An Assessment of Wine Room Air Conditioner Units for Noise and Cooling capacity

Similar documents
COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units

Appendix A Equipment Used to Monitor Hotels

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

Executive Summary 4G WiMax Radio Access Cabinet

Redesign of Bennett Hall HVAC System

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

A M E M B E R O F T H E K E N D A L L G R O U P

High-Efficiency Gas Furnace Designed with Your Comfort in Mind. Infinity 96 Gas Furnace with ComfortHeat Technology UP TO.

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Draft Control D R A F T C O N T R O L G U I D E w w w. f i e l d c o n t r o l s. c o m August 2007

WILLHI WH1436H Digital Humidity Controller Manual (NEW VERSION)

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

LOW COST FOOD STORAGE TECHNOLOGY: ENERGY SAVINGS AND PRODUCE STORAGE QUALITY. Ben Weil Luke Doody University of Massachusetts Amherst

Variable Refrigerant Flow (VRF) Systems

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating

Optimizing Electric Humidifier Operation with an Air Side Economizer

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Pacific Gas and Electric Company

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Dehumidifying with Dedicated Outdoor Air

Nest Learning Thermostat Summer 2012 Savings

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

Psychrometric Engineering Applications

The Only Gas Furnaces Made in Canada napoleonheatingandcooling.com

Test, Adjust, and Balance Services Submittal

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

Attractive. Selling a higher form. (up)selling Guide. Infinity 18VS heat pump & Infinity 19VS air conditioner

EHH SERIES DRAW THROUGH FAN COILS CFM

Temperature. In the HVAC area, we talk about two kinds of temperatures.

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

J. LINES, Graham Corp., Batavia, New York

HE-B Series Commissioning Report & User Guide

How to Cut Chiller Energy Costs by 30%

HICOSYS FOR PROCESS CONTROL OF SPRAY DRYERS

Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane.

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Technical Description. Laboratory Climate Test Chamber. System Weiss. Mat. No.: Type WKL 34/40

DISTRIBUTION SYSTEMS. Water Piping and Pumps

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Closing the Loop What s best for your system?

Infinity ICS Gas Furnace with IdealComfort Technology

Infinity ICS Gas Furnace with IdealComfort Technology

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

The Electronic Newsletter of The Industrial Refrigeration Consortium Vol. 11 No. 1, 2011

A/C Cooling Load calculation and measurement

LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

EC Series Wall Unit Humidifier

Seasonal Efficiency Longevity Part-Load Efficiency Condensing Operation Fast ROI MODULEX BOILERS MLX-1060 MLX-909 MLX-757

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

MD and Its Impact on Lab Facilities

The Only Gas Furnaces Made in Canada napoleonheatingandcooling.com

Development of the San Ace Airflow Tester - A Measuring Device for System Impedance and Operating Airflow of Equipment

Energy and Peak Power Reduction from Air Misting Products Applied to Commercial Condensing Units in Hot and Humid Climates.

Smart thermostat with Humidification/De-humidification control

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

9700 SERIES GAS FURNACES napoleonheatingandcooling.com

Final Report. Prepared for. Albany, NY. Robert M. Carver, P.E. Senior Project Manager. Prepared by. Ithaca, NY

Energy Recovery Ventilation

Reduce your energy use and save money year-round with ENERGY STAR certified appliances.

APC APPLICATION NOTE #109

Performance 96 Gas Furnace with Comfort Heat Technology

Constant climate chamber with ICH-compliant illumination

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration

Big Board Rework. Joerg Nolte Ersa GmbH Wertheim, Germany

Published by the California Building Performance Contractors Association

Residential Demand Controller Program

Humidity Generation and Humidity Measurement The Complete Guide

Benefits Offered by Passive Dehumidification Wheel Speed Control

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Sound Performance Rating of Outdoor Unitary Equipment

Farm Energy IQ. Farms Today Securing Our Energy Future. Tom Manning, New Jersey Agricultural Experiment Station

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower

High Performance Building Guide 1

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Minco SmartHeat SLT Self-Limiting Thin-Film Heater Technology

USER S INFORMATION MANUAL

Application Engineering

Experimental analysis of r134a, r22, and r404 for an edibon taab: Air conditioning lab unit

Optimisation of cooling coil performance during operation stage for improved humidity control

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Constant climate chambers. Always the right climate KBF KBF P KBF LQC KMF series

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Model KBF 1020 Constant climate chambers with large temperature / humidity range

Check out your benefits: Screw compressors SDF series

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Transcription:

An Assessment of Wine Room Air Conditioner Units for Noise and Cooling capacity Prepared for: Air Innovations 7000 Performance Drive North Syracuse, NY 13212 Final Report, August 8, 2010 Prepared by: Clarkson University, Center for Atmospheric Research in Science and Engineering (CARES)

Wine enthusiasts store and age fine wines and have special requirements that are not often satisfied by typical air-conditioning equipment. Commercially available air conditioners are provided by a number of manufacturers to control the internal environments of a wine storage rooms. A variety of designs are available for the consumers to select. This report is a summary of an assessment performed on five different wine room air conditioning units. Tests were performed to assess noise levels inside and outside the test room, the air flow on both sides of each unit and the cooling capacity for each unit under tightly controlled conditions. The units tested included two units from Air Innovations - Wine Guardian Models TTW018 and TTW009, two units from WhisperKOOL models - 4200 and 8000, and one unit from Breezaire. The testing was performed at Clarkson University during the spring of 2010. All five units were tested under the same environmental conditions which included a simulated wine room inside temperature of 58+/-1 F, relative humidity of 54 +/- 1 % RH and outside room temperature of 75+/-2 F. There was no criterion for relative humidity for the outside room position, yet remained ~30% throughout the series of tests. Study findings: 1. The Wine Guardian units were the most energy efficient units of all of the units tested when run in the continuous cooling mode. 2. Wine Guardian units produced lower noise levels by greater than 4 db(a). 3. The cooling capacity of the Wine Guardian units was found to be similar to the WhisperKOOL units of comparable size. However, the Whisper KOOL units were found to use significantly more (> 50%) energy during cooling. Evaluation conditions and Experimental Set-up All Units were tested in an 8 x12 x7 room. The room was cooled to the target temperature of 58 F with a window air conditioning unit. Humidity was controlled to 54% RH with a humidification unit designed for homes. The capacity of the room air conditioning unit and humidification unit were significantly over sized for the test room, yet this allowed for the relatively quick adjustment of the room conditions to the target temperature and humidity levels for testing each unit. The units tested included: 2

Wine Guardian Models TTW018 and TTW009 Manufactured by Air Innovations WhisperKOOL Models, Manufactured by Vinotheque Models: 4200 ( ~1000 ft 3 maximum room size ) and 8000 (~2000ft 3 maximum room size) Breezaire, by Breezaire Products Company Model WKL 4000 for a ~1000 ft 3 room 3

All units tested were through-the-wall type designs. Each unit was mounted into a 2 x 2 foot opening in a wall of a room with the following dimensions, 12 x 8 x 7 feet for each test. Insulation was packed around the unit to ensure the air was not transferred from the inside of the room to the outside of the room. Upon completion of the test, the unit was removed from 2 x 2 foot opening and the next wine room air conditioning unit was installed in the same location. The room was allowed to reach the 58/54 target values and the tests were completed. The following data was collected for both the intake and supply for both inside the room and outside of the room: Air flow (ft 3 /min), Dry bulb temperature ( F), Relative humidity (%RH), and noise levels (db(a). The air flow measurements were taken with an ALNOR Balometer hood. This device measured the volumetric flow rate of air from both the supply and return section of the unit. Special templates were developed to fit the Balometer to each unit and ensure the air flow was collected only from the section of the air conditioning unit of interest. Essentially the templates segmented the return air from the supply air and allowed for an accurate measure of the air flowing into the unit versus out of the unit. Finally, a meter was connected to each unit during the continuous cooling to determine the energy use in watts. A Fluke 975 Air Meter (Fluke Corporation) was used to measure the dry bulb temperature and relative humidity. The noise levels were measured with a Quest 2800 sound level meter (Quest Technologies) and air flow measurements were collected with an ALNOR Model - LoFlo Balometer 6200F. Calibration certification (# 70715255) by TSI incorporated. All measurements were collected in spring and summer of 2010. Findings: Detailed data tables and diagrams of the units are displayed in Appendix A. A summary is provided in Table I. The noise levels were taken at distances from 1 to 4 feet on the outside section of the unit. The levels at four feet ranged from a low of 56.4 db(a) for the TTW009 Wine Guardian unit to a high of 61.1 db(a) for the Breezaire unit. Noise levels are expressed in a log scale [Sound pressure levels (SPL = 20 Log(P/Po)], thus the difference in noise levels between the high and low unit varied by almost 5 fold. The cooling capacity was calculated using the difference between the intake enthalpy and supply enthalpy multiplied by the air flow and corrected to the appropriate units. The cooling capacity ranged from a low of 757 to a peak of 2972 Btu/hr. However, the units were rated for different size rooms, thus the variability was expected. The units sized for larger rooms, TTW018, WhisperKool 8000 and the Breezaire were found to produce a similar cooling capacity, 2165, 2972 and 2315Btu/hr. However, a watt meter used to measure the energy consumption displayed during peak cooling showed significantly lower consumption values for both Wine Guardian units as compared to the other units of similar size, suggesting that the Wine Guardian units will have a better cooling capacity per unit energy consumed. 4

Table I. Summary Data of the Wine Room Air Conditioning Units Wine Room Units Noise @ 4 (dba) Supply (Ft 3 /min) Cooling Capacity (Btu/hr) Energy (Watts) Wine Guardian TTW009 57.3 99 1007 288 Wine Guardian TTW018 56.4 147 2163 358 WhisperKOOL 4200 61 130 1112 473 WhisperKOOL 8000 59.3 337 2972 677 Breezaire WKL 4000 61 166 2316 608 Delivered voltage 112.3v The attached spread sheets show all the data for each unit. The temperature and RH measurements are quite constant. The air flow measurements were taken from the return air side for all the units. Measurements were repeated several times to ensure the flow rate was constant. In summary, the Wine Guardian units operate at the lowest noise levels and maximize cooling at in the most energy efficient manner. 5