Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

Similar documents
Technical Instructions Document No P25 ET September 28, ET 141 Electric Surface Mounted Thermostat.

Powers TM Controls ET 134 Line Voltage Room Thermostats

Powers Controls ET 134 Low Temperature Detection Thermostat

Powers Controls Low Temperature Detection Thermostat

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

TC-5231 Series, TC-5232, & TC-5241 Series

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

A19, A28 Series Thermostats for Agricultural Buildings

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

The T6140A,B Remote Bulb Temperature Controller

POWERS CONTROLS Pneumatic Thermostat Covers

POWERS Pneumatic Thermostat Covers

Powers Controls Free Energy Band TH 193 HC Hesitation Room Thermostat

Powers TM Controls Accessories for Installing TH 192, TH 194 or Free Energy Band TH 193 HC Room Thermostats

T4398A,B Precision Electric Heating Thermostat

Retrostat Kits for Johnson Controls D/N or H/C Thermostats

TK-1001, 1101, 1201, 1301, 1601

Installation Instructions

CAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS

A11 Series Low Temperature Cutout Controls

59T, 66T Series Electric Water Heater Controls

W43A Humidistat. Features and Benefits

TK-2001, TK-2012, TK-2201, TK-3001, TK-3201, TK-4001, TK-4012, TK-4212 TK

POWERS TM Controls HU 186 Room And Duct Hygrostats

59T, 66T Series Electric Water Heater Controls

DS 2001 REVISED Humidifier Assembly and Instruction Manual

T874 Multistage Thermostat and Q674 Subbase

Multistack Modbus Driver: Standard Unit

Thermostats type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety, Installation, and Operation Manual

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

HE120, HE160 Humidifier Installation Kit

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

L Honeywell. L4068 has spst switch; L6068 has spdt switch. L4068A,C,E,F have adjustable FAN OFF and differential settings.

KUH. Horizontal Unit Heater. Applications. Description

CUSTOMER SERVICE. Toll-free:

Schneider Electric Erie T155 Series

Powers TM Controls TH 188 Unit Mounted Thermostat

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer. Hot Water Inlet. Cold Water Inlet G3600LF

Thermostat KPU. Data sheet

ELECTRIC SPA-PAK HEATER INSTALLATION & OPERATING INSTRUCTIONS

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

Capillary & Bulb Thermostatic Control & Fail-Safe Limit

Thermostat Catalog 2004

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

Commercial/Industrial Combustion Control Level Three Announcement

Description. Construction

T4398A,B High Performance Electric Heat Thermostats

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

T834C Heating-Cooling Thermostat

Rotary XL (558 Series) and Classic (548 Series)

SECTION (15767) - UNIT HEATERS

L4188A,B; L4189A,B; L6188A-C; L6189A-C Aquastat Controllers

36T. Bimetal Disc Controls & Limits. Introduction

HE360 Humidifier Installation Kit

Installation, Operation and Maintenance Guide AP3900 Series Thermostatic Mixing Valves

LIFTAIRE II ELEVATOR AIR CONDITIONER

MR3CCUHV Temperature/Defrost Control

DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE

C6097A,B Pressure Switches

BULLETIN 600 SINGLE PHASE

T-Series Air Conditioner T15 Model

Two-Position Electric Duplex Room Thermostats

FAN POWERED VAV TERMINALS


Wiring Instructions. High-Capacity Steam Humidifiers

TK-1801, TK-1811 TK-1801, TKR-1811

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

OWNER S MANUAL MODEL BW4B SLICER WARMER

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

CLe-series Dishwashers

Installation Instructions. Remanufactured Veeder-Root Overfill Alarm and. Acknowledgement Switch. Overfill Alarm PMP # OEM #

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

Thermostat Catalog 2004

Tubular Industrial Process

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

T4098A,B Deluxe Electric Heat Thermostats

temperature Controllers

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015

Duct electric heater with temperature controller

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

Installation, Operation and Maintenance Guide G3600 Series Thermostatic Mixing Valves

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Tempered Water Outlet. Hot Water Inlet.

CAUTION CAUTION HCWB2 & HCWP2 SERIES IAQ HUMIDIFIERS USER S MANUAL FOR HCWB2 AND HCWP2 HUMIDIFIERS. Table Of Contents

BACK BAR REFRIGERATION Installation, Operation and Maintenance Instructions

Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s)

Mini Tank water heater Electric undersink Water heaters GL GL 4 - GL 6+

FAN POWERED VAV TERMINALS

QPM21 Series Duct CO 2 and Air Quality Sensors

Installation Instructions 30 French Door Built-in Wall Ovens

T-Series Air Conditioner T20 Model

Duct electric heater with heating. capacity from 0.6 kw up to 2.4 kw and an integrated. temperature controller

2 shp 13 lc 1 36 t - 1 a

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

INDEX APPLIANCE GAS WATER HEATER CONTROLS 150 ELECTRIC WATER HEATER THERMOSTATS 151 SNAP DISC CONTROLS/LIMITS/SWITCHES 152 GAS DRYER VALVES 153

Transcription:

Document No. 155-021P25 ET 141-5 ET 141 High Limit Control Thermostat Description Application The ET 141 high limit control thermostat is duct mounted and has a rigid bulb, bi-metal rod and tube construction. Normally, the thermostat is used as a high limit control when a "lock-out" type control is desired or required by local code. Often it is located in a return air duct and is wired to shut down air conditioning or ventilating fans when the duct air temperature becomes excessive. Product Number 141-0530 Specifications Switch Action Single-Pole, Single-Throw (SPST) manual reset Scale Range Adjustable from 25 F (-4 C) to 215 F (102 C) Maximum Bulb Temperature 300 F (149 C) Cover Finish Gray baked enamel galvanized steel Shipping Weight 1.8 Ib (0.8 kg) Thermal System Rigid bulb, bi-metal rod and tube construction Dimensions See Figure 3 Agency Certification UL Listed: File MP3487, CCN MBPR CSA Certified: File LR 948, Class 4813 02 Locked Rotor Amps (LRA) Table 1. Electrical Ratings. Motor Ratings (Full Load Amps) Non-Inductive Amps 120 Vac 240 Vac 120 Vac 240 Vac 120 Vac 240 Vac 96 48 16 8 16 16

ET 141 High Limit Control Thermostat Operation and Adjustment The setpoint adjustment knob (see Figure 2) permits adjustment of the setpoint between 25 F and 215 F (-4 C and 101 C). The temperature differential is factory set, non-adjustable, and approximately 20 F (11 C), depending on the rate of temperature change. The standard model includes a knob for setpoint adjustment. Temperature Setpoint Stop The temperature setpoint stop is an integral part of these controls, and is field adjustable. To set the stop, do the following: 1. Set dial temperature at desired stop. 2. Remove control cover. 3. Loosen the stop screw, slide the screw to the front of the control against the plastic stop behind the dial, and tighten the screw (see Figure 2). Sometimes, an exact stop setting is not possible, and the stop must be set to the closest stop corresponding to the required dial setting. Cutout Stop Bracket With Slot and Screw ET0110R1 Figure 1. Setpoint Stop Screw. Setpoint Adjustment Screw Reset Procedure Verify that the temperature has dropped to 20 F (11 C) below setpoint. Press the reset lever to reset the unit (closing the circuit). Reset Lever Setpoint Window ET0108R1 Setpoint Knob Figure 2. Page 2

ET 141 High Limit Control Thermostat Technical Instructions Installation 1. Select a mounting location for the thermostat in the duct (or plenum). The location must allow the sensing element to measure the average temperature in the duct. 2. Drill (or cut) a 1-3/8 inch hole in the duct at the selected mounting location (see Figure 3). 3. Using the flange as a template on the duct, mark the location for two #10 1/2" long sheet metal screws. 4. Punch (or drill) both sheet metal screw holes in the duct at the marked locations. 5. Secure the flange to the duct with the two #10 1/2" long sheet metal screws provided. 6. Insert the sensing element and sleeve through the flange installed in Step 5 (and into the duct). 7. Secure the thermostat to the flange by screwing the set screw firmly against the sleeve. Do not over-tighten the set screw. Insert the sensing element as far as possible into the air stream without allowing it to contact any object inside the duct. Provide at least 5-3/4 inch (14 cm) clearance between the sensor and any other objects inside the duct. Duct Set Screw Sheet Metal Screw Hole Flange 1-3/8 in. Hole 141-0530 Sensing Element Sheet Metal Screw Sleeve ET0105R1 Figure 3. Installation. Page 3

ET 141 High Limit Control Thermostat Wiring Diagram When the temperature increases to above the setpoint, the circuit opens. When the reset lever is pressed after the sensed temperature decreases to approximately 20F (11C ) below the setpoint, the circuit closes. See Figures 4 and 5 for terminal identification and typical wiring connections. Only use the terminal screws furnished with the thermostat (#8-32 1/4-inch binder head). Use of other screws will void warranty, may damage switch terminals, and result in improper connections Common Power Supply 141-0530 Other Operating or Limiting Control Fan Motor or Motor Starter Coil ET0106R1 Figure 4. Terminal Identification. ET0107R1 Figure 5. Typical Wiring Diagram. Checkout Procedure Return Air Applications After installing the thermostat, perform the following procedures. Observe at least three complete operating cycles to verify that all components are functioning properly. If the unit fails to checkout, replace it. 1. After completing the installation and wiring procedures, turn on the power to the circuit. 2. Turn the setpoint knob counterclockwise until the thermostat shuts down the system. The thermostat should lock-out. The setpoint at shutdown should equal the approximate duct air temperature. 3. Turn the setpoint knob clockwise to the desired setpoint. Nothing should happen. 4. Press the reset lever. The system should restart. Page 4

ET 141 High Limit Control Thermostat Technical Instructions Supply Air Applications 1. After completing the installation and wiring procedures, turn on the power to the circuit. 2. Raise the supply air temperature to the setpoint temperature. The supply air temperature can be raised by simulating a fan failure or restricting the return air flow. 3. When the system shuts down, determine the temperature at the thermostat sensing element. The temperature reading should closely approximate the thermostat's setpoint at which the system is shut down. 4. Return the system to normal operation by re-establishing the air flow or by restarting the fan. 5. Press the reset lever. The system should restart. Service There is no servicing of this thermostat. Replace if inoperative. Dimensions 0.34 (9) 4.41 (112) 0.61 (15) 0.35 (9) 1.81 46 1.30 33 3.66 (93) 1.25 (32) 9.33 (237) 0.5 (13) 4 (102) 0.25ÿ (6) 0.75ÿ (19) Diameter Diameter 2.16 (55) ET0109R1 0.88 (22) Diameter Figure 6. Dimensions in Inches (Millimeters in Parentheses). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. 2004 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A. Your feedback is important to us. If you have Document No. 155-021P25 comments about this document, please send Country of Origin: US them to technical.editor@siemens.com Page 5