FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

Similar documents
FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

FMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions

FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

Colibri. Automatic Tank Gauge CL6 Series Installation Guide

TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

Manual No: Revision: G. Sensor Products. Application Guide

Interstitial Liquid Sensor - Fiberglass Tanks

Fuel Management System Setup Guide

Manual No: Revision: H. MicroSensor. Installation Guide

Manual No: Revision: D. Sump Sensor. Installation Guide

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS ASHP, ASHH, ASUP, and ASUH

Manual No: Revision: J. Groundwater Sensor. Installation Guide

INSTRUCTION MANUAL. Revised: July 2, 2017 DRAWING NO REV. A LC1000 SERIES INTRINSICALLY SAFE ALARM CONSOLE

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

AUTOMATIC TANK GAUGES

C Electrical Connection Kit

M1500 SiteSentinel itouch Tank-Gauge Monitoring System Installation Guide. Part Number: M1500, Rev. 5

2 To 1 Sensor Input Box

LS500 Auto Learn Line Leak Detection

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

1993 Pond Rd., Ronkonkoma, NY Tank Gauging Liquid Level and Leak Detection Systems Relays. OEL8000II Installation Manual PRINT MENU DEL 1 ABC

INSTALLATION & OPERATING INSTRUCTIONS

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

Installation Electric Dryers Instructions 01

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

Variable Speed Flow Controller

Getting Started Quick Reference Guide

INSTALLATION GUIDE Dual Fuel Ranges

Viking Installation Guide

LED Flex Tube Assembly Guide

Remote Chexit Module (RCM) System. General Information

DE5300 Delayed Egress System. General Information

Installation Instructions

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Multi-Function Cooktop

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

SECTION ELECTRICAL GENERAL PROVISIONS

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

Operator s Manual CAYENNE HEAT N SERVE 4/3 RECTANGULAR RETHERMALIZER ENGLISH

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

Operating Instructions (ENG) MODEL: 115 V UL LISTING FOR 1/2 HP MODELS ONLY. Read instructions before operating the machine J 07/05/07

Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

PO Box 827 Hawley, MN (218) Fax (218)

TRUERH Series HE-67xx Humidity Element with Temperature Sensor

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SiteSentinel Integra 100 /500 Automatic Tank Gauge System Installation Manual

Installation Instructions

LGB Gas fired boiler

RK-05 Combustible Gas Transmitter Operator s Manual

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A

THREE CHANNEL CONTROLLER OMNTEC

Installation and Maintenance Manual. Model 154XST Series Strobe Light for Use in Hazardous Conditions. français...page 21 español...

SINGLE CHANNEL CONTROLLER

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Installation Instructions

NINE CHANNEL CONTROLLER OMNTEC

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Dishwasher Installation Instructions DW 24XT/DW 24XV

THE BEAUTY OF WATER THE SCIENCE OF RENEWAL. Heating Circulation System. Installation Instruction Manual

Installation Manual INTEGRATED MONITORING SYSTEM.

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.ca

Easy Dose Chemical Injection and Dispensing System DEMA Engineering Company

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.com

Installation Instructions

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

Flood Pumper Plus. Water Transfer Machine. Operator and Parts Manual. Model No.: Rev. 00 (11-99)

Installation. 324 Series Built-In Dishwashers U L. Viking Range, LLC 111 Front Street Greenwood, Mississippi USA (662)

Product Code for Zoom: KPLZML1RGBW Product Code for Wall Wash: KPLWWL2RGBW

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

Reliance DuraStar ATEX HAZARDOUS LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS

Installation Instructions for the LatitudeTM Solaris Stick Light Models SL8C-xxx

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire.

ELECTRIC WALL OVEN INSTALLATION INSTRUCTIONS

PORTABLE HAND POWER THREADER 1/2-2

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions

REPLACEMENT PARTS MANUAL

Installation Instructions Remote Blowers

AMP Low Voltage Landscape Lighting In-Grade Well Light AWL-55xx and VWL-55xx Series

3MAVR60XX Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3MAVR60XX

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

Heat Exchanger Block Replacement Instructions

Table of Contents. Important Safety Instructions. WARNING: If the instructions contained in this manual are not followed

PORTABLE HAND POWER THREADER 1/2-2

Installation Instructions

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

Next Generation Corona Discharge Installation & Operation Manual

Transcription:

FMP-DIS & FMP-EIS Interstitial BriteSensor & Standard Sensor Installation Instructions FMP-DIS Sensor FMP-EIS Sensor Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com

Overview The FMP-EIS is a Standard sensor and the FMP-DIS is an intelligent BriteSensor. These sensors are used to detect the presence of liquids in the normally dry interstitial (annular) areas of double-wall fuel storage tanks (a Class 1, Division 1, Group D Hazardous Area). Both types of sensors use electro-optical technology (LED & Prism) for liquid-detection. 3.35" (85 mm) 1.15" (29 mm) Weatherproof junction box, gasket, and cover, plus a 3/4 to 1/2 inch NPT reducing bushing if 1/2 inch RMC is used see the ATG Installation Guide for recommended electrical junction boxes. Wire: THHN, TFFN or THWN, 18 AWG: Red, White, & Black or Alpha Cable # 58113, 0.131 O.D. 1,500 feet (457 meters) maximum length. Alpha cable #58113 (INCON P / N 600-0063) must be used when using nonmetallic (PVC) conduit. Slip joint pliers to seat the no-strip, self-sealing wire connectors (connectors are included with the sensor). Thread UL approved sealant or pipe dope as required for installation in UST interstitial areas (Figure 2). Sensor Cable Riser Pipe Figure 1: FMP-DIS and FMP-EIS Dimensions The FMP-EIS communicates its current detection status to the ATG console (water present or normal no liquids detected). An open-circuit is recognized as an alarmcondition. The FMP-DIS sensor is enhanced with conductivity pins which allows it to discriminate between water and product. The FMP-DIS also communicates its identification code and current detection status to the ATG console (water present, product present, or normal no liquids detected). Both sensors are supplied with no-strip electrical wire connectors, 25 feet of cable, a Model ID tag, and a cordgrip fitting for connection to a weatherproof electrical junction box (see diagrams). Testing the Sensors Dip the tip of the sensor in a clean cup of water a standard sensor alarm is generated for a FMP-EIS sensor and a water alarm is generated for the FMP-DIS sensor. When dipped in isopropyl alcohol, the FMP-DIS sensor will produce a product alarm. Test sensors on a yearly basis, or more frequently per local code. During service & operation testing, the sensor should be inspected, and cleaned if soiled. Materials Required Optional TSP-DB1 Epoxy Seal kit for no-strip electrical connectors recommended for sites: within flood zones, high groundwater tables, with poor drainage, or when Junction Boxes are not used. ½ or ¾ inch NPT (National Pipe Thread, tapered), Rigid Metal Conduit (RMC) or nonmetallic (PVC) conduit if allowed by local codes. EYS Seal fittings and Epoxy to fill the fitting after operational testing is completed. Doublewall Fiberglass Tank Pull Wire Cover For 14 Inch (35.56 Cm) Min. Dia. Manhole Manhole Double Wall Fiberglass Tank Pull Wire Annular Space Interstitial Sensor (FMP-EIS or FMP-DIS) TSP-K12 Riser Cap (With Cord Grip - Compression ) Concrete Slab Per NFPA 30 Clean Fill Material (Gravel Typical) Weatherproof Junction Box Compression (Cord Grip) Eys Seal 1/2 or 3/4 Inch Conduit 2 Inch (50.8 Mm) Riser Pipe Interstitial Area (Dry) FMP-DIS or FMP-EIS Sensor Figure 2: Installation in Double-Walled Fiberglass Tanks TSP-KI2 Riser Cap for 2-inch riser pipes, includes a pre-installed 1/2 inch NPT compression gland (cord grip) fitting. Other riser caps are available for different riser pipe sizes consult your factory rep. Riser pipe 2 inch diameter, threaded at one end (NPT-14) with all rough edges removed / deburred from the inner edges. (The outside diameter of a 2 inch pipe is 2.38. The thread is 11-1/2). 2

Installation Sequence 1. * Install riser pipe, manhole. 2. Install conduit, EYS fittings, and weatherproof junction box. Note: Test the sensor before installation by immersing it in water and away from light. Verify that an alarm is produced at ATG console (FMP-DIS: water alarm, FMP-EIS: Sensor alarm). 3. Shut off power. ELECTRICAL DANGER Avoid electrical shock hazards: ensure all power going to the ATG console is turned off, tagged, and locked-out at the power panel before doing any maintenance or installation work at the ATG console 4. Interstitial installation (Figure 2), measure the length of the riser pipe + 1.5 x diameter of tank = total length. Mark this length on the cable and pull it through the FMP-KI2 riser cap cord-grip until the mark is 12 inches (30.5 cm) above the fitting. Tie one end of the pull-wire to the sensor pull cap and pull the wire until the sensor cable moves just above the cord-grip (leave the pull wire in place and loop the wire around the cable) and then tighten the fitting. 5. Interstitial installation (Figure 3), measure the INSTALL HEIGHT needed and add 1.5 inches for the riser cap = total height. Mark the total height required on the sensor cable, and pull the cable through the TSP-KI2 riser cap until the mark shows at the top of the cord grip fitting. Tighten the fitting and lower the sensor into the interstitial area of the tank as shown in Figure 3. Install Height (Measured) Double Wall Steel Tank Cover For 14 inch (35.56 cm) Min. Dia. Manhole Manhole TSP-K I2 Riser Cap (With Cord Grip - Compression ) Concrete Slab Per NFPA 30 Clean Fill Material (Gravel Typical) Weatherproof Junction Box Compression (Cord Grip) Eys Seal 1/2 or 3/4 Inch Conduit 2 Inch (50.8 Mm) Riser Pipe Interstitial Area (Dry) FMP-DIS or FMP-EIS Sensor Figure 3: Installation in double-walled Steel Tanks 6. Pull the sensor cables through the cord grip fitting at the junction box and tighten all remaining cordgrip fittings. Trim wire/cables to a 6 or 8 inch (15 or 20 cm) service-loop and splice the sensor and console wires together per Figure 4. 7. Power up console for next step. 8. Seal EYS seal fittings and electrical connectors with epoxy. 9. Turn off power again if other devices are to be installed (Repeat Step 3). 10. Reinstall all safety covers and guards, junction box gasket and covers use pipe-dope to seal all fitting threads. 11. Install the manhole cover. 12. Record the location where the sensor was installed on the chart on the back page of these instructions. This information will be needed when programming the ATG. 13. Turn on power and program the ATG Ref: all relating to Sensors in the Setup / Programming & Installation manuals. General Installation Notes * Steel double-walled tanks: codes may require a nonconductive isolation-bushing be installed between the tank and riser pipe. Warning It is the installer s responsibility to comply with all applicable federal, state and local codes. Failure to do so may create an Environmental Hazard. Plan your conduit routing. Dig trenches as necessary to install conduit from each junction box to the Intrinsically Safe (I.S.) knockouts at the ATG console. You must install a weatherproof, electrical junction box inside each manhole. The junction box should be installed high on the manhole wall to prevent it from being submerged during heavy rains. * Fill the bottom of the manhole with crushed stone to facilitate drainage when the sensor is installed in the interstitial space of a steel tank. Do not cover the top of the riser cap with fill material, it must remain accessible for service / sensor installation. The conduit may enter the manhole either from the bottom or the side. A junction box may be used inside of the building as a pull box to combine several sensor cables. If this is done, then only one I.S. conduit knockout will be used. Warning WARNING Conduits must have EYS seal fittings installed in accordance with NFPA 70 (National Electric Code) and NFPA 30A (Automotive and Marine Service Station Code). Failure to seal conduits in accordance with NFPA 30A, and NFPA 70 could allow flammable vapors to travel through the conduit in the ATG console. An explosion could result causing serious injury, property loss, or death. 3

4 Control Drawing: 1 of 2

Control Drawing: 2 of 2 5

Caution CAUTION Seal all threaded fittings and conduit threads to produce a weatherproof seal. Electrical Wiring Refer to the ATG Installation Manual for sensor wiring details. Blk 3 Wht +Red Blk 2 Wht +Red Blk 1 Wht +Red PWR (RED) IN (WHT) 3 Wires/cable from console 3-conductor cable from sensor GND (BLK) Note: The PWR (red) terminal is only used with 3-wire sensors Insert the unstripped wires fully into the self-sealing, no-strip electrical connector. Use slip-joint pliers and seat the black portion to make a good electrical connection TO 3-WIRE SENSOR Figure 4: FMP-DIS / FMP-EIS Wire Splicing and Console Wiring Record Sensor Location Sensor Channel # / Notes www.franklinfueling.com 2016 FFS 000-2086 Rev 2