PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

Similar documents
Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Smoke Transport and FDS Validation

Smoke Layer Height and Heat Flow through a Door

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

CFD Model of a Specific Fire Scenario

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

A Comparison of Aspirated Smoke Detectors

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Advantages and Disadvantages of Fire Modelling

Smoke Layer Height and Heat Flow through a Door

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Fire Scenario Influence of Material of Boundary Condition on Results

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Recent BRANZFIRE enhancements and validation

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Validation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Preliminary investigations of smoke movement through HVAC systems and duct smoke detectors. Lougheed, G.D.; McCartney, C.; Carpenter, D.W.

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

Validation of a Smoke Detection Performance Prediction Methodology. Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology

Case Study 2 (Production and Storage Buildings) - Spain

The Prediction of Smoke Detector. Activation Times in a Two-Storey House. Fire through CFD Modelling

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

Sprinklers Modeling for Tunnel Road Fire Fighting

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Modeling a real backdraft incident fire

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

First Revision No. 6-NFPA [ Section No. 2.2 ]

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

ABSTRACT. Stephen Kerber, Master of Science, Dr. James Milke, Fire Protection Engineering

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Validation of a Smoke Detection Performance Prediction Methodology. Volume 2. Large-scale room fire tests

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES

Chapter 17, Initiating Devices

Overview of the PRISME project Technical Description and Main Outcomes

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Computer Models For Fire and Smoke

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

An experimental study of the impact of tunnel suppression on tunnel ventilation

Test One: The Uncontrolled Compartment Fire

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Refining and Petrochemical Heater trouble shooting

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

Compression of Fins pipe and simple Heat pipe Using CFD

Potential Impact of New UL Fire Test Criteria

Fire Research and Education at the University of Maryland

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Measurements of Smoke Characteristics

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

Tunnel Fire Dynamics and Evacuation Simulations

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Considerations in the Design of Smoke Management Systems for Atriums

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

Travelling Fires for CFD

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

Fire Protection as the Underpinning of Good Process Safety Programs

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

article continues below

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

CFD Simulation of the Water Mist Effect on Fire

KEYWORDS: Smart fire detection, fire signatures, nuisance sources, non-fire signatures

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Smoke Alarm Research at NIST

UL268 7 th challenge with single infrared smoke detector

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Air Flow Study inside the Supermarket Refrigeration System

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

VIRTUAL FIRES via COMPUTERS

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

2012 International Symposium on Safety Science and Technology Investigation on compressed air foams fire-extinguishing model for oil pan fire

A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects

APPLYING LARGE EDDY SIMULATION IN THE STUDY OF FIRE AND SMOKE SPREAD AT UNDERGROUND CAR PARK

MINISTERIO DE FOMENTO

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

7.1 Smoke Detector Performance

Results from a Full-Scale Smoke Alarm Sensitivity Study

Case Study 1 Underground Car Park

Reference to the Smoke Damage Index (SDI) is needed as it is part of the test method.

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010

Transcription:

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR VIJAY T. D SOUZA, JASON A. SUTULA, STEPHEN M. OLENICK*, WEI ZHANG and RICHARD J. ROBY Combustion Science & Engineering, Inc. Columbia, MD 21045 Corresponding Author: solenick@csefire.com ABSTRACT This is a study into the ability of the Fire Dynamics Simulator - Version 1.0 (FDS 1.0) to predict smoke detector activation. FDS is a field computer model that has shown promise in the modeling of fire phenomena. Two methods were used to create a first order approximation of the ability of FDS to predict smoke detector activation. First, the fluid transport model of smoke within FDS was tested and compared with full scale UL217 test data. Second, a series of full-scale multicompartment fire tests were conducted to provide a data set to further validate the results obtained from FDS. It was determined that FDS can predict smoke detector activation when used in conjunction with smoke detector lag correlations that correct for the time delay associated with smoke having to penetrate the detector housing. INTRODUCTION The fundamental equations that govern fluid dynamics, heat transfer, and combustion have been defined and improved upon for decades. However, the daunting task of adequately modeling fire growth and behavior has been hampered by the sheer mathematical complexity of the equations involved, the number of variables that need to be taken into account, and maybe most importantly the processing capabilities of computers. The technological revolution has provided engineers with desktop personal computers that, for the first time, may provide economically convenient methods of numerically modeling fire phenomena. Recently, the emergence of computational fluid dynamics (CFD) fire modeling codes based on the RANS (Reynolds Averaged Navier-Stokes equations) has shown promising results when modeling fire induced flow. Exponential growth in computational clock speed has allowed the engineer with a desktop personal computer to define grids with hundreds of thousands of cells that bring approximation of fire phenomena to higher levels of accuracy. Another emerging technology, and the most promising for capturing large-scale transient flow, is the development of the Large Eddy Simulation (LES) technique for fire modeling. The Fire Dynamics Simulator (FDS version 1.0) is the most widely used LES FIRE SAFETY SCIENCE--PROCEEDINGS OF THE SEVENTH INTERNATIONAL SYMPOSIUM, pp. 187-195 187 Copyright International Association for Fire Safety Science

model in the fire science field [1]. LES modeling assumes that turbulent motion can be separated into large eddies and small eddies. The large eddies (grid-scale) motion is directly simulated and the small eddies (sub-grid scale) motion is modeled. [2] FDS has demonstrated good agreement with experimental data in numerous validation studies. The scope of this effort was to determine the ability of FDS to predict smoke detector activation. A two-step approach was used to determine a first order approximation of the smoke detection predictive capabilities of FDS. First, the smoke transport fluid model within FDS was tested against the repeatable smoke transport criteria that Underwriters Laboratories (UL) 217 (1985) dictates for non-fire retardant polystyrene foam. Second, FDS was used to model a series of full-scale multi-compartment fire tests that were instrumented with ionization smoke detectors, thermocouples, light extinction measurements, and other equipment. UL 217 TEST To determine if FDS had the ability to accurately model the fluid transport of the products of combustion, UL 217 was used as a test criterion. The 1985 edition of UL 217 (Single and Multiple Station Smoke Detectors) provides a rigid test setup that consists of a room with multiple locations for photocell assemblies and smoke detectors [3] (Figure 1). For the purpose of this phase of the study, the propagation of the smoke was of the most concern. UL 217 test D (Polystyrene Fire) was chosen as the test fire to be considered in this study. To determine the input parameters within the FDS model, oxygen consumption calorimetry was used to find the exact heat release profile of the polystyrene test sample used in the UL 217 test D. This profile was determined by burning a prescribed sample of foam polystyrene type packing material with a density between 24-32 kg/m 3 and no flame inhibitor, under a collection hood with oxygen sampling. It is known that approximately 13.1 kj of heat is released per gram of oxygen consumed. By monitoring the reduction of oxygen present in the hood exhaust, a measure of the heat release profile for the foam was determined for the duration of the test.. Q foam. oxy = m H (1) c( oxy) The heat release profile was then mapped into FDS by using the RAMP function, which allows the user to define the percentage of the peak heat release at various time intervals, thus producing a heat release rate curve. The smoke production properties of non-flame retardant polystyrene foam were taken from existing literature [4]. 188

Figure 1: UL217 Test Setup (Taken from UL 217 1985) [3] Fire A method of using FDS to accurately model smoke generation for small grid cells within the computational mesh was used. This technique involved defining a species, labeled smoke, with an initial mass fraction equal to zero and a molecular weight that was specified the same as air (29 g/mol). In the definition of the fire SURFACE line within the code, a species YIELD was defined that had the same properties found from the literature [4] for the percentage of smoke produced from a polystyrene foam fuel source. In essence, this method treats smoke as one of the gases generated from the surface of the fire and allows for a better approximation of the smoke concentration within a given cell in the computational domain. On the contrary, the function that is built into FDS for tracking smoke movement (SMOKE_YIELD) assigns a fraction of smoke to each thermal particle that is released from the combustion zone. The presence of a thermal element within a cell determines how much smoke is present. For small cell sizes, there is a greater chance of there not being at least one of these elements present at a given time, which would lead FDS to assume that there is no smoke present at that moment. This creates very erratic results, which are uncharacteristic with real smoke movement. For a detector activation analysis an average smoke presence is desired, therefore tracking the smoke production as a species yield proves to be more accurate. This application of FDS is a technique that this study sought to validate. UL 217 prescribes a rigid test scenario in which smoke must reach each of the sampling locations within the test room during a certain window of elapsed time. Furthermore, the test standard dictates the level of smoke obscuration at different times within the test at each location. The prescribed fire for the test is designed to provide this smoke profile. This kind of repeatable, well-documented test provided a solid set of data to compare 189

with the FDS model results. The following are the results of the FDS data compared to UL 217 stipulations: Table 1: Comparison of FDS Predictions vs. UL 217 Requirements. UL Smoke Profiles Smoke buildup shall occur: UL requires (s) FDS (s) Ceiling Detector 35-45 40 Sidewall Detector 25-35 34 33% obscuration per meter smoke shall occur: UL requires (s) FDS (s) Ceiling Detector 70-90 74-97 Sidewall Detector 60-80 66-78 33 43% obscuration per meter smoke shall remain: UL requires (s) FDS Ceiling Detector 90-120 (end) yes 33-56% obscuration per meter smoke shall remain: UL requires (s) FDS Sidewall Detector 80-120 (end) yes The FDS data demonstrates excellent agreement with the smoke profile requirements of UL 217. The range of times produced by FDS is directly correlated to the specific extinction coefficient (K m ) of the smoke produced. The specific extinction coefficient is a function of the size distribution and optical properties of smoke [5]. For smoke produced during flaming combustion of wood and plastics, the value of K m has been found to equal approximately 7.6 m 2 /g [6]. For the smoldering production of smoke from these materials, K m has been found to equal approximately 4.4 m 2 /g [6]. The burning of polystyrene foam in the configuration prescribed by UL 217 is a combustion process that involves both flaming and pyrolysis of the fuel. Because of this dual combustion process, the exact K m value for the smoke produced is really a function of time during the burning process. Figure 2 is a graph of the range of values produced by FDS for the sidewall detector in the modeled UL 217 test. Bouguer s law was used in conjunction with data obtained by FDS and the K m values to determine the percent optical density per meter at each location. It is postulated that because the UL time requirements fall within the range of times produced by FDS using the K m range mentioned above, this is an excellent validation of the fluid smoke transport model within FDS. 190

Figure 2: Graph of FDS Output for UL217 Test Sidewall Detector Sidewall Detector 60 55 50 Percent Obscuration per meter 45 40 35 30 25 20 15 High Km = 7.6 m2/g Low Km =4.4 m2/g 10 5 0 0.0 20.0 40.0 60.0 80.0 100.0 120.0 Time (s) FULL SCALE TEST The second phase of the validation study was to test the ability of FDS to predict smoke detector activation in a full scale, multi-compartment test setup. To accomplish this, three full-scale tests consisting of hydrocarbon pool (75% heptane / 25% toluene) fires were conducted. The test geometry consisted of two 2.4 m 2.4 m 2.4 m compartments connected by a 4.9 m corridor with 2.4 m high ceiling. The doors to both rooms were open during the tests, but the entire test geometry (both rooms and the corridor) was sealed, except for a small amount of construction leakage. Every attempt was made to seal construction gaps and minimize this leakage to the outside. The test fires were located near the back wall of room 1 (see Figure 3). For each test, a 15.25 cm diameter pan was filled with 75% heptane / 25% toluene by volume. The test pans were placed on scales that measured mass loss data in the event that a better heat release profile was needed for input into FDS. Coupling the known net heat of combustion for the two fuels with the mass loss data would provide this data. The test fires were ignited using a standard butane lighter. For each test, a series of ionization smoke detectors were placed on the wall 6 cm down from the ceiling in room 1 and the corridors, and on the ceiling of rooms 1, 2, and the corridor (see Figure 3 for detector placement). At each location where the smoke detectors were placed, a laser-photo diode pair was installed to measure the optical smoke density. A data acquisition system was used for recording data at a rate of one measurement per second. Temperature, optical density, smoke detector voltage output, and mass loss data were gathered by a Kiethley DAS-800 board with four EXP-800 191

expansion boards. Two cameras were also included in the test setup; one recorded the smoke layer at the ceiling of room 1 and the other recorded the smoke layer at the ceiling of room 2. Figure 3: Multi-Compartment Test Setup Smoke Detector CORRIDOR D #3 D #4 Smoke Detector D #1 D #2 D #5 ROOM 1 ROOM 2 Fire Location The input into FDS to model these tests consisted of the heptane/toluene effective heat release rate, heat of combustion, and smoke yield. This data is readily available in the literature for both of these fuels [4] (Table 1). The optical density and smoke velocity were sampled at each detector location within the FDS model, and were used in determining the predicted time to activation. Utilizing the previous outlined procedure for modeling smoke production, a two-step approach that coupled the model outputs of smoke velocity and optical density was used to determine detector activation. Table 1: Soot Yields and Heats of Combustion of Experimental Fuels [4]. Fuel Soot Yield (g/g) Hc (MJ/kg) n-heptane 0.037 48.07 Toluene 0.178 42.43 The first step was to determine when FDS predicted the optical smoke density to be at a threshold that was deemed critical for detector activation. From the UL 217 fire tests, this 192

range can be from approximately 23-56 percent obscuration per meter (% Obs/m). Because these tests involved a flaming fire (with no smolder), a K m value of 7.6 m 2 /g was used in the analysis. This procedure was repeated for each detector within the model to determine the time required for the necessary concentration of smoke to travel to each location. When this criterion was fulfilled, a smoke detector delay time associated with the time it takes for smoke to navigate and enter into the sensing chamber within the detector housing was factored into the calculation. This delay time is directly correlated to the velocity of the smoke when it reaches the smoke detector. Several studies have tried to quantify this detector lag time. Three different correlations for detector lag time (Brozovsky et. al [7] (2) & Cleary et. al [8] (3 + 4)) were compared in the analysis for two different critical optical densities (23% Obs/m, and 56% Obs/m). These correlations were chosen because they provide an analysis that is independent of a characteristic length scale that typically attempts to assess the physical construction of a particular detector. The Brozovsky et. al correlation is listed below: 3 2 t = exp( 1527U + 918.1U 187.7U + 14.84) (2) Where: t = Detector delay time U = Smoke velocity at detector location For the two correlations extracted from a study conducted by Cleary et. al, a twoparameter model was used to describe the lag time of the detectors. Two correlations were presented for two different, unidentified, ionization smoke detectors. The first parameter is the dwell time, which is the time for the smoke to reach the sensing chamber. The second parameter is the mixing time in the sensing chamber. These two times are assumed to act in series (i.e. one after the other). Therefore the lag time of a detector is the sum of these two parameters. The two sets of correlations that were used for ionization type smoke detectors are listed below: Ionization Detector Correlation #1 (3) Dwell time = 2.5 U -0.71 Mixing time = 0.76 U -0.87 Ionization Detector Correlation #2 (4) Dwell time = 1.8 U -1.10 Mixing time = 0.98 U -0.77 The final predicted detector activation time is equal to the transport time associated with the flow of smoke, at the specified concentration, to a specific detector in addition to the time delay associated with one of the detector lag correlations. The results are presented in Figure 4. The data suggests that when using a detector lag correlation, FDS can be used to predict detector activation time. 193

Figure 4: FDS Predicted Detector Activation Time vs. Experimental Data 90 Activation time (s) 80 70 60 50 40 Experimental average Actual tests 23% Brozovsky, et. al 23% Cleary et. al I1 23% Cleary et. al I2 56% Brozovsky et. al 56% Cleary et. al I1 56% Cleary et. al I2 30 20 10 0 0 1 2 3 4 5 6 Detector ID CONCLUSION The UL 217 validation test confirmed that the fluid transport model within FDS operates very effectively given a well defined input fire. The data suggests that the importance of choosing an accurate specific extinction coefficient has a significant effect on the predicted level of smoke obscuration. It is important to note that the specific extinction coefficient is a function of the different stages of combustion, and therefore a more accurate method of modeling fire would be to incorporate an iterative calculation of K m within the model. The FDS model of the full-scale multi-compartment fire tests shows an encouraging agreement with the experimental data. From the existing data, it is apparent that the incorporation of a delay time is significant [7,8]. For detectors located far from the fire source, the optical density requirements necessary for detector activation may be satisfied, but the smoke velocity is so low that the delay time can be significant. FDS was able to predict the detector activation of these distant locations with reasonable accuracy when coupled with the detector lag correlations. FUTURE WORK There is currently an effort to model test data from experiments involving complex geometries and detector locations far from the fire source (i.e. full scale house burns). Test configurations of this nature yield smoke flow velocities at the most distant detectors that are slow enough to make the detector lag correlations more significant in a detector 194

activation analysis. There is also work being done to determine the grid dependency of boundary layer effects near the wall. This additional analysis is important because smoke detectors are typically placed on walls where viscous boundary layer effects could be significant. ACKNOWLEDGEMENTS This research effort would not have been possible without the time Clarence Worrell and Maclain Holton spent in the lab conducting the full-scale tests. Special thanks goes to Jamie Ferrino for conducting the oxygen consumption calorimetry of the polystyrene foam for the UL 217 FDS input. Thank you to one of the developers of FDS, Kevin McGrattan, for his continued support of our efforts to further validate and improve upon the model. REFERENCES [1] K.B. McGrattan, et al. Fire Dynamics Simulator Technical Reference Guide. Technical Report NIST Internal Report (NISTIR 6467), National Institute of Standards and Technology, Gaithersburg, Maryland 20899, 2000. [2] W. Zhang, A. Hamer, M. Klassen, D. Carpenter, R. Roby. Verification of the Turbulence Statistics for Fire Dynamic Simulator in a Room Fire Model. 3 rd Technical Symposium on Computer Applications in Fire Protection Engineering. SFPE. Sept. 12-13 2001. Pp. 65. [3] UL 217, Standard for Single and Multiple Station Smoke Detectors, third edition, 1985, with updates through February 27, 1989, Underwriters Laboratories, Inc., Northbrook, Ill. [4] A. Tewarson. Generation of Heat and Chemical Compounds in Fires. The SFPE Handbook of Fire Protection Engineering, 2ed: 3-99 3-106, 1995. [5] G. Mulholland. Smoke Production and Properties. The SFPE Handbook of Fire Protection Engineering, 2ed: 2-221 2-222, 1995. [6] J.D. Seader and I.N. Einhorn, 16 th International Symposium on Combustion, Pittsburgh (1976). [7] E. Brozovsky, V. Motevalli, and R. P. Custer. A First Approximation Method for Smoke Detector Placement Based on Design Fire Size, Critical Velocity, and Detector Aerosol Entry Lag Time. Fire Technology, 31: 336-354, 1995. [8] T. Cleary, A. Chernovsky, W. Grosshandler, M. Anderson. Particulate Entry in Spot-Type Smoke Detectors. 6 th International Symposium on Fire Safety Science. Pp. 779-790. 195