File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 REPORT

Similar documents
Issued: January 13, 2006 Revised: April 21, 2009 REPORT. Automatic Sprinklers. The Viking Corporation Hastings, MI

File EX CA March 31, 2010 REPORT RESIDENTIAL SPRINKLERS. Viking Corp Hastings, MI. Copyright 2010 Underwriters Laboratories Inc.

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

File Ex643 Project 96NK8906 *Project 98NK Issued: January 31, 1997 Revised: October 21, 1999 REPORT SPRINKLERS, AUTOMATIC AND OPEN

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531

freedom residential flush pendent sprinkler vk476 (K4.9)

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

freedom residential concealed pendent sprinkler VK488 (K3.0)

freedom residential concealed pendent sprinkler vk474 (K5.8)

STANDARD/quick. Sprinkler 42o. August 8, 2011

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0.

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA

mirage standard response concealed pendent sprinkler vk492 (K5.6)

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

TECHNICAL DATA OBSOLETE

Standard Spray concealed horizontal sidewall sprinkler VK481

freedom residential concealed pendent lead free sprinkler

TECHNICAL DATA OBSOLETE

Quick response concealed horizontal sidewall sprinkler VK481

quick response Sprinkler 105a October 25, 2010

FREEDOM RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER VK480 TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

sprinkler vk538 (K11.2)

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

freedom residential concealed pendent Sprinkler vk458 (K7.4)

standard response Fusible Link Upright sprinkler VK204 (K8.0)

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

TECHNICAL DATA. UL/C-UL Listed as a standard response. horizontal ceilings. Listings up to a OBSOLETE

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

MIRAGE EC/QREC OH-ELO CONCEALED PENDENT SPRINKLER VK538 (K11.2) TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

quick response horizontal sidewall sprinkler vk360 (K8.0)

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA OBSOLETE

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

TECHNICAL DATA OBSOLETE

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

standard response fusible link sidewall sprinkler VK112 (K5.6)

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK498 (K5.8) TECHNICAL DATA

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

standard response dry horizontal sidewall sprinklers

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

micromatic standard response stainless steel sprinklers

INSTITUTIONAL QUICK RESPONSE FLUSH HORIZONTAL SIDEWALL SPRINKLER VK412 (K5.6) TECHNICAL DATA

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

freedom residential horizontal sidewall sprinkler Vk450 (k4.2)

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

Residential Sprinkler For Sloped Ceilings

microfast quick response Pendent sprinkler VK302 (K5.6)

standard response elo upright and pendent sprinklers (storage-density/area)

esfr pendent sprinkler vk510 (k25.2)

TECHNICAL DATA. The Viking Corporation s Web site at Overall Length (Sprinkler Body): 2-5/16 (59 mm)

standard response large orifice dry

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

microfast quick response extended coverage hsw sprinkler vk606

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

micromatic Standard response Horizontal Sidewall sprinkler

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

Transcription:

File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 Issued: August 3, 2006 Revised: April 29, 2009 REPORT on RESIDENTIAL SPRINKLERS Viking Corporation Hastings, MI Copyright 2006 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above named company to reproduce this Report provided it is reproduced in its entirety.

File EX3836 Page G1 Issued: 2006-08-03 Revised: 2008-12-30 GENERAL INTRODUCTION: This Report describes the investigation of residential sprinklers intended to be installed in accordance with the National Fire Protection Association Standard For Installation Of Sprinkler Systems For One- And Two-Family Dwellings And Mobile Homes, NFPA 13D, Installation Of Sprinkler Systems In Residential Occupancies Up To Four Stories In Height, NFPA 13R and Installation Of Sprinkler Systems, NFPA 13. OBJECT: * The object of this investigation was to determine compliance of the residential sprinklers with the Fourth Edition of the Standard For Residential Sprinklers For Fire Protection Service, UL 1626, the Canadian Standard for Automatic Sprinklers ULC/ORD C1626-03, and The Outline of Investigation for Fire Testing of Residential Sprinklers for Use with Smooth, Flat, Sloped Ceilings Having Pitches Not Exceeding 8/12, Subject 1626A. PLAN: The investigation of the residential sprinklers consisted of conducting a design parameter and installation instruction review, construction evaluation and performance testing as described in UL 1626,4 th Edition, Subject 1626A, Issue No.1, and the Canadian Standard for Automatic Sprinklers ULC/ORD C1626-03, 1 st Edition.

File EX3836 Page 1 Issued: 2006-08-03 Revised: 2009-04-29 DESCRIPTION PRODUCT COVERED: VK456, concealed pendent style sprinkler, discharge coefficient K = 4.9, fusible link heat responsive element, 140 F temperature rated VK457, concealed pendent style sprinkler, discharge coefficient K = 4.9, fusible link heat responsive element, 165 F temperature rated VK474, concealed pendent style sprinkler, discharge coefficient K = 5.8, fusible link heat responsive element, 165 F temperature rated These sprinklers have a maximum pressure of 175 psig for wet systems only for spacings and flow rates as indicated below: SIN Style FOR INSTALLATION UNDER SMOOTH, FLAT CEILINGS Nominal Maximum Minimum Flow, Temperature K-Factor Sprinkler gpm/sprinkler Rating, F Spacing, ft. psig 140 4.9 14 by 14 13 7.0 Flowing Pressure, 140 4.9 16 by 16 14 8.2 140 4.9 18 by 18 17 12.0 140 4.9 20 by 20 23 22.0 165 4.9 16 by 16 13 7.0 165 4.9 18 by 18 18 13.5 165 4.9 20 by 20 20 16.7 165 5.8 16 by 16 16 7.6 165 5.8 18 by 18 19 10.7 165 5.8 20 by 20 23 15.7 *

File EX3836 Page 2 Issued: 2006-08-03 Revised: 2009-04-29 SIN FOR INSTALLATION UNDER SLOPED CEILINGS 2/12 TO 8/12 (IN./IN.) PITCH TESTED PER SUBJECT 1626A, ISSUE NO. 1 Maximum Temperature Nominal Sprinkler Minimum Flow, Style Rating, F K-Factor Spacing, ft. gpm/sprinkler USL VK456 Concealed USL VK456 Concealed USL VK457 Concealed USL VK457 Concealed All sprinklers utilize a 135 F cover plate. Flowing Pressure, psig 140 4.9 16 by 16 17 12.0 140 4.9 20 by 20 26 28.2 165 4.9 16 by 16 26 28.2 165 4.9 20 by 20 31 40.0 ENGINEERING CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE'S USE): USL - indicates Listing to UL1626. CNL - indicates Listing to Canadian Standard ULC/ORD-C1626-03. GENERAL CHARACTER: The SIN VK456, VK457 and VK474 residential sprinklers are automatic sprinklers of the fusible link heat responsive element type consisting of a frame, deflector, pin arms, lever, lever bar, fusible link heat responsive element, screw, button, seat, Teflon coated Belleville spring washer, and a concealed round or square coverplate assembly. The chart below illustrates the decorative type of paints/finishes to be utilized on the coverplates. The application process for these paint types is to be performed by the Viking Corp. Paint Type Maximum Thickness, Mils (in.) Paint Color Acrylic Latex 1.5 (0.0015) Any Lacquer 2.0 (0.002) Any Enamel 2.0 (0.002) Any Alkyd Enamel 3.0 (0.003) Any Latex 4.0 (0.004) Any Urethane 4.0 (0.004) Any Catalyzed Epoxy 5.0 (0.005) Any Acrylic 5.0 (0.005) Any USE: The residential sprinklers are for use in their intended operating position only in accordance with the National Fire Protection Association Standards For Installation Of Sprinkler Systems, NFPA 13D, NFPA 13R, and NFPA 13; and the manufacturer's installation instructions.

File EX3836 Page C1 Issued: 2006-08-03 CONCLUSION Samples of the product covered by this Report have been found to comply with the requirements and the products are judged to be eligible for Listing and Follow-Up Service. The manufacturer is authorized to use the UL Mark on such products which comply with the Follow-Up Service Procedure and any other applicable requirements of Underwriters Laboratories Inc. Only those products which properly bear the UL Mark are considered as Listed by Underwriters Laboratories Inc. Report by: Steven J. Wisniewski Lead Engineering Associate Reviewed by: Michael G. McCormick Lead Engineering Associate