IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Similar documents
Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

CHAPTER 1 INTRODUCTION

DEEPAK PALIWAL, S.P.S.RAJPUT

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

η second law = Second law efficiency

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

A Comparison Between Refrigerants Used In Air Conditioning

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

JJMIE Jordan Journal of Mechanical and Industrial Engineering

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Design of LPG Refrigeration System

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

International Journal of Advance Engineering and Research Development

Design & Fabrication of Hybrid Cooler

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Experimental Investigation on R 290 and R 600a In a Vapor Compression Refrigeration

Waghmare Tushar Ramrao, D.S.Nakate

II. OBJECTIVE OF RESEARCH

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Study of R161 Refrigerant for Residential Airconditioning

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

ADVANCES in NATURAL and APPLIED SCIENCES

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

CHAPTER 1 INTRODUCTION

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

Department of MCE, Islamic University of Technology 2. Abstract

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Performance Study of Geotropic Blends of Isobutane R600a and Propane R290 in Domestic Refrigerator as Alternative Refrigerants to R134a

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Enhancement of COP using Nanoadditives in Domestic Refrigerator

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

A Review Paper on Comparative Study of Household- Refrigerator with Alternative Low Global Warming Potential Refrigerants

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Performance of an Improved Household Refrigerator/Freezer

Enhancement of COP in Vapour Compression Refrigeration System

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

ADVANCES in NATURAL and APPLIED SCIENCES

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION

Transcription:

Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser at Condenser Inlet Yetti Siva 1, Dr.Smt.G.Prasanthi M.E.,Ph.D. 2 1 PG Scholar, Department of Mechanical Engineering, J.N.T.U.A College of Engineering, Ananthapuramu, A.P, India 2 Professor, Department of Mechanical Engineering, J.N.T.U.A College of Engineering, Ananthapuramu, A.P, India Abstract Most the refrigerants like, R11 and R12, R22 contain chlorine atoms which are responsible for the ozone depletion. These hydro-chlorofluorocarbons will be phased out by the year 2020 according to the Montreal protocol. Thus, alternative refrigerants like and hydrocarbon mixture (R290/R600a) are used being in place of them. These refrigerants have zero ozone depletion potential and negligible global warming potential. In the present work performance comparison between and hydrocarbon mixture (R290/R600a) has been carried out in domestic refrigerator. In addition to this, diffuser is incorporated at the inlet of condenser, and heat exchanger is arranged at outlet of condenser. The diffuser main purpose compressor work can be reduced and the heat exchanger main purpose refrigeration effect can be increased. Further the energy performance characteristics such as coefficient of performance (COP) and refrigeration effect, compressor work will be found out the above refrigerants ( and HC mixture (R290/R600a). Keywords: Vapour Compression Refrigeration System, Subcooling, Diffuser, Heat exchanger,, HC mixture (R290/R600a). 1. Introduction As per Montreal protocol 1987, the use of chlorofluorocarbons (CFCs) was completely stopped in most of the nations. However, hydro chlorofluorocarbons (HCFCs) refrigerants using in developing nations and developed nations should phase out by 2030.Most of the developed nations reduced the consumption of HCFC refrigerants. The Kyoto Protocol of United Nations Framework Convention on Climate Change (UNFCCC) calls for reduction in emission of six categories of greenhouse gas, which includes hydro fluorocarbons (HFCs) used as refrigerants. To meet the global demand in refrigeration and air-conditioning sector, it is necessary to look for long term alternatives to satisfy the objectives of international protocol. Only a few pure fluids are having properties closer to the existing halogenated refrigerants. The refrigerant mixtures provide much flexibility in searching new environment friendly alternatives to match the desirable properties with the existing halogenated refrigerants. The two alternative options are HC and HFC mixtures with lower GWP.HC based mixtures are environment friendly, which can be used as alternative refrigerants. In agreement with the Montreal protocol many refrigerants containing CFCs and HCFCs were increasingly replaced with hydro-fluorocarbons (HFCs).Which have zero ozone depletion potential (ODP) and negligible global warming potential (GWP). Table1: Properties refrigerants for experimental working Refr iger ant Chem. comp Mol. Wt. g/mol C.T C C.P mpa. NBP C O D P GWP R- C2H2 102 101. 4.06-26 0 1430 134a F4 1 CAR E-30 R290/ R600a 50.15 114. 8 4.04-32.8 0 <20 Refrigeration consists of several equipment s like compressor, condenser, expansion devices, evaporator etc. A refrigerant compressor is a machine used to compress the refrigerant from the evaporator and to raise its pressure so that the corresponding temperature is higher than that of the cooling medium. The condenser is an important device used in the high pressure side of a refrigeration. Its function is to remove heat of the hot Vapour refrigerant discharged from the compressor. The evaporator is used in the low pressure side of a refrigeration. The liquid refrigerant from the expansion device enters into the evaporator where it boils and changes into vapour. The function of an evaporator is to absorb heat from the surrounding location or medium which is to be cooled, by means of a refrigerant. The temperature of the boiling refrigerant in the evaporator must always be less than that of the surrounding medium so that the heat flows to the refrigerant. The expansion device which is also known as throttling device, divides 265

the high pressure side and the low pressure side of a refrigeration. It is connected between the receiver and the evaporator. Many efforts have to be done to improve the performance of vapour compression refrigeration. 2. Literature Review Moo-Yeon lee et. al. (1) have studied the performance of a small capacity directly cooled refrigerator by using the alternative to.the compressor displacement volume of the alternative with R600a/R290 (45/55) has modified from that of the original with to the optimized R600a/R290 was approximately 50% of that of the optimized. The capillary tube lengths for each evaporator in the optimized R600a/R290 were 500mm longer than those in the optimized. The power consumption of the optimized was 12.3% higher than that of the optimized R600a/R290. The cooling speed of the optimized R600a/R290 (45/55) at evaporator 0C was improved temperature by 28.8% over that of the optimized. M.Mohanrajet.al. (2) also carried experimental investigation to find out a drop in replacement for R134a with the binary mixture of45.2%r290/54.8%r600a in a 200 liter single evaporator domestic refrigerator. Tests were carried out at different ambient temperatures (24, 28, 32, 38 and 430C); cycle ON/OFF tests was carried out at 32 0C ambient temperature. The results showed that the HC mixture has lower energy consumption; pull down time and ON time ratio by about 11.1%, 11.6% and 13.2% respectively, with 3.25 to 3.6% higher COP. The discharge temperature of HC mixture was found to be 8.5 to 13.4 K lower than that of R134a. The overall result has proved that the above hydrocarbon refrigerant mixture could be the best long term alternative to R134a. It is clear from the above discussion that various researchers have tried for a suitable alternative for R134a. It has been observed that the energy consumption of R12 appliances tend to increase while they are retrofitted with R134a. These days, the concern for the global warming has never been greater. In 1997 the Kyoto protocol was agreed by many nations calling for the reduction in emissions of greenhouse gases including HFCs (R134a). Pure hydrocarbons are not drop in replacements for R134a refrigerators due to mismatch in saturation characteristics. Zeotropic mixture of 50%R290/50%R600a can be used as drop in replacements for R134a refrigerator by adjusting the capillary length and optimizing the refrigerant charge, but the hydrocarbons have the flammability factor. NeerajaUpadhyay (3) developed a new configuration of the diffuser and sub-cooling in vapour compression refrigeration cycle, for sub-cooling a fan is used. By using diffuser power consumption is less for same refrigeration effect so performance is improved. The size of the condenser can also be reduced due to more heat transfer. So cost of the condenser will be reduced. The parameters like pressure and temperature were measured. After result analysis, we have found that the COP was enhanced from2.65 to 3.38 in the case when conventional Vapour Compression Refrigeration System was used with Diffuser. R. T. Saudagar, Dr. U. S. Wankhede (4) developed advances in vapor compression refrigeration to improve coefficient of performance of and after comparative study suggest a new area of research. It was found through the literature that advances in the design of compressor reduced the compressor work where in capillary tube increased the refrigerating effect. Modifications in condenser are meant to increase degree of sub-cooling of refrigerant which increased refrigerating effect. The minimization of the hunting behavior of evaporator at the onset of superheat using balanced point approach was reviewed as advances in evaporator. The purpose of a compressor in vapor compression is to elevate the pressure of the refrigerant, but refrigerant leaves the compressor with comparatively high velocity which may cause splashing of liquid refrigerant in the condenser, liquid hump and damage to condenser by erosion. It is needed to convert this kinetic energy to pressure energy for this purpose diffuser can be used. R. T. Saudagar, Dr. U. S. Wankhede (5) design and testing of diffuser at condenser inlet in vapour compression refrigeration. Four diffusers with divergence angle 10 o, 15 o, 20 o and 30 o were designed for same inlet and outlet diameters. The diffusers used were with inlet diameter equal to discharge tube diameter of compressor and outlet diameter equal to condenser inlet diameter. The was analyses using the first and second laws of thermodynamics to determine the refrigerating effect, the compressor work input, coefficient of performance (COP) and the rate of heat rejected from the. During the test, the COPs of the without diffuser and with optimized diffuser at condenser inlet were found out. With diffuser at condenser inlet, amount of heat rejected from condenser is also increased. To remove the same amount of heat, less heat transfer area required. This concept reduces size of condenser to achieve the same 266

efficiency. IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December 2015. Amitnarwal, SarveshKumar,RishabhVerma,Ravi Kumar (6) improved coefficient of performance of. To improve the coefficient of performance, it should be noted that compressor work should decrease and refrigerating effect should increase. Modifications in condenser are meant to increase degree of sub-cooling of refrigerant which increased refrigerating effect or more cooling water is required in condenser. The purpose of a compressor in vapour compression is to elevate the pressure of the refrigerant, but refrigerant leaves the compressor with comparatively high velocity which may cause splashing of liquid refrigerant in the condenser tube, liquid hump and damage to condenser by erosion. It is needed to convert this kinetic energy to pressure energy by using diffuser. By using diffuser power consumption is less for same refrigerating effect so performance is improved. Amit prakash (7) improved coefficient of performance of. To improve the coefficient of performance, it is to require that compressor work should decrease and refrigerating effect should increase. Modifications in condenser are meant to increase degree of sub-cooling of refrigerant which increased refrigerating effect or more cooling water is required in condenser. The purpose of a compressor in vapour compression is to elevate the pressure of the refrigerant, but refrigerant leaves the compressor with comparatively high velocity which may cause splashing of liquid refrigerant in the condenser tube, liquid hump and damage to condenser by erosion. It is needed to convert this kinetic energy to pressure energy by using diffuser. By using diffuser power consumption is less for same refrigerating effect so performance is improved. From above literature review it is understood that every scholar tried to improve the COP of VCR either by increasing refrigeration effect or by decreasing the compressor work. Particularly for sub cooling they used different techniques like forced air cooling and water air cooling.it is understood that same effect of sub cooling can be achieved by using heat exchanger. Further improving of COP of VCR it is trying to decrease the compressor work by using of diffuser. For decreasing compressor work diffuser placed at inlet of the condenser. For increasing refrigerating effect heat exchanger is placed at out of the condenser. As a result of both diffuser and heat exchanger COP of VCR may be increased. 3. Experimental Work A Domestic Refrigerator of capacity 215 liters is selected for this experiment. Present work deals with the improvement of vapour compression refrigeration by using sub-cooling (heat echanger at condenser outlet) and diffuser at inlet of condenser (Fig.1) and compare refrigerants,hc mixture (R290/R600a). In this work, individual testing of 1.existing, 2.modified with sub-cooling and 3.modified with diffuser and with sub-cooling both refrigerants carried out by experimentally. For this purpose, first of all vaccum is created in the refrigerating compressor and pressure gauges, i.e. low pressure gauge is fitted at suction line to the compressor and high pressure gauge is fitted at discharge of the compressor. And also thermo couples are fitted for various temperature measurements i.e. at compressor outlet, at condenser outlet, at evaporator outlet, at defreezer. 1.The existing experiment is started first with R134a. Observations are noted like suction and discharge pressures, various temperature readings. Energy performance calculations are done like Refrigeration effect, Compressor work, COP. Similarly the refrigerant HC mixture (R290/R600a) also be tested with existing. Finally the existing of both refrigerants performance values are listed below table 2. 2.For the modified heat exchanger is arranged at outlet of condenser (Fig.1). The heat exchanger main purpose is increase the refrigerating effect by sub-cooling the refrigerant. Heat exchanger is a passive device for operating heat exchanger no need of power. Finally the modified with heat exchanger the experiment is started with and calculations are done. Similarly the refrigerant HC mixture (R290/R600a) also be tested with improved with sub-cooling. Finally the improved with sub-cooling of both refrigerants performance values are listed below table 2. 3.Finally the improved with diffuser at condenser inlet and with heat exchanger at condenser outlet (Fig.1). The diffuser is a device which slows down fluid. That means velocity of fluid decreases with increasing pressure. The main purpose of diffuser is compressor work can be reduced. So finally the improved experiment will be started and calculations are done. Similarly the refrigerant HC mixture (R290/R600a) also be tested with improved. Finally the improved of both refrigerants performance values are listed below table 2. 267

Fig. 1 Line diagram of Experimental setup Compressor work (kj/kg) 300 Refrigeration effect kj/kg 250 200 150 100 COP 133 46 47 45 250 270 284 143 148 with and diffuser HC mixture (R290/R 600a) (R290/ R600a) 85 88 84 2.89 3.04 3.29 (R290/ R600a) 2.94 3.06 3.38 Graph 1: Variation of Refrigeration effect The above graph shows that Refrigeration effect of the both s compare the refrigerants is and HC mixture (R290/R600a). Fig. 2 Experimental Working 4. Results and Discussion By performing this experiment the following results were obtained. Table2: Experimental comparison with both refrigerants (R134a and HC mixture) Parameter Refrigeratin g effect (kj/kg) System with heat exchanger with diffuser and heat exchanger 133 143 148 (R290/ R600a) 250 270 284 Refrigeration effect of the existing is 133 KJ/kg and refrigeration effect of the existing HC mixture is 250 KJ/kg. Refrigeration effect of the improved with is 143 KJ/Kg and refrigeration effect of the existing and sub-cooling HC mixture is 270 kj/kg. Refrigeration effect of improved with sub-cooling and diffuser is 148 kj/kg and refrigeration effect of improved with sub-cooling and diffuser HC mixture is 284 kj/kg. The refrigeration effect of the modified with and diffuser is increased due to the refrigerant is HC mixture (R290/R600a) by compare to. 268

Compressor work kj/kg 90 80 70 60 50 40 85 46 47 88 44 84 with with and diffuser HC mixture (R290/R 600a) COP 3.4 3.2 3 2.8 2.6 2.4 2.94 2.89 3.043.06 with 3.38 3.29 with and diffuser HC mixture (R290/R6 00a) Graph 2: Variation of Compressor work Graph 3: Variation of COP The above graph shows that compressor work of the both s compare the refrigerants is and HC mixture (R290/R600a). Compressor work of the existing is 46 KJ/kg and compressor work of the existing HC mixture is 85 KJ/kg. Compressor work of the improved with is 47 KJ/Kg and compressor work of the existing and sub-cooling HC mixture is 88 kj/kg. Compressor work of improved with sub-cooling and diffuser is 44kJ/kg and compressor work of improved with sub-cooling and diffuser HC mixture is 84 kj/kg. The compressor work of the modified with and diffuser is decreased due to the refrigerants are and HC mixture (R290/R600a). The compressor work of modified is decreased due to diffuser. Refrigerant leaves the compressor with high velocity which may result in splashing of liquid refrigerant in the condenser. A diffuser is placed at the inlet of the condenser, and as a result the compressor work is reduced considerably. Coefficient of performance of the existing is 2.89 and coefficient of performance of the existing HC mixture is 2.94. Coefficient of performance of the improved with sub-cooling is 3.04 and coefficient of performance of the existing and sub-cooling HC mixture is 3.06. Coefficient of performance of improved with and diffuser is 3.29 and coefficient of performance of improved with sub-cooling and diffuser HC mixture is 3.38. The coefficient of performance of the modified with sub-cooling and diffuser is increased due to the refrigerant is HC mixture (R290/R600a) by compare to R- 134a. COP of modified is increased due to reduction of compressor work and increase in refrigerating effect. For reduction of compressor work diffuser is used, for increasing refrigerating effect sub cooling is done. 5. Conclusions Experimental analysis of diffuser at the condenser inlet and heat exchanger at condenser outlet of vapor compression refrigeration of a domestic refrigerator of 215 liters capacity, with and HC mixture(r290/r600a) as refrigerants. The results obtained are presented below. 269

For the existing the COP is 2.89, work done by the compressor in the normal VCR is 46 KJ/Kg and the power consumption by the VCR is 1.2 KW. For the modified VCR with the heat exchanger at condenser out let, the cop is 3.04, work done by the compressor in the modified VCR is 47 KJ/Kg and the power consumption by the VCR is 1.143 KW. From the above results it is also concluded that, all the performance parameters for R134a and HC Mixture (R290/R600a) behave similar and HC Mixture have high COP. Presently R134a is used as a transitional replacement for R12. But R134a has higher GWP. Hence permanent solution is necessary. HC Mixture (R290/R600a) with zero ODP and negligible GWP. Hence it is recommended that HC Mixture (R290/R600a) may be used as an alternative refrigerant for R- 134aapplications. For the modified VCR with the diffuser at the condenser coil inlet and heat exchanger at condenser outlet, the cop is 3.29, work done by the compressor in the modified VCR is 44 kj/kg and the power consumption by the VCR is 1.06 KW. HC mixture (R290/R600a) For the existing the COP is 2.94, work done by the compressor in the normal VCR is 85 KJ/Kg and the power consumption by the VCR is 1.19 KW. For the modified VCR with the heat exchanger at condenser out let, the cop is 3.06, work done by the compressor in the modified VCR is 88 KJ/Kg and the power consumption by the VCR is 1.12 KW. For the modified VCR with the diffuser at the condenser coil inlet and heat exchanger at condenser outlet, the cop is 3.38, work done by the compressor in the modified VCR is 84 kj/kg and the power consumption by the VCR is 1.02 KW. Comparing both the refrigerants and HC mixture with the modified with diffuser and heat exchanger it is observed and increase of 0.09 in COP. The modified VCR with the diffuser at the condenser inlet and heat exchanger at condenser out let. Comparing both the refrigerants and HC mixture with the modified with diffuser and heat exchanger it is observed and decrease of 0.04 in power consumption. The modified VCR with the diffuser at the condenser inlet and heat exchanger at condenser out let. Hence it is recommended that to place a diffuser at the condenser inlet and heat exchanger at condenser outlet these gives an increase in discharge pressure and refrigerating effect, reduces the work done by the compressor and power consumption for the refrigerator of 215 liters of capacity with R134a and HC mixture as refrigerants. References [1] Moo-Yeon Lee, The performance of a small capacity directlycooled refrigerator by using the mixture of R600a/R290 mass fraction of 45:55 as an alternative to R134a, International Journal of Refrigeration June 2008. [2] NeerajaUpodhya, To study the effect of Sub-cooling and Diffuser on the Coefficient of Performance of Vapour Compression Refrigeration System, International Journal of Research in Aeronautical and Mechanical Engineering ISSN: 2321-3051 June 2014. [3] R.T.Saudagar, and Dr.U.S.Wankhede, Vapour compression refrigeration with diffuser at condenser inlet, International Journal of Engineering Research and Development ISSN: 2278-0673, Volume 1, Issue 11 (July 2012), PP. 67-70. [4] M Yari, and M Sirousazar, Performance analysis of the ejector-vapour compression refrigeration cycle, Part A: Journal of Power and Energy,Vol.221, No. 8, December 2007, pp. 1089-1098. [5] Selvaraju, and A. Mani, Analysis of an ejector with environment friendly refrigerants, Applied Thermal Engineering, 2004, pp. 1-12. [6] Jianlin Yu, Hua Zhao and Yanzhong Li, Application of an ejector in auto cascade refrigeration cycle for the performance improvement, International journal of refrigeration, vol.31, 2008, pp.279-286. [7] N.D. Banker, P. Dutta, M. Prasad and K. Srinivasan, Performance studies on mechanical+ adsorption hybrid compression refrigeration cycles with HFC 134a, In ternational journal of refrigeration, vol.31, 2008, pp.1398-140. [8] P N Ananthanarayanan, Basic Refrigeration and Air Conditioning, Tata McGraw-Hil 2004. [9] P.L.Ballany, Refrigeration and Air Conditioning khana publishers, 2004. [10] S.C Arora, and Domukundawar, Refrigeration and Air Conditioning, Dhanpatrai sons Publications Co.Ltd.,2000. 270

[11] Amit Prakash, Improving the performance of Vapor compression refrigeration by using sub- cooling and diffuser, International Journal of Engineering, Business and Enterprise Applications 13-129 2013. [12] R.S. Khurmi, G.K. Gupta S.Chand, A Text book of Refrigeration And Air Conditioning, 2006. 271