GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

Similar documents
GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

MGC Dock User s Manual

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

OI-2400-DOCK Multi Gas Docking Station. Operation Manual trevision 2.2w

MGC Dock User s Manual

Single Gas Clip and SGC Plus User s Manual Rev 2.1 READ FIRST BEFORE OPERATION WARNING STATEMENTS / AVERTISSEMENT Activating tthe detector for the

RK Carbon Monoxide Transmitter Operator s Manual

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

Single Gas Clip and SGC Plus User s Manual Rev 2.3

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

Macurco Single-Gas XL Series Monitor, CM-1XL Carbon Monoxide (CO), HS-1XL Hydrogen Sulfide (H2S) User Instructions

RK-05 Carbon Monoxide Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

RK-02 Multi Point Detector Operator s Manual

RK/ RK Oxygen Detector Operator s Manual

QUICK REFERENCE GUIDE

RK CO 2 Transmitter Operator s Manual

! "! # Please read these installation and operating instructions completely and carefully before starting.

RK Multi Point Detector Operator s Manual

RK Combustible Gas Transmitter Operator s Manual

GasAlertMicro 5. 1, 2, 3, 4, and 5 Gas Detectors. Quick Reference Guide

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

NH 3 RESPONDER Portable Ammonia Leak Detector QUICK REFERENCE GUIDE

Beacon 800 Gas Monitor Operator s Manual

RK/ RK Oxygen Detector Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

RK-05 Carbon Monoxide Detector Operator s Manual

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

RK/ RK Carbon Monoxide Detector Operator s Manual

CMF, CMX & CMA series

Controllers. Instruction Manual WARNING

Remote Relay Module (RRM)

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

RK Transmitter Technical Notice

NH3 RESPONDER PORTABLE AMMONIA LEAK DETECTOR. Quick Reference Guide

RK / RK Methane Detector Operator s Manual

Instruction Manual WARNING

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Single Gas Detector. Quick Reference Guide

RK-03 Hydrogen Detector Operator s Manual

Document No

ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

RK/ RK Combustible Gas Detector Operator s Manual

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

Operator s Manual. 1, 2, 3, and 4-Gas Detector

RK / RK CO 2 Detector Operator s Manual

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

Combustible Gas Sample-Draw Detector Operator s Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

GasAlertMicro 5 and GasAlertMicro 5 PID O 2, CO, H 2 S, PH 3, SO 2, Cl 2, NH 3, NO 2, HCN, ClO 2, O 3, VOC, and Combustibles

User s Manual and Warranty Information for Counterweighted Chain Drive ThyssenKrupp Access

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

VX SERIES Wireless Thermostat with Occupancy Sensor

Spa Control System OWNER S MANUAL

Operator s Manual. 1, 2, 3, and 4-Gas Detector

Macurco HD-11 Hydrogen Gas Detector

Blade Series Heat Exchanger Operation and Installation

LV-S-5. Instruction Manual DIRECT CONTACT STRAY VOLTAGE DETECTOR GENERAL DESCRIPTION HOW IT WORKS

Installation and Operations Manual

DGS - Danfoss Gas Sensor Check / Calibration Procedure

AT-G-DETECT Gas Sensing System

Beacon 110 Gas Monitor Operator s Manual

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Carbon Monoxide Sample-Draw Detector Operator s Manual

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

ST-IAM Sensor Transmitter Integrated Area Monitor. Check / Calibration Procedure* 10 ASH (1)

Safe T Net 210. Instruction Manual Part Number Mar2010

Design Criteria. Installation

USE AND CARE GUIDE FOR MODEL MEK1, MEK15. Express Cordless Kettle

Humidity Monitor model 01080

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

SEC 2000 Millenium Infrared Gas Detector

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

MaxLite LED MICRO-T PANEL

Transcription:

GG-NH3 AMMONIA GAS SENSOR Installation and Operation Manual

2 GG-NH3 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration Technologies, the protection provided by the equipment may be impaired. This equipment should be installed by qualified personnel.

GG-NH3 3 Table of Contents General Description...4 Installation.... 4-6 Locating the Sensor...4 Installation Guidelines...5 Wiring....6 Operation....7 Start-Up....7 Calibration....7 Maintenance...9 Specifications....10 Warranty....11 For technical support, contact: Calibration Technologies 920 N Trade Winds Pkwy Columbia, MO 65201 866-394-5861 Sales@ctiengineering.com www.ctiengineering.com

4 GG-NH3 General Description The GG-NH3 sensor is a +24 VDC, three-wire, 4/20 ma sensor for ammonia which utilizes proven electrochemcial sensor technology for fast and accurate leak detection. The standard detection range of the GG- NH3 sensor provides real-time continuous monitoring of ammonia concentrations accurately down to 5 ppm without false alarms. CTI typically recommends a 0/100 ppm range for all personnel and product protection areas. Higher ranges (0/250, 0/500, 0/1000) are optional for higher alarm setpoint areas such as Engine Rooms. The GG-NH3 sensor provides an industrial standard linear 4/20 ma output signal compatible with most gas detection systems and PLCs. The output signal is not affected by drastic temperature and moisture variations that occur during washdown, defrost cycles, etc. The transmitter circuit board is sealed in potting compound, protecting sensitive electronic components and copper tracing from corrosion. The specially vented chemical-resistant polycarbonate (or optional stainless steel) enclosure protects the sensor from accidental damage, weather, and direct hose hits from clean-up crews. Installation Locating the sensor One of the most important considerations when installing the GG-NH3 sensor is that it must be easily accessible for calibration and maintenance. For optimum personnel protection (representative concentration reading that an employee would be exposed to), mount the sensor at a height in the breathing zone of the employees. It would typically be about five feet off the ground, which also allows easy access. As a general rule of thumb, try to mount sensors within 30 feet of potential leak sources. Caution: Remove protective label The GG-NH3 sensor is shipped with a yellow label installed over the gas diffusion port of the electrochemical cell to preserve cell life. The cell will not detect ammonia vapors with this label installed. Remove label and discard during installation.

GG-NH3 Installation Guidelines: Remove and discard protective cell label. Always mount sensor vertically. Locate sensor to be easily accessible for calibration and maintenance. Mount sensor close to potential leak source. Mount sensor in "breathing zone" (4'-5' above floor) for optimum personnel protection. Take air movement and ventilation patterns into account. Keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters to prevent electrical interference. Protect sensor from physical damage (forklifts, etc). Mounting screws should be screwed into studs when mounting on a wall with studs. Never mount the sensor in CA (controlled atmosphere) rooms. Normal atmospheric levels of oxygen are required for operation. More than one sensor should be installed in each room for highly critical locations. Mount sensor enclosure through the mounting holes as shown in Figure 1. 7.75" 6.5" 2.0" Figure 1: Mounting Dimensions 5 6.8"

6 GG-NH3 Wiring Electrical wiring must comply with all applicable codes. Electrical Power: 24 VDC regulated, 350 ma. Output: Linear 4/20 ma output. Monitoring equipment may have a maximum input impedance of 700 ohms. Cable Recommendation: 20/3 shielded cable (General Cable C2525A or equivalent). Length of cable to sensor should be no greater than 1,500 feet. Monitoring: Monitoring equipment must be configured to indicate a fault if the signal is below 1 ma. All signals over 20 ma must be considered high gas concentrations. Alarm setpoints should not be lower than 10% of full-scale range. Wiring Guidelines: Always use 3-conductor, insulated, stranded, shielded copper cable. Do not pull sensor wiring with AC power cables. This can cause electrical interference. If cable runs cannot be made without a splice, all splice connections should be soldered. Ground the shield at the main control panel. Connect the shield wire in the sensor terminal block labeled SHLD. Always disconnect power at the controller before performing any wiring at the sensor. To maintain NEMA/IP rating of the enclosure, conduit fittings of the same rating or better must be used. To case (earth) ground of monitoring equipment To ground terminal of power supply To +24V terminal of power supply To signal input of monitoring equipment Terminal Block Plug (Field Wiring): SHLD: To case (earth) ground of monitoring equipment GND: To ground terminal of power supply +24V: To +24V terminal of power supply SIG: To signal input of monitoring equipment

GG-NH3 Operation Start-Up Sensor can be response tested and/or span calibrated immediately after power up. Allow 60 seconds for power up time delay of sensor to end (green power LED will flash during power up). Start-Up test: 1) One person exposes each sensor to calibration gas. 2) The second person stays at the control panel to determine that each sensor, when exposed to the gas, is connected to the proper input and responds, causing appropriate alarm functions. LED Functions (see Figure 2 on page 8) Calibration The GG-NH3 sensor comes factory calibrated and should require only minimal adjustment after installation. There are two pots on the preamp that are used for calibration (see Figure 2). Note: Never measure sensor output in ma. Always use mvdc or VDC voltmeter settings. Zero Calibration: After the sensor is installed and has been powered up for a minimum of 8 hours, the unit can be zero calibrated by the following: Be sure the unit is in clean air. Adjust the zero pot until the sensor outputs 40 mv from Test [-] to Test [+] (see Figure 2).Note: To zero the sensor immediately after power up or cell replacement, unplug cell from the transmitter and adjust signal to 40 mv. Span Calibration: DO NOT ADJUST THE SPAN POT WITHOUT CERTIFIED CALIBRATION GAS! If span adjustment is required, use the following procedure: To enter calibration mode (disables all filtering and averaging), turn the Zero pot clockwise 1/4 turn and then back again. Successful entry into calibration mode will be indicated by the Power (green) LED blinking twice per second. Calibration mode will time out automatically after 10 minutes. Apply span gas at 0.5 to 0.8 L/min (span gas must be in air, not nitrogen or other carrier). Sensor should react to gas within 15 seconds. Once the output signal has peaked (or 2 minutes maximum) adjust the Span pot until the correct output is achieved (see Figure 2). With full-scale span gas, the calculated span value is 200 mv. ((span gas / sensor range * 16 + 4) (ma output)) Note: Below are a few response characteristics which may be an indication that the gas sensor is at or near the end of its useful life. If any of these characteristics are observed, the cell should be replaced. Slow response to / recovery from calibration gas. Failure of the output to reach 50% of the calibration gas value prior to span adjustment. Unable to achieve correct output during span. 7

8 GG-NH3 Cell Sensor Cable plugs into socket here Span adjustment Zero adjustment 40-200 mv mvdc Black Red - + Fault (red) LED: On steady if supply voltage is less than 10VDC. Status (amber) LED: Blinks once per second if RFI is detected. Power (green) LED: On steady to Indicate Power. Blinks once per second for 60 seconds during power-up. Blinks once per second continuously if supply voltage is too low. Blinks twice per second in calibration mode (4 minute timeout delay). Figure 2: Sensor board components and zero/span adjustment

GG-NH3 Maintenance The GG-NH3 sensor is designed for long life and minimal maintenance. For proper operation, it is essential that the test and calibration schedule be adhered to. Calibration Technologies recommends the following maintenance schedule: Maintenance Guidelines: The sensor is shipped with a factory calibration. Sensor should be calibrated 6 months from purchase date. Calibrate the detector at least once every 6 months. Calibration should be performed with certified calibration gas. Calibration kits and replacement cylinders are available from Calibration Technologies. All tests and calibrations must be logged. Always disconnect power at the controller before performing any wiring at the sensor. Sensor Life: The electrochemical cells are extremely reliable, but several things can cause depletion of the chemistry within the cell including: A period of time Exposure to high temperatures Continuous, long term exposure to ammonia When the cell becomes depleted, the unit will give no indication of failure other than the sensor will not respond. For this reason, it is absolutely essential that the sensor be calibrated on a regular basis. Typical cell life is 2 to 5 years. When the cell becomes depleted, a replacement cell can be optained from Calibration Technologies. Simply unplug the cell's ribbon cable from the transmitter, pull the old cell from the spring clip, discard the old cell and replace with a new one. The new cell can be span-calibrated immediately. However, an 8 hour warm-up period is required before zeroing, if necessary. 9

10 GG-NH3 Specifications Input Power: +24 VDC, 350 ma Detection Principle: Electrochemical Detection Method: Diffusion Gases: Ammonia (NH3) Ranges: 0/100 (standard) 0/250 0/300 0/500 0/1000 Custom ranges available. Call for more information Output Signal: Linear 4/20 ma (max input impedance: 700 Ohms) Response Time: T50 = less than 30 seconds T90 = less than 60 seconds Accuracy: +/- 5% of full-scale, but dependent on calibration gas accuracy and time since last calibration Zero Drift: Less than 0.1% of full-scale per month, non-cumulative Span Drift: Application dependent, but generally less than 3% per month Linearity: +/- 0.5% of full-scale Repeatability: +/- 1% of full scale Power (green) LED: Blinks once per second for 60 seconds during power-up. If supply voltage is too low (<10 VDC) or improperly grounded, green LED will blink once per second continuously. Stays steady on to indicate power. Blinks twice per second in calibration mode (4-minute timeout delay) Status (amber) LED: Blinks once per second if RFI (radio frequency interference) is detected Fault (red) LED: Stays on steady if supply voltage is too low (<10 VDC) Wiring Connections: 3-conductor, shielded, stranded, 20 AWG cable (General Cable C2525A or equivalent) up to 1500 ft Terminal Block Plug (Field Wiring): 26-12 AWG, torque 4.5 lbs-in Enclosure: Injection-molded, washdown-duty, polycarbonate sensor housing with hinged lid and captive screw. For non-classified areas. Optional 18 GA, NEMA 3RX washdown-duty stainless steel enclosure with hinged lid and captive screw. For nonclassified areas Temperature Range: -50 F to +122 F (-46 C to +50 C) Humidity Range: 5% to 100% condensing Dimensions: 7.7" high x 6.7: wide x 3.8" deep Weight: 3.0 lbs Certification: ETL Listed: Conforms to UL 61010-1 Certified to CSA C22.2 No. 61010-1

GG-NH3 11 Limited Warranty & Limitation of Liability Calibration Technologies, Inc. (CTI) warrants this product to be free from defects in material and workmanship under normal use and service for a period of two years (including the sensor element), beginning on the date of shipment to the buyer. This warranty extends only to the sale of new and unused products to the original buyer. CTI's warranty obligation is limited, at CTI's option, to refund of the purchase price, repair, or replacement of a defective product that is returned to a CTI authorized service center within the warranty period. In no event shall CTI's liability hereunder exceed the purchase price actually paid by the buyer for the product. This warranty does not include: a) routine replacement of parts due to the normal wear and tear of the product arising from use; b) any product which in CTI's opinion, has been misused, altered, neglected or damaged by accident or abnormal conditions of operation, handling or use; c) any damage or defects attributable to repair of the product by and person other than an authorized dealer or contractor, or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on: a) proper storage, installation, calibration, use, maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI; b) the buyer promptly notifying CTI of any defect and, if required, promptly making the product available for correction. No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI; and c) the right of CTI to require that the buyer provide proof of purchase such as the original invoice, bill of sale or packing slip to establish that the product is within the warranty period. THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER'S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CTI SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTRACT, TORT OR RELIANCE OR ANY OTHER THEORY.

ctiengineering.com 866-394-5861 GG-NH3-DOC1-2 20171204