Lobby Lighting Design

Similar documents
Exterior Façade Lighting Design

Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile

Lobby Lighting Redesign

Café DUSON- Overview

Duke Tower Main Entrance Lobby Overview

Overview. The Reading Room

The Bahen Centre for Information Technology. Meeting Room Lighting Redesign. Introduction. University of Toronto ~ Toronto, Ontario, Canada

Lighting Existing Conditions and Design Criteria Report

1.0 Introduction to Lighting Depth. 1.1 Hotel Tower Facace and Porte Cochere

Lord Stirling Community School

Lighting Existing Conditions and Design Criteria Report Brian Regan Ltg./Elect. Virginia Historical Society 10/8/03

Jennifer Mers. Rio Hondo Library and Learning Resource Center. Executive Summary. General Building. Lighting/Electrical Option

Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY

Lindsey Beane. Executive Summary

LIGHTING EXISTING CONDITIONS SUMMARY EXECUTIVE SUMMARY Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA

2.0 Lighting Depth Introduction

The Children s storytelling area

Technical Assignment I

Gathering Space. Function and Orientation. Space Characteristics Gregory Wolfe 2004 Senior Thesis Lighting / Electrical

Lighting Existing Conditions and Design Criteria Report

Cosmetology Lab Redesign

LIGHTING NORTH FAÇADE AND PLAZA

Advanced Lighting For Office

Technical Report #1 Existing Lighting Conditions and Design Criteria

Technical Report One

South Nassau Communities Hospital North Addition

University of California Santa Barbara. Student Resource Building

Thesis Proposal. Brian Regan The Virginia Historical Society Building West Wing Addition RICHMOND, VIRGINIA

Eric Anderson. Technical Report 1. Existing Lighting Conditions

Advances in Non-Residential Lighting Technologies

TABLE OF CONTENTS 3 5.PART 1: EXISTING SPACE AND LIGHTING CONDITIONS 6 8.PART 2: LIGHTING DESIGN CRITERIA

1.1.0 Exterior Facade

University Park, PA. The Pennsylvania State University Architectural Engineering Lighting and Electrical Faculty Advisor: Dr.

Hawthorn Building. Penn State Altoona Campus Altoona, PA. Walter Nichols. Lighting/Electrical Option Faculty Advisor: Dr.

COMMERCIAL LIGHTING DESIGN GUIDE

Executive Summary. CNBC Global Headquarters Christine Cajilig

Schematic Design Ideas for the Westlake Recreation Center. Presented by: Summer Padgett At Lutron Electronics On December 9, 2003

INDEPENDENCE VISITOR CENTER PHILADELPHIA, PA

Lighting Depth Part 1: Exterior Space

Multipurpose Room. Existing Conditions General Overview. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC

Lighting Depth Study. Exterior Departure/Canopy Area

Table of Contents. Parts 1 & 2 Descriptions and Design Considerations Part 3 Evaluation and Critique of Existing Lighting Systems...

Marie Ostrowski Lighting/Electrical Dr. Mistrick Science Building Phase 1 Buffalo State College Buffalo, NY Monday, October 5, 2009 Technical Report

Table of Contents. Heather Lion Redifer Commons University Park, PA. General Lamp and Ballast Information 1-2

Lighting Design Criteria: Codes and Standards

Abbey Beresik. Executive Summary. Ronald Reagan Presidential Library Simi Valley, California

Dorrance H. Hamilton Building

Technical Report 1 Part 2

REVISIONS Summary of Change. 6/1/12 All Replaced entire document with new revision

Spertus Institute of Jewish Studies

Related Sections: TBD. Effective Date: January 1, 2016

The New York University Concourse Project. New York City. Existing Conditions and Design Criteria

HOSPITALITY LIGHTING DESIGN GUIDE

Lighting Depth CAL IT 2. Brian Smith. Introduction

Lighting Existing Conditions and Design Criteria Report

Duke University Medical School. Duke School of Nursing

New LED Product Offerings

Franklin Square Hospital Center

Thesis Proposal Update #2

THE AUGUST WILSON CENTER FOR AFRICAN AMERICAN CULTURE PITTSBURGH, PENNSYLVANIA. PERKINS + WILL chematic Design Presentation MICHAEL P.

Shepherd University Wellness Center AE 481 Thesis Lighting Technical Report 1

Lighting Design Thought Process

Technical Assignment 1 Existing Lighting Conditions and Design Criteria

Schematic Design Proposal Presentation

Technical Report I. jack risser lighting/electrical. s. good the nerman museum. overland park, kansas sept 16 th, 2013.

Steve Neimeister 8 October 2003 AE 481W AstroPower Headquarters Newark, Delaware Lighting/Electrical Option Consultant: M. Moeck

B. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.

Lighting depth. Mark W. Miller Sibley memorial Hospital Grand Oaks Washington, DC. Introduction

L ig h t in g Dept h 8

1.2.0 Apartment Lobby

Mezzanine Youth Area:

RESIDENTIAL LIGHTING DESIGN GUIDE

3. Desk lamps are generally 12 to 20 high and are used to light a specific work area.

실내디자인스튜디오 Reflected ceiling plan

Non-Cutoff and Semi-Cutoff Wall Pack Primary Use and Edits to Outdoor Wall-Mounted Luminaire Primary Use

General Building Overview

PRESCRIPTIVE APPROACH

Inspiration. Wall Street. Innovative Dynamic. Original. Established. Powerful Enlightened. Competitive. Modern. Intrigue

Gregory A. Wolfe Lighting / Electrical

TECHNICAL ASSIGNMENT #3: SCHEMATIC LIGHTING DESIGN

University of California, San Diego Cal IT 2 Brian Smith. Schematic Design Presentation 06 December 2005

Lighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ

Richmond Building Energy Challenge. Project List - Lighting Technologies

Center for Health Research and Rural Advocacy

Lighting. Showroom Lighting Requirements. Introduction. Technology. Fixture and Performance

Main Lobby Area (North Vestibule thru South Vestibule):

Lighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1

THE COMPLETE GUIDE TO OUTDOOR WALL LIGHTS

HARRY RANSOM HUMANITIES RESEARCH CENTER

SUPERMARKET LIGHTING DESIGN GUIDE

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD

Corbin Building. Technical Assignment 1. Matthew Trethaway Lighting/ Electrical AE 481W September 22, 2011 Advisor: Dr. Houser

Lindsay Frederick. Lighting + Electrical. Dr. Houser Faculty Advisor. Native American Cultural Center Arizona. Technical Report I

Woolly Mammoth Theatre. Washington DC

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

LIGHTING WITHOUT LIMITS. Manufacturers of LED and Fluorescent Luminaires

Are LED s ready for Prime Time?

SMEAL COLLEGE OF BUSINESS BUILDING University Park, PA

Transcription:

Lobby Lighting Design The main lobby in Duques is hall is located on the first and second floor of the building. It is the main pathway in and out of the building for the more important spaces, such as the auditorium and capital market classroom, which are found on the first floor. Two primary entrances are found in the space, the main entrance to the building and the side entrance, which is found in the supporting stair well. The first floor of the lobby doubles as a multi purpose area. Chairs and lounge tables have been set up to allow students a place to congregate between classes, and the space is also suitable for a larger meeting place for any banquet type function. The second floor is not designed in the same fashion. It has openings to the floor below it, while the main part of the room is the pathways running between the spaces. Picture L.1 Design for the lobby is very important, as it will be the first place that influences a visitors impression of the building. It is important to provide light on the task plane for motion and other simple visual tasks, but it is also important to add light to the vertical plane to enhance that atmosphere of the space. The openings between the first and second floor allow for unique lighting opportunities, and the lobby itself gives the opportunity to provide visual emphasis on any type of display for the space. Study rooms were placed at six locations in the lobby. These rooms function as their own spaces, but are different from the classrooms that are serviced from the lobby. The study rooms only hold a small group of people, and provide a contained environment in which to meet and discuss away from the distractions of an open environment. Normally, these rooms would be considered separately from the space, but I included them in the design of my lobby. One wall of the room is completely clad in glass and faces the lobby so people can see inside out and outside in. Calculation information such as fc levels and power density was considered separately but included in this analysis. As in the capital market classroom and the auditorium, finishes become an important part of the space. In the lobby, where it is as important to highlight the vertical planes, properly highlighting the finishes will also bring out the most from the architecture. Picture L.2

Design Considerations The biggest consideration for this space was taking advantage of the two floors, and using the other architectural principles of the building in the lighting design. Placing light around the perimeter of the space was a large consideration. By lighting the walls and the ceiling, it is not only possible to create a degree of psychological comfort, but to also cause the eye to perceive the space as being larger than it truly is. Lighting levels also became a very important aspect to consider in the design of the lobby. Large levels of light are not commonly used in areas designed primarily for motion tasks. However, the main floor of the lobby is designed to be a meeting place as well as a passage way, which affected the design of the space. The primary goal for the space was to create a visually important environment. Upon entering the space, the viewers attention should not only be drawn through the space, but to the different parts of the lobby in which someone would want to travel to. Carefully highlighting the entrances to the varying parts of the room was very important in the design of this space. Design Criteria All design criteria is based upon the standards set forth in the IESNA Lighting Handbook, and the following criteria was taken from it. Path finding was the biggest concern in the space. The lobby is first, before any thing else, the first place anyone must visit before passing to any other part of the building. Everyone who must travel into and around the building must pass into the lobby, and should be able to easily find their way to their destination Providing adequate lighting levels was another very important consideration. Lighting the task plane, the floor in this case, is vital to the needs of the person traveling from space to space with in the building. However, placing light on the vertical planes through the room is just as important. With high levels of traffic passing through the space, it is not only important to place light on the vertical plane of where someone is going, but on the face of people that they will meet with in the space. Lighting the entrance to the lobby is very essential in the design of the space as well. The main entrance to the building should be very welcoming and inviting to anyone approaching the building. As most people will be entering through this primary entrance, enhancing the space with accent lighting will give the opportunity to display artwork or anything the owner should desire. Once again the type of light present within the space will help to influence the atmosphere of the lobby and of the building. Lamps that will clash with the finishes of the building or fail to light the areas of architectural interest will only hinder the design of the space.

Design Standards Horizontal Illumination Main Lobby min 30 fc Second floor 10fc to 20 fc Hallways 10 fc Vertical Illumination Vertical surfaces first floor 30 fc or greater Vertical surfaces second floor 20 fc or greater ** Fc values vary throughout the space based on the areas that are to be highlighted. Vertical surfaces were designed to be greater than many of the horizontal levels to help highlight the areas of the room that are more important. Power Density requirements 1.3 w/ft2 (Ashrae Standard 90.1 standards)

Fixture Schedule Fixture cut sheets can be found in ( appendix L ), and the lamp and ballast data that was used with each of the fixtures can be found directly after it. Label A7 A8 A9 A10 A11 A12 B2 B3 B4 B5 B6 B7 D1 Description Narrow assymetric wall light, open reflector and dry wal mounting Continuous run, recessed perimeter light, open aperature wall wash Cove light, continuous run option, painted white housing 4' long continuous run up light, lensed portion for optional downlight Pendant fixture with square shape, up and down light, louvered down light Square shaped pendant fixture, direct indirect with louvered down light 8.5" circular recessed downlight, horizontal mounted lamp Narrow 7x12 inch square recessed wall washer, lensed in silver finish Square wall decorative wall sconce, ADA compliant fixture 4x9 recessed downlight with open aperature, specular white finish 4" small recessed circular downlight, open aperature 4x4" square recessed downlight, lensed with comfort clear finish Pendant hung decorative downlight, white housing open apperature Lamps Manufacturer Voltage Wattage Ballast (1) T5 - T5-A Focal Point 277 28W Electronic (1) T8 - T8-B Focal Point 277 32 Electronic (1) T5 - T5-A Lightolier 277 28W Electronic (1) T8 - T8-B Mark Lighting 277 35W Electronic (2) T8 - T8-B Axis 277 64W Electronic (1) T5- T5ho-A Alight 277 49W Electronic (1) Triple tube - TTB (1) Triple tube - TT-C (1) Triple tube - TT-A (1) Triple tube - TT-A (1) Triple tube - TT-D (1) triple tube - TT-B Erco 277 32W Electronic Eliptipar 277 45W Electronic Visa 277 26W Electronic Lightolier 277 26W Electronic Portfolio 277 18W Electronic Lightolier 277 35 W Electronic (1) Metal Halide Erco 277 70 W -

Lamp Data Label Type CRI CCT W Initial Mean Lumen Lumen Manufactuer T8-B T8 80 3500 32 2950 2800 Philips T5-A T5 80 3500 21 2100 1974 GE TT-A TT 80 3500 26 1800 - Philips TT-B TT 80 3500 35 2400 - Philips TT-C TT 80 3500 45 3200 - Philips TT-D TT 80 3500 18 1200 1130 Philips T5ho-A T5Ho 80 3500 49 4900 4606 GE MH-1 MH 80 4200 70 5700 4560 Philips Ballast Data Label W Lamp Dimming BF Manuf BL-5 32 t8 no 1 Advanced BL-6 21 T5 no 1 Advanced Btt-4 18 TT no 1 Advanced Btt-5 26 TT no 1 Advanced Btt-6 35 TT no 0.98 Advanced Btt-7 45 TT no 0.98 Advanced BL-1b 54 t5ho no 1 Advanced Light Loss Factor The assumed room cleaning period for this room was 12 months and the room was kept under the clean category. The calculated percent of expected dirt depreciation was 12%. Data for this section was assumed to be lower than actual standards would be. By assuming standards to be low, it provides the design in the space will be over sufficient as opposed to under sufficient. RC = ( 2.5 * 11 * 383.5 ) / 4455.8 = 2.4 RC is assumed same for the second floor, same overall area and height.

Label Maintenance Category LLD RSDD LDD BF LLF A3 V 0.80 0.95 0.88 1.00 0.67 A4 IV 0.80 0.98 0.39 1.00 0.70 A5 II 0.80 0.94 0.80 1.00 0.71 A5a II 0.80 0.94 0.80 1.00 0.71 A6 VI 0.80 0.80 0.95 1.00 0.61 A6a VI 0.80 0.80 0.95 1.00 0.61 B2 IV 0.80 0.98 0.89 1.00 0.70 ** LLD was determined at standard.8 value for fluorescents. ** All ballast factors were calculated at 1.0, as all other values were under estimated Power Density First Floor Second floor Label Wattage Quantity Power Power Label Wattage Quantity Density Density A7 28 0 0 A7 28 4 112 A8 32 8 256 A8 32 20 640 A9 28 0 0 A9 28 55 1540 A10 35 10 350 A10 35 0 0 A11 64 8 512 A11 64 16 1024 A12 49 8 392 A12 49 8 392 B2 32 16 512 B2 32 8 256 B3 45 3 135 B3 45 0 0 B4 26 2 52 B4 26 2 52 B5 26 3 78 B5 26 3 78 B6 18 0 0 B6 18 6 108 B7 35 10 350 B7 35 10 350 D1 70 4 280 D1 70 4 280 Total = 2917 Total = 4832 W/ft2 = 0.655 W/ft2 = 1.798 Following the ASHRAE 90.1 standards, the first floor would meet the requirements but the second floor would not do to the amount of indirect lighting that is present within the space. To accommodate for this, the first and second floor were considered together as one space, so the savings for the first floor would balance out the loses for the second floor. ( 2917 + 4832 ) / (4455 + 2688 ) = 1.1 W/ft 2 Controls The controls for the Lobby are much easier then the controls for the auditorium and for the capital market classroom. As interesting as the space is, the building is a simple education facility and there is no need for multiple settings within the space.

Controlling the lights is as simple as wiring a switch into the circuit, as no Grafik Eye type system will be needed in this setting. One situation arises with the installation of a switch. Placing a switch on the wall would be easy enough, but in a space with as many people passing through, the switch will most likely be tampered with. A few options arise, such as placing a switch in the open, but having it only become accessible with a key. A simple enough solution; however, that particular solution was avoided in this case. Placing a switch on the wall becomes the equivalent of placing a foreign object within the space. To avoid this, the lights were placed on the building time clock, allowing for automatic on and off according to the times that the building will typically be used. An override switch will be contained in one of the electrical rooms. Floor Plan Figure L.1 Figure L.2

Luminaire Plans The following figures contain the luminaire layout for the lobby. Each luminaire is labeled in the similar manner X1 PXX X X The first number represents the fixture s representation in the luminaire plan. The second number is the panel on which the circuit can be found, the third number is the branch circuit on the panel, and finally, the final number is in correspondence to the dimming zone of the room when dimming is applicable.

Ceiling Plan 1.A The area shown in this portion of the luminaire plan is the entrance to the lobby and the open stairwell directly in front of that entrance. Figure L.3

Ceiling Plan 1.B Figure L.4 Figure L.4 is a representation of the middle portion of the first floor. Contained in this space are two of the four openings to the floor above, as well as one of the study rooms, which can be found on the lower portion of the page. The areas that are set back are the entrances to the classrooms.

Ceiling Plan 1.C Figure L.5 Figure L.5 is the last luminaire plan for the first floor. It contains the back hallways, which leads to the secondary stairwell in the building. Also in this plan is the second study room on the first floor. Next to the study rooms are the entrances to the different classroom, and the second set of openings to the second floor.

Ceiling Plan 2.A Figure L.6 Figure L.6 displays the first area of the second floor. The steps leading up onto the initial landing and the surrounding area, and the areas on either side for walk up computer stations. Luminaire A8 is a cove fixture, which is set in a cove that is 1.5 tall and 1.5 deep.

Ceiling Plan 2.B Figure L.7 Figure L.7 is a display of the middle portion of the second floor of the lobby. Again, fixture A8 is a cove light that is set in a cove 1.5 deep and 1.5 tall. The area between the two sets of cove lights is a suspended pathway between the entrances to two of the classrooms.

Ceiling Plan 2.C Figure L.8 Figure L.8 is the final portion of the second floor lobby. It contains another set of cove lights that have been placed in a cove of the same dimensions. The two rooms set off of the main part of the lobby are two study rooms.

Calculation Data The task plane on the first floor, the floor itself, succeeded in reaching the desired fc levels. With the goal of a minimum of 30 fc in this space to provide sufficient lighting for reading tasks that will last only a short amount of time. Levels on the second floor also reach their desired values, washing the floor at values above 10 fc. The results can be seen in this following section, which provides pseudo color renderings of the first floor and the second floor. Figure L.1 Figure L.2

Spatial Highlights Another primary concern for the space was the lighting of the more important aspects of the room more prominently, in this case the entrances to the rooms and the main entrance to the building. Using recessed fixtures to bring out the deep rich wooden color of the finish around the classroom entrances, and by highlighting works of art by the building entrance, attention was drawn to these aspects of the room allowing them to stand out more prominently then the rest of the room. A display at the entrance of the building highlights several works of art in an attempt to draw interest into the space. Rendering L.1 Recessed perimeter lights help to place light on the rich wooden façade that clads the walls around the doorways to draw people into the classrooms. Rendering L.2

Spatial Renderings View of the first floor of the Lobby Rendering L.3 Rendering of one of meeting rooms. Rendering L.4 Rendered view of the second floor Lobby area. Rendering L.5 Rendered view of the coved portions of the ceiling. Rendering L.6