TROUBLESHOOTING TROUBLESHOOTING. Indoor unit EEPROM parameter error. Indoor / outdoor units communication error. Zero-crossing signal detection error

Similar documents
SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit.

SERVICE MANUAL K LIGHT COMMERCIAL

DuctlessAire ES Series. Service Manual 2016 ABSSA-B4-1601

YC ON-OFF SERIES. Service Manual

Mission 3D Inverter Series

Dream Inverter Series. Service Manual 2017

HABITAT USER MANUAL TIN310**V33 TIN414**V33 TIN520**V33 TIN625**V33 TIN1036H2V02 TIN1939H2V02 INVERTER MINI SPLIT

Vertu Plus 3D Inverter Series

15C Inverter Series. Service Manual

SERVICE MANUAL. Room Air Conditioner Split Wall-Mounted Type

Service Manual for TAS-18EHN, TAS-24EHN

KMIR218-H221 / KMIR327-H217 / KMIR436-H217 / KMIR545-H219

Multi zone. MULTI OUTDOOR UNITsS. CONDENsSING UNITsS. Revision V1.0: Table of Contents

SERVICE MANUAL. Room Air Conditioner Split Wall-Mounted Type

Service Manual CAUTION ! WARNING SAFETY CONSIDERATIONS INTRODUCTION. 38MA*R Outdoor Unit Single Zone Ductless System Sizes 09 to 36

Service Manual CAUTION ! WARNING INTRODUCTION. 619PB High Wall Ductless System Sizes 09 to 36

LUNA INVERTER SERIES. Service Manual ASI-A-1301

F SERIES ON-OFF SERIES. Service Manual 2016

KSIN INVERTER SERIES Service Manual 2013

NORTH AMERICAN HVAC PRODUCTS LTD 3208 BETA AVE, BURNABY BC V5G 4K4 CSNA-1305-A SERVICE MANUAL AIR CONDITIONER SPLIT WALL-MOUNTED TYPE.

Bosch Split-Type Ductless Air Conditioner / Heat Pump

SEER 15 DC INVERTER SERIES

FROZEN SERIE SERVICE MANUAL. DC Inverter R32. Sistemi per la climatizzazione

INSTRUKCJA SERWISOWA 12F INVERTER SERIES. Service Manual FSI-A-1310

Mono 3D. SMART Inverter Air Conditioner SERVICE MANUAL. Revision A: , Content updated.

SERVICE MANUAL SPLIT WALL-MOUNTED TYPE MODELS MWCOHC30S/MRCOHC30AS MWCOHC36S/MRCOHC36AS

Part 3 Troubleshooting

DCH DCI Series R410A HEATPUMP REFRIGERANT

INVERTER SERIE H6 Service manual

CAUTION DLFEHA. SERVICE MANUAL High Wall Ductless System Sizes 09 to 24

YN-M SERIES MULTI SPLIT SYSTEM MULTI CIRCUIT OUTDOOR UNITS (2, 3 AND 4 ZONES) SERVICE MANUAL PRE 2014 MODELS (Pre Serials) CONDENSING UNITS

SUPER DC INVERTER MULTI TYPE INSTRUKCJA SERWISOWA

MULTI INVERTER SERIE H6M

KSIM20912-H216 KSIM30912-H216 KSIM40912-H216

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

Part 5. Troubleshooting. 1. Normal Air Conditioner Phenomenon Air Conditioner Protection in Common

CONTENTS. Product Specification..1 Refrigeration Diagram.. 3 Wiring Diagram.6 Troubleshooting Guide...9

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1

Service Manual CAUTION

Service Manual CAUTION. 40MBDQ Ducted Style Ductless System Sizes 18 to 48 ! WARNING

CAUTION DLFPHA. SERVICE MANUAL High Wall Ductless System Sizes 09 to 12 ! WARNING

KSIA SERIES SPLIT TYPE ROOM AIR CONDITIONER. For Split Wall Mounted Series R410a Inverter Model Type For F

Blanc ON-OFF Series. Service Manual 2016

Westinghouse. Split System Inverter Series. Service Manual

SERVICE MANUAL Room Air Conditioner DC Inverter Multi Split Outdoor units

FIXED SPEED SERIES - 50 HERTZ 2017 SERVICE MANUAL

KTIR AIR CONDITIONER SERIES TROUBLESHOOTING

Service Manual CAUTION. 38MAQ Outdoor Unit Single Zone Ductless System Sizes 09 to 30 ! WARNING SAFETY CONSIDERATIONS

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER

Owner s Manual Super-Slim Four-Way Cassette

Owner s Manual. Middle Static Pressure Duct Type MEU-18MPH2 MEU-24MPH2 MEU-36MPL2 MEU-48MPL2 MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER

KSD-35 DR11 KUE-35 DVN11

Troubleshooting & Reference

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC

Installation, Operation & Maintenance

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

E11 Indoor Board Failed to Receive Signal from Signal Output Board III - 65 E12 Automatic Address Setting is in Progress: Automatic Address Setting

KDIR TROUBLESHOOTING. Middle Static Pressure Duct Type SERIES

OWNER S MANUAL KPD-105 DTN11 KPD-140 DVN11 KPD-140 DTN11 KPD-160 DTN11 KPD-52 DVR11

Split DC Inverter Air Conditioner SERVICE MANUAL

CAUTION DLCPRA. SERVICE MANUAL Outdoor Unit Single Zone Ductless System Sizes 09 to 12 ! WARNING

CW-5000/5200 Series Industrial Chiller maintenance manual

Service manual. MIV V4+ Mini

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H

Table of Contents. Page. 1. Safety Precautions Specifications Product Features Maintenance and Disassembly...

Double Door Over 70. Service Manual. Models: F NMTZH 821 F T F NMTZH 822 F T

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX

HKD DCI Series REFRIGERANT R410A HEATPUMP SM HKD DCI 4-A.1 GB REFRIGERANT

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

SPLIT TYPE AIR CONDITIONER WAS-09HSTD WINTAIR

Multi zone Two, Three, Four and Five Zones

Fast Track Troubleshooting

Product Data FEATURES AND BENEFITS. QHF 50Hz Heat Pump Inverter Single Phase 2.5kW to 8.0kW

SERVICE MANUAL AS-09UR4SGN. Hisense Corporation 第 1/51 页

SERVICE MANUAL. Wall Mounted Type DC Inverter WARNING. Haier Group Version V1 Date

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02

SERVICE MANUAL. Wall Mounted Type DC Inverter WARNING. Haier Group Version V1 Date

3.4 SPINDLE AMPLIFIER MODULE

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

Room Air Conditioner Service and Parts Manual

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT

Model No.: PS08-01 PS10-01 Ref: KY80 KY100

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1

SERVICE MANUAL. Wall Mounted Type ON/OFF T-Series HSU-07HUN103/R2-P WARNING. Haier Group Version V1 Date

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

Fora Failure Algorithms

REFRIGERANT ON-VEHICLE INSPECTION AC 14

Mobile Type Air Conditioner

INSTALLATION AND USER MANUAL

Código de Erros Split Piso Teto

This air conditioner comprises an indoor unit, outdoor unit, and a connection pipe.

Service Manual. Inverter air conditioner TAC-18CHSA/JAI. Models CONTENTS. 1. Important Notice

Room Air Conditioner Service and Parts Manual

Transcription:

www.olmo-comfort.com TROUBLESHOOTING When below list for identification of error code occurs, please turn off air conditioner and disconnect power, and then contact the qualified professionals for service. Error code E0 E1 E2 E3 E4 E5 EC F1 F2 F3 F4 TROUBLESHOOTING Indoor unit EEPROM parameter error Indoor / outdoor units communication error Zero-crossing signal detection error Indoor fan speed has been out of control Indoor room temperature sensor T1 open circuit or short circuit Evaporator coil temperature sensor T2 open circuit or short circuit Refrigerant leakage detection Outdoor temperature sensor T4 open circuit or short circuit Condenser coil temperature sensor T3 open circuit or short circuit Compressor discharge temperature sensor T5 open circuit or short circuit Outdoor unit EEPROM parameter error F5 P0 P1 P2 P4 Outdoor fan speed has been out of control IPM malfunction or IGBT over-strong current protection Over voltage or over low voltage protection High temperature protection of compressor top diagnosis and solution Inverter compressor drive error WARNING When below phenomenon occurs, please turn off air conditioner and disconfor service. Power cord is overheating or damaged. There s abnormal sound during operation. Circuit break trips off frequently. Air conditioner gives off burning smell. Indoor unit is leaking. If the air conditioner operates under abnormal, it may cause

1. Diagnosis and Solution 1.1 EEPROM parameter error diagnosis and solution(e0/f4) E0/F4 Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip. Supposed causes Installation mistake Troubleshooting: Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? PCB faulty If the EEPROM chip is welded on main PCB, replace the main PCB directly. Otherwise, check whether the EEPROM chip plugged in main PCB well? Correct the connection. Replace the main PCB. EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. For the location of EEPROM chip, please refer to the below photos. Indoor PCB Outdoor PCB te: The two photos above are only for reference, it s may be not same totally with the ones on your side. 2

1.2 Indoor / outdoor unit s communication diagnosis and solution(e1) E1 Supposed causes Wiring mistake Troubleshooting: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously. Indoor or outdoor PCB faulty Power off, then turn on the unit 5 seconds later(reconnect the power wire).is the error still displaying after several minutes? Measure Vs, is it moving alternately with positive value? (Vs is the voltage between L2 and S of outdoor unit. Connect the red pin of multimeter with L2 port, black pin with S port) Check all the wiring with outdoor u n i t s. Is the wiring to the outdoor m a i n PCB connect e d correctly? I s the reactor connected well? M e a s u r e t h e r e s i s t a n c e o f t h e reactor(the one without capacitor). If it is zero,follow the below step. If not, replace a new reactor. Check all the wiring with indoor units. Is the wiring to the indoor main PCB connected correctly? Replace the outdoor main PCB. Replace the indoor main PCB. Power on. Is the error extinguished? Power on. Is the error extinguished? Replace the indoor main PCB. Replace the outdoor main PCB. 3

1.3 Zero crossing detection error diagnosis and solution(e2) E2 When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal. Supposed causes Connection mistake Troubleshooting: PCB faulty Check if the connections and power supply is normal? Correct the connections. Turn on the unit when the power supply is good. Indoor main PCB is defective. Replace indoor main PCB. 4

1.4 Fan speed has been out of control diagnosis and solution(e3) E3 When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure. Supposed causes Wiring mistake Fan ass y faulty Fan motor faulty PCB faulty Troubleshooting: Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? The unit operates normally. Shut off the power supply, rotate the fan by hand. Does it rotate properly? Find out the cause and have it solved. For example, check whether the fan is blocked or the bearing is broken? Check the wires of fan motor. Are all the connections good? Correct the connections. Check whether the fan motor is normal through index 1? Replace the fan motor If the malfunction is still existing, replace the main PCB Check whether the main PCB is normal through index 2? Replace the main PCB. The malfunction is solved? 5

1.5 Open circuit or short circuit of temperature sensor diagnosis and solution(e5) E5 If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure. Supposed causes Wiring mistake Sensor faulty Troubleshooting: Check the connections between temperature sensor and main PCB. Are the connections good? PCB faulty Correct the connections. Check the resistance value of the sensor via table1(p64)and table 2(p65), is it normal? Replace indoor or outdoor main PCB. Replace the sensor and check if the problem happen again? 6

1.6 Refrigerant Leakage Detection diagnosis and solution(ec) EC Define the evaporator coil temp.t2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 <Tcool 28.4 o F(-2 o C) does not keep continuous 4 seconds and this situation happens 3 times, the display area will show EC and AC will turn off. Supposed causes T2 sensor faulty Indoor PCB faulty System problems, such as leakage or blocking. Trouble shooting: Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? Is there cool air blowing out from indoor air outlet? Check if T2 sensor is well fixed. Correct the installation or replace T2 sensor. Does the problem remain again? Is there any leakage? Especially the connection parts, such as the gas valve and the liquid valve. Replace indoor PCB. Repair the leakage and recharge the refrigerant. Is there any blocking? (Such as the capillary or the welded points of the pipes.) Clear the blocking. 7

1.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(p0) P0 Supposed causes When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show P0 and AC will turn off. Wiring mistake; IPM malfunction; Outdoor fan ass y faulty Compressor malfunction; Outdoor PCB faulty Trouble shooting: Check if the wiring between main PCB and compressor connected by error and if the wires and connectors are broken? Correct the connection or replace the wires and connectors. IPM continuity check. Check if the IPM terminal resistance values are uniform. Replace the IPM board or replace the main PCB if the IPM board and main PCB are integrated together. Check if the outdoor fan runs properly or the outdoor unit ventilation is good. please refer to the below remark, check whether the resistance of the fan motor is normal. If not, replace the fan motor. Check if the compressor resistance values are uniform. Replace the compressor. Replace the outdoor main PCB if the main PCB and IPM are separate. 8

1.8 Over voltage or too low voltage protection diagnosis and solution(p1) P1 An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit. Supposed causes Power supply problems. Trouble shooting: System leakage or block PCB faulty Check if the power supply is normal. Disconnect the unit with power supply and try to restart the unit when power supply gets normal. Check if all the connections and wires are good? Correct the connections or replace the wires. Power on and when the unit is in standby, check if the voltage between P and N is around DC 310V or 340V or 380V? For different kinds of units, the voltage differs. Consult with technical engineer to get definite value. Then start up the unit, measure the voltage between P and N. Is it in 220V~400V? Replace the IPM board if it is separate with main PCB. Replace outdoor main PCB. 9

1.9 High temperature protection of compressor top diagnosis and solution(p2) P2 If the sampling voltage is not 5V, the LED will display the failure. Supposed causes Power supply problems. Trouble shooting: System leakage or block PCB faulty Check if the air flow system of indoor and outdoor units are obstructed? Clear up the air inlet and outlet or the heat exchanger of indoor and outdoor units. Turn off the power supply and turn it on 10 minutes later. Check if the unit can start normally. Check if all the connection, especially the connection of OLP (Over Load Protector) sensor is good. Correct the connection. Check if the refrigerant charge volume is normal? Measure the resistance between the two ports of the OLP. Is it zero? Replace the OLP. Replace the outdoor control PCB. Refrigerant system is blocked, such as capillary or welded point of pipes. Recharge the correct refrigerant volume. 10

1.10 Inverter compressor drive error diagnosis and solution(p4) P4 Supposed causes Trouble shooting: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on. Wiring mistake; IPM malfunction; Outdoor fan ass y faulty Compressor malfunction; Outdoor PCB faulty Check if the wiring between main PCB and compressor connected by error and if the wires and connectors are broken? Correct the connection or replace the wires and connectors. IPM continuity check. Check if the IPM terminal resistance values are uniform. Replace the IPM board or replace the main PCB if the IPM board and main PCB are integrated together. Check if the outdoor fan runs properly or the outdoor unit ventilation is good. please refer to the below remark, check whether the resistance of the fan motor is normal. If not, replace the fan motor. Check if the compressor resistance values are uniform. Replace the compressor. Replace the outdoor main PCB if the main PCB and IPM are separate.

www.olmo-comfort.com