AHRI Standard 870 (I-P) Standard for Performance Rating of Direct Geoexchange Heat Pumps

Similar documents
Performance Rating of Heat Pump Pool Heaters

Performance Rating of Heat Pump Pool Heaters

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

Performance Rating of Unit Ventilators

ANSI/AHRI Standard 911 (SI) 2014 Standard for Performance Rating of Indoor Pool Dehumidifiers

Performance Rating of Automatic Commercial Ice-makers

Performance Rating of Refrigerant Pressure Regulating Valves

ANSI/AHRI Standard 620 (I-P) 2014 Standard for Performance Rating of Self-contained Humidifiers for Residential Applications

Flow Capacity Rating of Suction Line Filters and Suction Line Filter Driers

AHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

Sound Performance Rating of Non-ducted Indoor Airconditioning

Sound Performance Rating of Outdoor Unitary Equipment

Performance Rating of Computer and Data Processing Room Air Conditioners

Performance Rating of Active Chilled Beams

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

Specifications for Fluorocarbon Refrigerants

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

Specifications for Fluorocarbon Refrigerants

ANSI/AHRI Standard 1360 (I-P) 2016 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners

AHRI Guideline N with Addendum Guideline for Assignment of Refrigerant Container Colors. ARI Standard 1200

Performance Rating of Commercial and Industrial Humidifiers

2015 Standard for Performance Rating of Refrigerant Recovery Equipment and Recovery/Recycling Equipment

ANSI/AHRI Standard Standard for Performance Rating of Indoor Pool Dehumidifiers

AHRI Standard 1360 (I-P) 2017 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners

ANSI/AHRI Standard 1351 (SI) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings

AHRI Guideline N Guideline for Assignment of Refrigerant Container Colors. ARI Standard 1200

Specifications for Refrigerants

Specifications for Refrigerants

1997 STANDARD for APPLICATION OF SOUND RATING LEVELS OF OUTDOOR UNITARY EQUIPMENT. Standard NORTH FAIRFAX DRIVE! ARLINGTON, VIRGINIA 22203

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

WATER-SOURCE HEAT PUMPS CERTIFICATION PROGRAM For 50 Hz Products

ASHRAE Standard

ASHRAE Standard

AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING AND TESTING REQUIREMENTS FOR LOW CAPACITY WINDOW TYPE AND SINGLE-SPLIT

2016 Annual Conference

INDOOR POOL DEHUMIDIFIERS CERTIFICATION PROGRAM

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Methods of Testing Capacity of Refrigerant Solenoid Valves

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Low GWP Refrigerants for Air Conditioning Applications

CHAPTER 6 REFERENCED STANDARDS. American Architectural Manufacturers Association 1827 Walden Office Square Suite 550 Schaumburg, IL

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Pressure Enthalpy Charts

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

CHAPTER 5 REFERENCED STANDARDS. American Architectural Manufacturers Association 1827 Walden Office Square Suite 550 Schaumburg, IL

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Certification Programs, Standards,

IECEE OPERATIONAL DOCUMENT

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance

Saudi Standards, Metrology and Quality Org.(SASO)

CHAPTER 6 [CE] REFERENCED STANDARDS

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Oxyvap Evaporative Cooling Applications

Report No CRT-414

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

January 16 th, 2014 New York City

Approval Standard for Electric Equipment for use in Hazardous (Classified) Locations General Requirements

0.4 In the preparation of this standard, assistance has been derived from the following standards:

Low Global Warming Refrigerants For Commercial Refrigeration Systems

The products covered by the Regulation can be classified as follows:

The Refrigeration Cycle

Unofficial Translation

Geothermal Heat Pump Systems

Method of Test for Rating Pool Heaters

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

ENGINEERING. Edition No. 13 October 2002

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

IS0 INTERNATIONAL ORGANIZATION FOR STANDARDIZATION IS0 RECOMMENDATION R 916 TESTING OF REFRIGERATING. 1st EDITION. December 1968

Applying VRF? Don t Overlook Standard 15

AHRI Certification Program Scopes - COOLING

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Refrigerant Glide and Effect on Performances Declaration

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Applying VRF? Don t Overlook Standard 15

Application Engineering

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

ENGINEERING SPECIFICATIONS

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

ENGINEERING SPECIFICATIONS

ISO INTERNATIONAL STANDARD. Safety identification Escape and evacuation plan signs. Identification de sécurité Plans d'évacuation et de secours

INTERNATIONAL STANDARD

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Providing Solutions. Simplifying Regulation. IIAR Standards. Peter Thomas, P.E., CSP Resource Compliance, Inc.

SECTION AIR-SOURCE UNITARY HEAT PUMPS

Transcription:

AHRI Standard 870 (I-P) - 2016 2016 Standard for Performance Rating of Direct Geoexchange Heat Pumps

IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be nonhazardous or free from risk. Note: This standard supersedes ANSI/AHRI Standard 870-2005 with Addendum 1. For SI ratings, see AHRI Standard 871 (SI) -2016. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The certification program includes all factory made residential, commercial and industrial Direct Geoexchange Heat Pumps as defined in Section 3. It does not apply to the rating and testing of retrofit units. Certified Ratings The following ratings are verified by test at the Standard Rating Conditions: 1. Full load Cooling Capacity, Btu/h 2. Full load Heating Capacity, Btu/h 3. Energy Efficiency Ratio, EER, Btu/(W h) 4. Coefficient of Performance, COP (W/W) 5. Part-load Cooling Capacity (if applicable), Btu/h 6. Part-load Heating Capacity (if applicable), Btu/h 7. Part-load Energy Efficiency Ratio (if applicable), EER, Btu/(W h) 8. Part-load Coefficient of Performance (if applicable), COP (W/W) Price $10.00 (M) $20.00 (NM) Printed in U.S.A. Copyright 2016, by Air-Conditioning, Heating, and Refrigeration Institute Registered United States Patent and Trademark Office

TABLE OF CONTENTS SECTION PAGE Section 1. Purpose... 1 Section 2. Scope... 1 Section 3. Definitions... 1 Section 4. Classification... 3 Section 5. Test Requirements... 4 Section 6 Rating Requirements... 4 Section 7. Minimum Data Requirements for Published Ratings... 5 Section 8. Operating Requirements... 6 Section 9. Marking and Nameplate Data... 6 Section 10. Conformance Conditions... 6 TABLES Table 1. Classification of Direct Geoexchange Heat Pumps... 3 Table 2. Capacity Rating Multiples... 4 Table 3. Standard Rating Conditions... 5 APPENDICES Appendix A. References Normative... 7 Appendix B. References Informative... 7

PERFORMANCE RATING OF DIRECT GEOEXCHANGE HEAT PUMPS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Direct Geoexchange Heat Pumps: definitions; classification; test and rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. For the remainder of this standard, the terms heat pump or equipment are also used to designate Direct Geoexchange Heat Pumps. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory made residential, commercial and industrial Direct Geoexchange Heat Pumps as defined in Section 3, and within the capacity range of 18,000 Btu/h through 180,000 Btu/h. 2.1.1 Energy Source. This standard applies only to electrically-driven, mechanical vapor-compression refrigeration systems. 2.1.2 Alternative Applications. Equipment designed for rating under this standard is not suitable for alternative applications covered in ANSI/AHRI/ASHRAE ISO Standards 13256-1 and 13256-2. 2.1.3 Exclusions. This standard applies to the rating and testing of complete refrigeration systems and does not apply to individual system components for separate use. Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Terminology website (https://www.ashrae.org/resources--publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Coefficient of Performance (COP). The ratio of Cooling/Heating Capacity in watts to the power input values in watts at any given set of Rating Conditions expressed in watts/watt. For heating COP, supplementary resistance heat shall be excluded. 3.2 Cooling Capacity. The capacity associated with the change in air enthalpy which includes both the latent and sensible capacities expressed in Btu/h. 3.3 Direct Geoexchange Heat Exchanger. A continuous sealed tube(s) heat exchanger with refrigerant supply and refrigerant return. This may be comprised of several tubes and may be supplied with each heat pump. The heat exchanger(s) may be factory or field assembled. 3.4 Direct Geoexchange Heat Pump (DGX). A heat pump consisting of (1) one or more factory made assemblies which normally include an indoor conditioning coil with air or water moving means, (2) compressor(s), and (3) a subsurface refrigerant piping loop system functioning as a Direct Geoexchange Heat Exchanger, and may include means to provide a heating function, or a cooling function, or both. The separate system components shall be designed for use together. Models designated as cooling only need not include the heating function and models designated heating only need not include the cooling function. The four types of Direct Geoexchange Heat Pumps within the scope of this standard are as follows. 3.4.1 DGX-to-Air Split System (Type 1). Compressor and indoor coil are in separate cabinets. Indoor coil is with or without a fan. 1

3.4.2 DGX-to-Air Packaged System (Type 2). Compressor and indoor coil are in one cabinet, with or without a fan. 3.4.3 DGX-to-Water Split System (Type 3). Compressor and Indoor water-to-refrigerant heat exchanger are in separate cabinets. Indoor water-to-refrigerant heat exchanger is with or without a pump. 3.4.4 DGX-to-Water Packaged System (Type 4). Compressor and indoor water-to-refrigerant heat exchanger are in one cabinet. Indoor heat exchanger is with or without a pump. Note: ANSI/ASHRAE Standard 194 uses the term Direct-expansion Ground Source Heat Pump in lieu of Direct Geoexchange Heat Pump. 3.5 Effective Power Input. The average electrical power input in watts, supplied to the equipment within a defined interval of time. This is the sum of the following, as appropriate: 3.5.1 The power input for the operation of the compressor, excluding supplemental electric heat, W 3.5.2 The power input of all control and safety devices of the equipment, W 3.5.3 The proportional power input of the conveying devices for the transport of heat transfer media through the heat pump only (e.g., fans, pumps, whether internal or external, whether provided with heat pump or not), W 3.6 Energy Efficiency Ratio (EER). The ratio of the Cooling Capacity in Btu/h, to the Effective Power Input in watts, at any given set of Rating Conditions, Btu/(W h). 3.7 Heating Capacity. For DGX-to-Air systems, the rate at which the equipment adds heat to the air passing through the indoor coil under specified conditions of operation, including the fan power adjustment. For DGX-to-Water systems, the rate at which the equipment adds heat to the Indoor Water passing through the indoor heat exchanger under specified conditions of operation, including the pump power adjustment, Btu/h. 3.8 Indoor Water. The liquid used in the indoor side water-to-refrigerant heat exchanger. This is not the same working fluid as the Test Liquid. 3.9 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a heat pump may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the heat pump or published in its specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.9.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions). 3.9.2 Part-load Rating. A rating based on tests performed at part-load Rating Conditions. 3.9.3 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.10 Rating Conditions. Any set of Rating Conditions under which a single level of performance results and which causes only that level of performance to occur. 3.10.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics as listed in Table 3. 3.11 Shall or Should. Shall or Should shall be interpreted as follows: 3.11.1 Shall. Where Shall or Shall not is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 2

3.11.2 Should. Should is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.12 Test Liquid. An antifreeze mixture used in the refrigerant-to-test liquid heat exchanger (ground loop simulator) consisting of water and 15% methanol, by mass. Section 4. Classification 4.1 Classification. Direct Geoexchange Heat Pumps (DGX) within the scope of this standard shall be classified as shown in Table 1. Designation Table 1. Classification of Direct Geoexchange Heat Pumps AHRI Type 3 Arrangement Heating & Cooling Heating Only Cooling Only 1 DGX-to-Air Split System (Type 1) with Indoor Fan HRCU-DGX-CB HORCU-DGX-CB HCRCU-DGX-CB FAN INDOOR COIL DGX-to-Air Split System (Type 1) without Indoor Fan HRCU-DGX-C HORCU-DGX-C HCRCU-DGX-C INDOOR COIL DGX-to-Air Packaged System (Type 2) with Indoor Fan HSP-DGX-CB HOSP-DGX-CB HCSP-DGX-CB FAN INDOOR COIL DGX-to-Air Packaged System (Type 2) without Indoor Fan HSP-DGX-C HOSP-DGX-C HCSP-DGX-C INDOOR COIL DGX-to-Water Split System (Type 3) with Circulating Pump HRCU-DGX-CWP HORCU-DGX-CWP HCRCU-DGX-CWP DGX-to-Water Split System (Type 3) without Circulating Pump HRCU-DGX-CW HORCU-DGX-CW HCRCU-DGX-CW CIRC PUMP INDOOR HX INDOOR HX DGX-to-Water Packaged System (Type 4) with Circulating Pump HSP-DGX-CWP HOSP-DGX-CWP HCSP-DGX-CWP CIRC PUMP INDOOR HX DGX-to-Water Packaged System (Type 4) without Circulating Pump HSP-DGX-CW HOSP-DGX-CW HCSP-DGX-CW Legend First Segment: INDOOR HX Notes: 1. Arrangement denotes Heating & Cooling and Heating Only mode functions. Separated enclosures indicate a remote condensing unit (RCU) and adjoining enclosures indicate a single package (SP). 2. HEAT denotes supplemental heating options such as electric resistance heat. 3. For AHRI Types XXXX-YYY-ZZZ, XXXX is Segment 1, YYY is Segment 2, and ZZZ is Segment 3. H = Heat Pump (Heating and Cooling, unless followed by an O or C ) O = Heating Only C = Cooling Only R = Remote CU = Condensing Unit SP = Single Package Second Segment: DGX = Direct Geoexchange System Third Segment: C = Outdoor Coil (Ground Loop) B = Indoor Fan W = Indoor Water Heat Exchanger P = Indoor Circulating Pump 3

Section 5. Test Requirements 5.1 Test Methods. All tests shall be conducted in accordance with ANSI/ASHRAE Standard 194. Section 6. Rating Requirements 6.1 Standard Rating. Standard Ratings shall be established at the Standard Rating Conditions specified in Section 6.1.3 using test procedures described in ANSI/ASHRAE Standard 194. Standard Ratings relating to Cooling and Heating Capacities shall be net values, including the effects of circulating fan and circulating pump heat, but not including supplementary heat. Standard efficiency ratings shall be based on Effective Power Input as defined in Section 3.6. 6.1.1 Values of Standard Capacity Ratings. Capcaity ratings shall be expressed only in terms of Btu/h in multiples shown in Table 2. Table 2. Capacity Rating Multiples Capacity Ratings, Btu/h Multiples, Btu/h and 200 and 500 65,000 and <135,000 1,000 135,000 and 180,000 2,000 6.1.2 Values of Standard Energy Efficiency Ratio or Coefficients of Performance. Standard Energy Efficiency Ratios for cooling, whenever published, shall be expressed in multiples of the nearest 0.1 Btu/(W h). Standard Coefficients of Performance for heating, whenever published, shall be expressed in multiples of the nearest 0.1 Btu/(W h). 6.1.3 Standard Rating Conditions. Equipment with dual rated frequencies shall be tested at each frequency. The test conditions for Standard Ratings shall include the following. 6.1.3.1 Standard Rating Conditions. Standard Rating Conditions for all types are described in Table 3. For each test, the heat pump shall be operated and readings taken in accordance with ANSI/ASHRAE Standard 194. 6.1.3.2 Electrical Conditions. Standard rating tests shall be performaned at the nameplate rated voltage and frequency. 4

Equipment Classification DGX-to-Air (Types 1 &2) DGX-to- Water (Types 3 &4) Note: Rating Conditions Standard Part-load Standard Table 3. Standard Rating Conditions Operating Mode Entering Air Temperature dry bulb/wet bulb,ºf Entering Water Temperature, ºF Surrounding Air Temperature,ºF Saturated Refrigerant Temperature,ºF 1 (Evaporating) (Condensing) Heat 68.0/59.0 N/A 68.0 32.0 (Evap) Cool 80.6/66.2 N/A 80.6 77.0 (Cond) Heat 68.0/59.0 N/A 68.0 41.0 (Evap) Cool 80.6/66.2 N/A 80.6 68.0 (Cond) Heat N/A 104.0 59.0-86.0 32.0 (Evap) Cool N/A 53.6 59.0-86.0 77.0 (Cond) Heat N/A 104.0 59.0-86.0 41.0 (Evap) Part-load Cool N/A 53.6 59.0-86.0 68.0 (Cond) 1. Refrigerant pressure and temperature are measured at the inlet to the heat pump being tested. Increasing superheat will increase the equipment entering refrigerant temperature and increasing sub-cooling will decrease the equipment leaving refrigerant temperature. 6.2 Part-load Rating. Heat pumps which are capable of capacity control shall be rated at each step of capacity reductionprovided by the heat pump and allowed by the controls. 6.2.1 Part-load Rating Conditions. The conditions of test for Part-load Ratings are the same as for the Standard Ratings in Section 6.1 except for the values listed in Table 3. 6.2.1.1 Capacity Reduction Means May be Adjusted to Obtain the Specified Step of Unloading. No manual adjustment of indoor air quantities or water flow rates from those of Standard Rating Conditions shall be made. Automatic adjustment of the quantities by system function is permissible provided it is by means of a control system which is an integral part of the equipment to be tested and the control is configured to function in accordance with the manufacturer s published instructions. The manufacturer must provide a schematic and sequence of operation for providing control of the system during test. Section 7. Minimum Data Requirements for Published Ratings 7.1 Minimum Data Requirements for Published Ratings. As a minimum, Published Ratings shall include Standard Ratings and, as applicable, Part-load Ratings. All claims to ratings within the scope of this standard shall include the statement Rated in accordance with AHRI Standard 870 (I-P). All claims to ratings outside the scope of this standard shall include the statement Outside the scope of AHRI Standard 870 (I-P). Wherever Application Ratings are published or printed, they shall include a statement of the conditions at which the ratings apply. Calculations for the Published Ratings shall be in accordance with ANSI/ASHRAE Standard 194. 7.1.1 Published Ratings shall consist of the following information at Standard Rating Conditions and part-load Rating Conditions, as appropriate: 7.1.1.1 Cooling Capacity, Btu/h 7.1.1.2 Energy Efficiency Ratio, EER, Btu/(W h) 7.1.1.3 Heating Capacity, Btu/h 7.1.1.4 Coefficient of Performance, COP, W/W 7.2 Tolerances. To comply with this standard, measured test results shall not be less than 95% of Published Ratings for performance ratios and capacities. 5

Section 8. Operating Requirements 8.1 Operating Requirements. To comply with this standard, Direct Geoexchange Heat Pumps shall be designed and produced in such a manner that any production units shall meet the operating requirements of ANSI/ASHRAE Standard 194. This shall include an insulation effectiveness test, a low-temperature start and operating test, and maximum operating test. Section 9. Marking and Nameplate Data 9.1 Nameplate Data. As a minimum, the nameplate shall display the manufacturer's name, model designation and electrical characteristics. Nameplate voltages for 60 Hertz systems shall include one or more of the equipment nameplate voltages shown in Table 1 of AHRI Standard 110. Nameplate voltages for 50 Hertz systems shall include one or more of the utilization voltages shown in Table 1 of IEC Standard 60038. Section 10. Conformance Conditions 10.1 Conformance. While conformance with this standard is voluntary, conformance shall not be claimed or implied for products or equipment within the standard's Purpose (Section 1) and Scope (Section 2) unless such product claims meet all of the requirements of the standard and all of the testing and rating requirements are measured and reported in complete compliance with the standard. Any product that has not met all the requirements of the standard cannot reference, state, or acknowledge the standard in any written, oral, or electronic communication. 6

APPENDIX A. REFERENCES NORMATIVE A1 Listed here are all standards, handbooks and other publications essential to the formation and implementation of the standard. All references in this appendix are considered as part of the standard. A1.1 ANSI/AHRI Standard 110-2016, Air-Conditioning, Heating, and Refrigerating Equipment Nameplate Voltages, 2012, Air-Conditioning Heating and Refrigeration Institute, 2111 Wilson Blvd., Suite 500, Arlington, VA 22201, U.S.A. A1.2 ANSI/ASHRAE Standard 194-2012, Method of Test for Direct-expansion Ground Source Heat Pumps,2012. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A. A1.3 AHRI Standard 871(SI)-2016, Performance Rating of Direct Geoexchange Heat Pumps, 2015, Air- Conditioning Heating and Refrigeration Institute, 2111 Wilson Blvd., Suite 500, Arlington, VA 22201, U.S.A. A1.4 ANSI/AHRI/ASHRAE ISO Standard 13256-1:2012, Water-source heat pumps-testing and rating for performance- Part I: Water-to-air and brine-to-air heat pumps, 2012. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tillie Circle, N.E., Atlanta, GA 30329, U.S.A. A1.5 ANSI/AHRI/ASHRAE ISO Standard 13256-2:2012, Water-source heat pumps-testing and rating for performance- Part II: Water-to-water and brine-to-water heat pumps, 2012. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tillie Circle, N.E., Atlanta, GA 30329, U.S.A. A1.6 ASHRAE, Terminology, https://www.ashrae.org/resources--publications/free-resources/ashrae-terminology, 2016, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A. A1.7 IEC Standard 60038-2009, IEC Standard Voltages, 2009, International Electrotechnical Commission, 3, rue de Varembe, P.O. Box 131, 1211 Geneva 20, Switzerland. APPENDIX B. REFERENCES INFORMATIVE B1 Listed here are standards, handbooks and other publications which may provide useful information and background but are not considered essential, References in this appendix are not considered part of the standard. B1.1 ANSI/AHRI Standard 210/240-2008 with Addenda 1 and 2, Unitary Air-Conditioning and Air- Source Heat Pump Equipment, Air-Conditioning, Heating, and Refrigeration Institute, 2008, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201, U.S.A. B1.2 ANSI/ASHRAE Standard 34-2013 with addenda, Number Designation and Safety Classification of Refrigerants, 2015, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, GA 30329, U.S.A. 7