Installation and Operating Instructions. -Suction Gas Heat Exchanger-

Similar documents
Installation and operating instructions. DK energy storage and DK energy buffer

Operating instructions Open two-stage compressor FZ 16

OIL SEPARATORS APPLICATIONS

Operating instructions for semi-hermetic motorcompressors

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

Service Manual For electronic dual temperature zone wine cellar Includes DWC282 / 283

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

How to deal with ...R410A MITSUBISHI ELECTRIC R32 R125 R410A AIRCONDITIO NING

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Installation Instructions

Instruction Manual. Pharma-line ESE02198-EN Original manual

Air Conditioner. user installation & manual manual. imagine the possibilities

SEMI-HERMETIC SCREW COMPRESSORS

RCM Refrigerant Module

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

Geberit Supply Systems. Mapress and Mepla

R Series Cooling Modules

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

R Series Cooling Modules

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

hygienic design CLEANLINESS MADE TO MEASURE: HYGIENIC DESIGN FANS

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

42PHW / 42PHQ 42PHQ...K

HELMUT KÄMPKEN GMBH OPERATING MANUAL

Liquid Chillers Grasso BluGenium. Product Information (Translation of the original text) L_141011_1

THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC

M P 1 2 F G C O M P R E S S O R TECHNICAL SPECIFICATIO N

MBWeich 100. Operating manual. 1. Introduction. 2. Use

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1

Daikin Direct Expansion (DX) Cooling Coils

Flameproof Manual Call Points

Pressure switch KPU. Data sheet

Operating manual Spare parts list Stone cutoff saw TME700P

Installation Instructions

Installation instructions Danfoss heat pump DHP-R

UPFLOW/DOWNFLOW COILS

ISHRAE. Guideline document to ISO Version 1 Feb Indian Society of Heating, Refrigerating and Air Conditioning Engineers

Installation Instructions

Air Cross 21 Installation and User Manual

SANCO. Once you've used SANCO you'll never use anything else. [GB] SANCO. KME Germany GmbH & Co. KG

[FLARE CONNECTION TYPE] ATTENTION

VCYL. Liquid sight glasses 9.1 NEW. Refrigeration & Climate Components Solutions. Max WP 46 bar and multi-fluids (G1 or G2) n Applications

Installation Instructions

R Series Cooling Manual

Industrial cooling systems LT

CONDOR-H (horizontal) / CONDOR-V (vertical)

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

DUST COLLECTOR OPERATION AND SAFETY INSTRUCTIONS FM230 CAUTION: READ THE INSTRUCTION MANUAL BEFORE USING THE APPLIANCE

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

Tradition & Technology

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

Owner s Manual Window Air Conditioner

GE Monogram. Installation. Instructions. Stainless Steel Bottom Mount Built-In Refrigerators. Models ZICS36N RH ZICS36N LH

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

COLD. Basic Training Course II. November ESSE - Wilhelm Nießen

Installation and maintenance condensing unit manual

Industrial Tubes. TECTUBE _cips, TECTUBE _med [GB] KME Germany GmbH & Co. KG

Installation of Glass Lined Equipment

NE6210CZ NE6210CZ C O M P R E S S O R TECHNICAL SPECIFICATION HUANGSHI DONPER ELECTRICAL APPLIANCE CO., LTD

BRAZED PLATE HEAT EXCHANGERS

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

TURBOIL (welded) / TURBOIL-F (flanged)

FINO Kältetrockner. Original FINO

Room Air Conditioner SERVICE MANUAL MODEL : LW6013ERY3. CAUTION

Bulletin , March Electric Hot Gas Bypass Valves

Room Air Conditioner Service and Parts Manual

Please read the following installation instructions first after purchasing this product or transporting it to another location.

Water-Cooled Dual Compressor Screw Chiller

DK-HEAT RECOVERY FOR TRANSCRITICAL CO 2 REFRIGERATION SYSTEMS

CFF-500 CHILLER. Operator s & Installation Manual. Release Date: November 3, 1996 Publication Number: Revision Date: March 25, 2014 Revision: F

Refrigerator KE T

12.0 cu.ft., 2 way, 4-door, R.V. refrigerator with ice maker.

FSW300 Series Flow Switch

ENERSAVE Hydrocarbon Scroll Water Cooled Chiller

Inspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

EN-CV: LHCb SciFi Common chiller. Martin Doubek September 25, 2017

MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS

ROCOOL For commissioning, maintenance work and documentation of refrigeration systems of all kinds An absolute all-rounder due to the unique

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Repair instruction and handling for Isobutane (R600a) refrigerant.

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

M2 Series Startup Form

EkoAir Heat exchanger selection manual.

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Practical Application of Refrigerants R 600a and R 290 in Small Hermetic Systems

PWM expansion valves 2028

DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

TECHNICAL SERVICE GUIDE

Three-way reversing valve

Installation Instructions

Transcription:

Installation and Operating Instructions -Suction Gas Heat Exchanger- Issue: 08-2011

Preface With this Heat Exchanger, you have purchased a DK quality product. DK products are manufactured according to the relevant standards and recommendations. Each unit is carefully inspected and all components undergo compression trial which allows us to supply you with a reliable system. A long and trouble-free service life requires an expert installation and commissioning of the unit. For your own benefit, the following assembly notes should be closely observed. The documentation in your hand complies with state-of-the-art technology available at the date of issue. The manufacturer reserves the right to perform technical alterations according to the further development of the product. We wish you a successful application of your DK Heat Exchanger DK-Kälteanlagen GmbH, D-48282 Emsdetten, Germany

1. Table of Contents 1. Table of Contents...1 2. Safety Notes...2 3. Service...3 4. Fitting and installation...4 4.1 Refrigerant Connection...4 5. Commissioning the system...7 6. Operation...7 7. Maintenance...7 8. Dimensions...8 9. Technical data...9 1

2. Safety Notes Please observe the following for your personal safety as well as for the maintenance of your warranty: The assembly and starting of the refrigeration system may only be performed by trained licensed experts who hold the required permits. Such installation staff must observe the generally applicable regulations of the UVV/VBGA for Electrical Plants and Equipment as well as all applicable regulations (VBG20). Repair work which exceeds the maintenance work stipulated in this technical documentation must only be carried out by qualified experts. For this, please refer to your refrigeration expert. DK-Kälteanlagen GmbH is not liable for damage caused by improper use or independent interference, especially to functional refrigerant units. Only such persons are entitled to commission the unit who are familiar with the assembly instructions according to use. A prerequisite for this is knowledge of the relevant regulations for the prevention of accidents as well as generally recognised technical safety rules. When handling cleaning agents and disinfectants the manufacturer s safety regulations must be strictly observed. 2

The texts used in this documentation graphically emphasise instructions and notes subject to particular caution.... points out that non-observance may lead to personal injury or damage of the technical equipment.... provides useful information concerning regulatory application or maintenance of the product s service value. 3. Service In your own interest, please observe that any required repair work within the warranty period may exclusively be performed by a servicing facility authorized by DK-Kältenanlagen GmbH. This ensures your warranty rights. Repair and maintenance work on electrical and refrigeration equipment must only be carried out by licensed refrigeration companies. For this, please refer to your refrigeration specialist. 3

4. Fitting and Installation The DK Suction Gas Heat Exchanger is a pressure vessel made completely of copper (CU- DHP). The standard model of this exchanger is supplied with a steam-tight insulation. Upon request of the customer this insulation can be waived. Please observe that the vessel is not exposed to any severe shocks (e.g. rough depositing on a single foot while unloading from the truck)! No late welding or soldering must be performed to the shell of the exchanger! The insulation is made of a closed-pore tight foam insulation against diffusion of vapour made of laminate (e.g. Armaflex or Aeroflex). As a rule, the DK Suction Gas Heat Exchanger is mounted to the machine frame or any other horizontal surface and fastened at the intended points Fastening material is not included in the delivery. 4.1Refrigerant Connection The fluid inlet is marked with a green-red stripe; the outlet is marked with a green stripe The inlet to the suction line is marked in blue. A blue-red marking is attached to the outlet of the suction line (see pic. 1). The suction line and fluid connection is made of metric copper pipe (CU-DHP). Alignment for the suction line connections see pic. 1 to 2. Special designs are not considered. 4

All connecting lines must be sufficiently fastened. In the event of unfavourable operational circumstances of the refrigerant condenser (pulsation impact) appropriate measures must be taken to dampen vibration. Connecting materials such as sleeves or reductions that may be required are not included in the delivery. When leaving the lines unattached for a longer time the vibrations transfer to the connections of the exchanger. This can lead to fissures in the connecting sleeves. Hits of the liquid refrigerant must be avoid in the whole range of capacity. 5

For longer lines which are not attached the vibration translates via the lines to the connections of the exchanger. This can lead to cracks in the connection pieces. When soldering the refrigerant lines to the heat exchanger inlet or exit it must be observed that the insulation is not damaged or burnt. The connections measure 200 mm and should not be shortened by more than 100mm (except for injection lines). Please ensure the sufficient cooling of the connection pieces. When cutting the connection pieces maximum neatness is paramount. Sawdust must not enter the inside of the exchanger. When cutting with a pipe cutter the intersection must be burred. Burr must not enter the inside of the exchanger. 6

5. Commissioning the Unit The refrigeration unit, and therefore also the DK Suction Gas Heat Exchanger, must only be commissioned following the conscientious drying and evacuation. The DK Suction Gas Heat Exchanger is designed for the exclusive use of FC, CFC, H-FC, H-CFC and respective blends as well as for hydrocarbons such as propane, butane, isobutane or ethylene. The DK Suction Gas Heat Exchanger is not suitable for the refrigerant R 717 (NH 3 ). 6. Operation The DK Suction Gas Heat Exchanger is designt for fitting in the liquid and suction gas line of one - or more - refrigeration plant. It only works on this places. The limit values stated on the model plate and in the documentation with regard to pressure and temperature must not be exceeded during operation or standstill of the unit. 7. Maintenance The DK Suction Gas Heat Exchanger has no mobile parts that require maintenance. 7

8. Dimensions suction line IN blue side view front view connections liquid OUT green insulation connections liquid IN green / red distance between mounting suction line OUT blue / red top view op view of the base of Suction Gas Heat Exchanger t e top view of the base of -Suction Gas Heat Exchangertype

9. Technical data DK Suction Gas Heat Exchanger (1,0 m) Copper lacked pipe with fi nned tubes housed in copper piping, single-walled, complete with mounting supports, insulation and cold clamps Type 42/ 3x13 54/ 5x13 64/ 7x13 76/ 9x13 89/ 12x13 108/ 20x13 133/ 30x13 159/ 40x13 219/ 64x13 External pipe (mm) 42 54 64 76 89 108 133 159 219 Internal tubes 3x13 5x13 7x13 9x13 12x13 20x13 30x13 40x13 64x13 Length of internal tubes (mm) 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 1.000 Distance mounting (mm) 500 500 500 500 500 500 500 500 500 Total length (mm) 1.500 1.500 1.500 1.500 1.500 1.550 1.550 1.550 1.600 Total height (mm) 360 370 380 400 420 450 480 500 560 Suction line (mm) 28 35 42 54 64 76 89 108 133 Liquid line (mm) 16 18 22 22 28 35 42 54 64 Surface LP side (m²) 0,48 0,8 1,12 1,44 1,92 3,2 4,8 6,4 10,24 Weight (kg/m) 5 9 13 17 22 33 41 52 87 Weight (kg per 0,1 m) 0,5 0,5 1 1 2 3 4 5 6 Capacity of heat exchanger (W) 1) 1.550 2.590 3.620 4.665 6.220 10.360 15.550 20.700 33.100 Content of outer pipe area (LP side) in dm 3 0,8 1,3 1,9 2,8 4,0 5,5 8,3 12,4 26,1 Content of tube area (HP side) in dm 3 0,26 0,35 0,5 0,6 0,8 1,3 2,0 2,8 4,8 Max. operating pressure: outer pipe area (OA) 16 bars - tube area (TA) 30 bars 1) capacity quoted for R404A installation conditions: Normal cooling refrigeration units: Subcooling of liquid from +40 C to +30 C - overheating of suction gas from ±0 C to +20 C Deep freezing refrigeration units: Subcooling of liquid from +40 C to +35 C - overheating of suction gas from -25 C to -15 C 9