 961/962. Ultrasonic level switches. Worldwide level and flow solutions DESCRIPTION. Loop or line powered FEATURES AGENCY APPROVALS

Annubar Flowmeter Series

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

Replacing GWR Sensor Electronics

LC2200 Level Controller Installation and Maintenance Instructions

Dräger Polytron 5720 IR Detection of carbon dioxide

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

INSTRUCTION MANUAL (ATEX)

Dräger Polytron 8100 EC Detection of toxic gases and vapors

Dräger Polytron 8100 EC Detection of toxic gases and oxygen

SET-2000 Hi Level/Oil

OPTIBAR DP 7060 Supplementary Instructions

SET-2000 Oil/Sludge 12 VDC

Instruction manual APU Hard alarm output contacts

Dräger Polytron 8720 IR Detection of carbon dioxide

SET Installation and Operating Instructions. Level switch for one sensor

OilSET-1000 (12 VDC)

Public Safety DAS Annunciator Panel

Model 144H. Product Data Sheet , Rev DB February Content

Rosemount 3100 Series Ultrasonic Level Transmitters

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

Fisher LCP100 Local Control Panel

Mobrey ultrasonic Liquid level detection systems

OPTIWAVE X500 Supplementary Instructions

PROCESS AUTOMATION PROTECTING YOUR PROCESS THE DEFINITION FOR INTRINSIC SAFETY K-SYSTEM K-SYSTEM THE MOST TRUSTED NAME.

VERSAFLOW VORTEX Supplementary instructions

Dräger Polytron 8700 IR Detection of flammable gases and vapors

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Ultrasonic Switches. Features & Benefits

4) Intrinsic Safety Certification

Sapphire. Ultrasonic Point Level System User Guide P/N Part of Thermo Fisher Scientific. Revision C

E C H O T E L C O N T A C T U L T R A S O U N D

Ultrasonic Point Level Switches

Rosemount 2100 Series

User s Manual. AXF Series Magnetic Flowmeter Installation Manual ATEX and IECEx Explosion Proof Type IM 01E20A01-11EN IM 01E20A01-11EN.

VersaFlow Coriolis 100 Mass Flow Sensor Technical Datasheet. Specification

Rosemount 3100 Series Ultrasonic Level Transmitters

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

SmartPower Solutions. Quick Start Guide , Rev CA March 2015

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

Snifter ATEX22 VERSION. User Manual. Distributor

805QS Pressure Switch-Transmitter

Archive. LC2200 Level Controller. 1. Safety information. 2. General product information. 3. Installation. 4. Setting up the controller

Operating Instructions

Operating Manual MS220DA

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

Danfoss gas detection unit Type GD Heavy Duty

Model 144H. Product Data Sheet , Rev DB February Content

Instruction manual ICU Hard alarm output contacts

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

MSM400 Ultrasonic Suspended Solids Monitoring and Control System

User s Manual YTA610 and YTA710 NEPSI Certification

Sensor Interface Module Installation/Operation Instructions

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

Rosemount 2088, 2090P, and 2090F Pressure Transmitters

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

INSTRUCTION MANUAL (ATEX / IECEx)

Greentrol Automation, Inc.

Dräger QuadGard Control System

MBCE-110/230UV Flame Sensor Module

Pump-Down Controller MODEL 4052

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

Instruction Manual. CAT 100 & CAT 200 Continuous Analyzer Transmitter Addendum for Hazardous Area Applications. 3 rd Edition 05/2007

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001

Analog Room Pressure Monitor RPC Series

SmartPower Solutions [ SmartPower Solutions. Quick Installation Guide , Rev AC January 2012

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

MAN0604_Issue 09_ Apex

ph COOLING TOWER CONTROLLER

VA301C CONTROLLER WITH BACnet OPTION

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

Mobrey MSP900SH Level and MSP900FH Flow Ultrasonic Transmitters

INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas

Dräger Polytron 8200 Stationary gas detector (CatEx)

Quick Start Guide. XNX Universal Transmitter

Terminal Automation Solutions

Ultrasonic switch. Pointek ULS200. Quick Start Manual 03/2013. Milltronics

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

This symbol indicates prohibition. The specific prohibited action is provided in and/or around the figure.

Transcription:

AlarmScout 961/962 (loop powered) Installation, operation & service manual AlarmScout 961/962 loop powered

@@ UNPACKING Unpack the instrument carefully. Make sure all components have been removed from the foam protection. Inspect all components for damage. Report any concealed damage to the carrier within 24 hours. Check the contents of the carton/crates against the packing slip and report any discrepancies to Honeywell Enraf. Check the nameplate model number to be sure it agrees with the packing slip and purchase order. Check and record the serial number for future reference when ordering parts. Nameplate: - part number - serial n 008 044 These units are in compliance with: 1. The EMC directive 2004/108/EC. The units have been tested to EN 6126: 1997 + A1 + A2. 2. Directive 94/9/EC for equipment or protective system intended for use in Figure 1 potentially explosive atmospheres. EC-type examination certificate number ISSeP06ATEX011X - intrinsically safe and ISSeP06ATEX008 - flameproof enclosure.. The PED Directive 97/2/EC (pressure equipment directive). Safety accessories per category IV module H1. SPECIAL CONDITIONS FOR ATEX INTRINSICALLY SAFE USE Materials marked as Category 1 equipment and used in hazardous areas requiring this category, shall be installed in such a way that, even in the event of rare incidents, the aluminium enclosure cannot be an ignition source due to impact or friction. MOUNTING Filling line High alarm High high alarm Pump control High alarm High alarm @@@ @@@ @@@ @@@ Threaded Figure Auto fill or empty pump control Pump protection Low alarm Figure 2 Pump Figure 4 Welded flange Warning: Bring the instrument on the same potential as the tank potential prior to the installation. 2 Instruction & installation manual AlarmScout 961/962 loop powered Part No.: 4417902_Rev.0

WIRING WITH CABLES Model 961: single gap Model 962: dual gap Figure 5 Figure 6 Hi 22 Lo.6 FAULT LOOP MODEL 961 8 16 F A U L T TIME DELAY + External grounding screw, only for ATEX flameproof enclosure. FAULT Hi 22 Lo.6 MODEL 962 TIME DELAY LOOP 8 12 16 + Plugged entry Shield to green grounding screw HAZARDOUS AREA Shield not connected Ground + Standard shielded twisted pair cable (recommended but not needed when wired as per NAMUR NE 21 for field strengths up to 10 V/m). SAFE AREA I.S. wiring Important: Connect the unit to the ground for avoiding earth potential drifts. The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the field (at the level switch side) but connecting in the control room is also allowed. WIRING WITH CONDUITS Caution: Observe all applicable electrical codes and proper wiring procedures 1.Make sure the power source is turned off. 2. Unscrew and remove housing cover.. Pull power supply and relay wires through the conduit connection. 4.Connect power leads to proper terminals for AC power (102 to 265 V AC) or for DC power (18 2 V DC) a. AC Power Connect hot wire to terminal marked L1 and the neutral wire to the terminal marked L2. The green head screw should be used for grounding. b.dc Power Connect wires to terminals (+) and (-) on the terminal block. The green head screw should be used for grounding. 5. Connect desired relay wiring (if applicable). 6. Prevent moisture seepage into housing by installing an approved seal drain fitting in the conduit run leading to the unit. 7. Wiring is complete. Replace housing cover. Caution: In hazardous areas, do not power the unit until the conduit is sealed and enclosure cover is screwed down securely. Part No.: 4417902_Rev.0 Instruction & installation manual AlarmScout 961/962 loop powered

USER INTERFACE Model 961: single gap Model 962: dual gap Figure 7 Figure 8 FAULT Hi 22 Lo.6 LOOP MODEL 961 8 16 F A U L T TIME DELAY + Time delay potentio - meter Hi 22 Lo.6 FAULT LOOP MODEL 962 8 12 16 TIME DELAY + Time delay potentio - meter Testing fault Testing loop Safe green (8 ma) Alarm yellow (16 ma) Separate fault red Testing fault Testing loop Safe green (8 ma) Lower gap yellow (12 ma) Upper gap red (16 ma) SET UP AND FUNCTIONS Set up Fault selection: Select for which the unit should report a malfunction 22 ma or,6 ma Time delay setting: Turning the potentiometer clockwise will increase the time delay from 0,5 s to 45 s. Time delay is typically used where turbulence, boiling or splashing can cause false level alarms. Setting delay to a longer value will increase time to actuate. Model 961 high-low level fail safe selection mode Level Output 8 ma green 16 ma yellow Fault red «Hi» High Level 8 ma (± 1 ma) ON OFF OFF 16 ma (± 1 ma) OFF ON OFF «Lo» Low Level 8 ma (± 1 ma) ON OFF OFF 16 ma (± 1 ma) OFF ON OFF Model 961 fault conditions mode Output Fault red «Hi» High Level 22 ma ON «Lo» Low Level,6 ma ON 4 Instruction & installation manual AlarmScout 961/962 loop powered Part No.: 4417902_Rev.0

SET UP AND FUNCTIONS Model 962 high-low level fail safe selection mode Level Output 8 ma green 12 ma yellow 16 ma red 8 ma (± 1 ma) ON OFF OFF «Hi» High Level 12 ma (± 1 ma) OFF ON OFF 16 ma (± 1 ma) OFF OFF ON 8 ma (± 1 ma) ON OFF OFF «Lo» Low Level 12 ma (± 1 ma) OFF ON OFF 16 ma (± 1 ma) OFF OFF ON Model 962 fault conditions mode Output 8 ma green 12 ma yellow 16 ma red «Hi» High Level 22 ma OFF OFF OFF «Lo» Low Level,6 ma OFF OFF OFF Part No.: 4417902_Rev.0 Instruction & installation manual AlarmScout 961/962 loop powered 5

MAINTENANCE Manual Testing Loop Test: (8 ma / 12mA / 16mA): Pressing the Loop Test pushbutton, will manually test the loop and connected actuators/indicators. The loop test forces the output and corresponding ʼs to shift from 8 ma to 12 ma (only 962) to 16 ma back to 8 ma. The time delay setting is not active during testing. Fault Test (.6 ma /22 ma): Pressing the Fault Test pushbutton for a minimum of 2 seconds, will manually test the fault output and connected actuators/indicators. The fault test simulates a circuit failure and forces the output to either.6 ma or 22 ma. The time delay setting is not active during testing. Troubleshooting Problem Action/Indication Solution No loop No ʼs are ON Check wiring / input power Check for malfunction (model 962). See below No change in output between wet gap / dry gap Gap may be plugged by solids / dense foam Clean the transducer Gap is out of reach of liquid Check mounting section on page 2 and relocate the unit or check blocking valves. Chattering output Excessive aeration / Turbulence Increase time delay Check input power Relocate the AlarmScout Fault is ON (model 961) All ʼs OFF (model 962) A system fault has been detected Press «Loop Test» pushbutton to identify the problem: Check input power * --- * : 1 flash (red ) Check wiring between transducer and electronics or replace transducer. ** --- ** : 2 flashes (red ) Replace electronics *** --- *** : flashes (red ) The unit senses excessive noise interference. Check shield connection or eliminate interference from a walkietalkie, radio or other EMC source 6 Instruction & installation manual AlarmScout 961/962 loop powered Part No.: 4417902_Rev.0

SPARE PARTS Replacing electronics/transducer The electronics can be exchanged in the field under process conditions. Follow below steps to exchange electronics/ transducer: Note: Adjust set up of the replacing electronics following the settings of the old electronics (see configuration section). Check with customer and verify applicable site permits prior to start activities. 1. Disconnect power before removing the housing cover 2. Remove power/output wires (a). Click out the protection cap of the electronics (b) 4. Remove the 2 bracket screws and slide out electronics (c) 5. Remove the transducer wires (see Wiring section) (d) 6. Re-assemble following the same procedure in opposite way. Make sure that the tip on the bracket of the electronic block is seated properly in the corresponding recess in the housing base - (e) Spare parts Partn : Digit in partn : 1 2 4 5 6 7 8 9 10 11 1 Serial n : See nameplate, always provide complete partn and serial n when ordering spares. b c a 2 d e Spare part (1) Housing cover consult factory (2) "O"-ring 012-2201-27 (4) Transducer consult factory 4 () Electronic module Digit 4 Digit 5 Digit 10 Spare part A or C 089-7259-005 1 5 1 089-7259-00 2 all 089-7258-00 Figure 9 Part No.: 4417902_Rev.0 Instruction & installation manual AlarmScout 961/962 loop powered 7

For More Information To learn more about Honeywell Enraf s solutions, contact your Honeywell Enraf account manager or visit www.honeywellenraf.com. Americas Honeywell Enraf Americas, Inc. 2000 Northfield Ct. Roswell, GA 0076 USA Phone: +1 770 475 1900 Email: enraf-us@honeywell.com Europe, Middle East and Africa Honeywell Enraf Delftechpark 9 2628 XJ Delft The Netherlands Phone: +1 (0)15 2701 100 Email: enraf-nl@honeywell.com Asia Pacific Honeywell Pte Ltd. 17 Changi Business Park Central 1 Singapore 48607 Phone: +65 655 2828 Email: enraf-sg@honeywell.com 4417902_Rev.0 APRIL 2012 2011 Honeywell International Inc.