WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

Similar documents
MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

MANUAL RESET ALARM RELEASE

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Hand Chain (Model FCF) &

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

INSTALLATION & MAINTENANCE CORNELL FIREGARD CHAIN & ES ECO #1515 REVISION # 0000 FIREGARD CRANK OPERATORS BY: RICKM DATE: 3/23/2011

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

RELEASE DEVICE CONTROLS

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

OWNER S MANUAL. Extended Performance Release Device. Models: Firefly III Plus, Firefly III Plus with Voiceboard

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Installation Guide for models:

Installation Guide for models:

Series. Access Power Controllers. Installation Guide

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

INSTALLATIONN GUIDE & OPERATION MANUAL

Model 17A00 Expansion Enclosure

Multiple Input and Output Modules

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FST-EPB Series. Single Motor

Remote Alarm Panels Features

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Conventional Smoke Detectors KFAPO

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Access Power Controllers with Power Supplies

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

RM-1 Series. Remote Microphones. (RM-1, RM-1SA) Document Revision B RM-1 RM-1SA. RM-1 on ADP-4 dress panel. RM-1SA in a CAB-RM or CAB-RMR

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Conventional Releasing Control Panel

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Remote NAC Power Supply D7038

FM-200 In-Cabinet Series

INSTALLATION INSTRUCTIONS TALKBACK MODULE

FMR Installation Instructions. Addressable Fire System Controller

D7053. Installation Instructions Multiplex Input/Output Module

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

DS160/161 Request To Exit PIR sensors Installation Instructions

DS160/DS161 Request To Exit PIR sensors Installation Instructions

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

4100U City and Relay Cards Installation Instructions

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

Crypto-Lock. Model CC-8521B Updated 7/17. Access Control System. MONITEQ, Inc. INSTRUCTION MANUAL

TS93 EMF SERIES. INSPK NO Rev.03/10

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

ANNUNCIATOR FIXED MODULE

FDF Foam Pump Controllers Features

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Duct smoke housing, 2-wire D340/D340P

PSN-1000 & PSN 1000(E) Installation Manual

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

Public Safety DAS Annunciator Panel

* These Remote Mics must be SPRM-GP

Wiring Instructions (01-09)

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

July 14, 1999 DF C-100.

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

Transcription:

WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems. 2. DO NOT install this unit without fuse links. 3. Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with all of the latest National fire Protection Association (NFPA), Underwriters Laboratories (UL), National electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). 4. To be performed by factory authorized personnel only. 5. Clear fire door opening and prohibit all traffic through door opening during testing of system! Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release mechanism before connecting to a fire door. INTRODUCTION The releasing device is a failsafe constantly energized solenoid mechanism. It is designed for use on rolling doors, single-slide and center-parting level and inclined track doors. Inside the mechanism, contact relays receive the alarm signal from the fire alarm control panel. When the unit receives the signal, the power to the solenoid is cut, releasing the fire door mechanism and hence close the fire door. The alarm signal can be Form C dry contact or 24VDC/VAC. Any interruption of power will release the solenoid mechanism. The release has a 10 second delay upon power failure and alarm, closed door detection capabilities, Form C relay outputs for the status of release box and 24VDC power output for door close warning. 1

SPECIFICATION Input Power*: 115VAC, 0.5A; 24VAC, 0.5A; 24VDC, 0.2A Alarm Dry Contact Rating: Lower Limit Microswitch Rating: Door Close Warning Power: Status Dry Contact: Frequency: Release Pull: Fuses: 24VDC, 0.08A, 5.16 ohms max line impedance 30VDC, 0.08A, 5.16 ohms max line impedance 24VDC @Max. 0.23A, Resistive, Special Application (see below) Rating: 30VDC/VAC, 2A, Resistive Load 50Hz or 60Hz 50 lbs (22.7kgs) F1: 2A@250V, Slo-Blo Type F2: 3A@250V, Slo-Blo Type *Input voltage [standby/full load**/start current]: 115VAC [0.5/0.6/1.1A], 24VAC [0.5/0.8/1.8A] or 24VDC [0.2/0.4/1.8A]. **Full load current only required for optional warning device(s). Must install with UL approved fusible links. 24V input power can be 24VDC or 24VAC or 24VDC from an approved UL1481 regulated power supply. 18-gauge wire recommended. For Indoor Dry location use only. Close warning power is provided for less than a minute. Any fire Listed audible or visual device may be used if the 24VDC input is powered by a UL1481 regulated power supply. When input power is 115VAC or 24VAC, please connect the following compatible devices: Bridgeport Fitting Inc Series 840P & 840T and Federal Signal Corp Model LP6 and Series LP3. Note: Door Close Warning Output is only functional when the box has input power. INSTALLATION WARNING Disconnect power supply before servicing. - For Indoor Dry location use only. All wiring must satisfy the most current version of NFPA72 National Fire Alarm Code and the National Electric Code. - 18-gauge wire is recommended 2

INSTRUCTION & DRAWING 1. Actual configuration may differ. Must pull straight cable minimum 18 inches before turning (This unit may be rotated 90 degrees CW for a vertical pull.). See door manufacturer recommendations and NFPA 80 for use of this product with specific door. DO NOT install this unit without fusible links. 2. To be performed by factory authorized personnel only. 3. The release device shall be mounted on a vertical surface with chain end link exiting side of enclosure as illustrated on figure 1. The unit may be rotated 90 degrees CW for a direct vertical pull. Release Device Figure 4. Release device and associated hardware [sash chain or 1/16 cable, eyebolts, fusible links (DO NOT install this unit without fusible links), turnbuckles] shall be installed as per door manufacturers recommendations (figure 1 typical installation configuration). Note should be taken that the end link direction of pull is perpendicular to the enclosure side. An eyebolt installed at a distance of 18 to 24 inches from the release device should adequately redirect sash chain pull as illustrated in figure 1. Please also see figure 2 for illustration. 3

Figure 2 WARNING Disconnect power supply before servicing. 5. ELECTRICAL CONNECTIONS Installation of all wiring and connections shall be performed in accordance with, but not limited to, the latest NFPA, U.L. and N.E.C. standards. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material, wiring gauge related to power capacity requirements and circuit length and wiring methods. 6. Verify voltage rating of release device to power source being utilized. 7. Connect fusible link and fire door system to release box. 8. Connect power and alarm connection to the unit. 9. Remove the Set-Tie cable after power and alarm connection. Set-Tie cable mechanically secures release latch and must be removed to allow proper emergency operation of release device after installation is completed. NOTE: A trouble sounder will be activated if power is present, the latch is engaged, but the Set-Tie has not been removed and/or the lever is in the DIS-ARMED position. 4

WIRING WARNING Disconnect power supply before servicing. WIRE ROUTING + - + - 41 42 31 32 33 35 36 37 38 R3-48 Note: Not supervised. 5

TERMINAL CONNECTIONS WARNING Disconnect power supply before servicing. TB1 L N Input power 115VAC* See Note. 5 TB2 41 (+) 42 (-) 31 32 33 35 (+) 36 (-) 37 38 Input 24VDC/VAC *Note. 5 Alarm Dry Contact (N/C) *Note 1 Door close warning 24VDC, total 0.23A *Note 3 Lower Limit Microswitch (N/C) *Note 2 Status dry contact *Note 4 30VDC/VAC 2A 16AWG 37.9ft Resistive load * Note: 1. Terminal 31&32 Building fire alarm panel needs to provide dry contact (N/C) connection with minimum capacity of 24VDC and 0.08 amp. To have 5.16 ohms max line impedance. 2. Terminal 32&33 Use this connection to notify release device the status of the door. Field installation of microswitch on the door is necessary to use terminal 32&33. When the door is already in its close position, a closed contact (N/C) can cause the release device not to release (5.16 ohms max line impedance). Power failure will still cause the solenoid to let go, hence resetting is necessary. 3. Terminal 35&36 This connection provides 24VDC, 0.23A power with 18AWG wire for maximum of 20 ft., when release device has been released. This can be used to provide power for warning devices. The warning power is provide for less than a minute. The wiring connections are enclosed within conduit or equivalently protected against mechanical injury. 6

4. Terminal 37&38 These terminal connections will provide the status of this release device. When release device is in the standby mode, connection is open (N/O). When release device have been activated or released, connection would be in closed (N/C) state. 5. See connection chart for power inputs. Connection Chart Connection Type Power Input Terminals Line In High Voltage L & N Connect 115VAC Low Voltage 41 & 42 (24VDC or 24VAC) Connect 24VDC or 24VAC (Voltage supplied by FACP or an UL listed power supply) Alarm Connection 31&32 Connect FACP* Alarm Dry Contact (5.16 ohms max line impedance) High Voltage Alarm Signal Connect Alarm Signal 115VAC Do Not Connect Jump (Wire size min 18AWG) Low Voltage Alarm Signal Do Not Connect Connect Alarm Signal 24VDC or 24VAC (Voltage supplied by FACP) Jump (Wire size min 18AWG) *Note: FACP Fire Alarm Control Panel. 7

WIRING DIAGRAM Release box (115V 1ψ or 24VAC/VDC) 8

SCHEMATIC 9

TESTING 1. Simulate an alarm condition and see if the solenoid disengages and releases the fire door. 2. Simulate a power failure and see if the solenoid disengages and releases the fire door. RESETTING 1. Make sure power and alarm connection is normal. 2. Push the release latch all the way back into the slot. 3. Verify the solenoid is holding. 4. Connect fusible links to the fire door system. Note: If the power or the alarm is not normal, solenoid will not hold. Hence the release latch will not stay in the slot. MAINTENANCE INSTRUCTIONS WARNING Disconnect power supply before servicing. Check the following items at the intervals listed: CHECK LIST DESCRIPTION EVERY 3 MONTHS EVERY 6 MONTHS EVERY 12 MONTHS Fasteners Check & tighten as required Drop-test Inspect door, drop-test for proper operation and full closure per NFPA-80 Inspect and service whenever a malfunction either door or release device is observed or suspected. Before servicing, always disconnect power supply to the release device. Replace fuses only with those of the same type and rating. All replacement parts must be obtained from the door manufacturer per NFPA-80. Testing of the release device is independent of, and shall in no way be interpreted as an alternative method of, testing of the fire alarm system, and/or any other system component employed on the fire door or counter fire door installation. TESTING SHALL BE PERFORMED AND WITHNESSED FOR PROPER OPERATION. 10