System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Similar documents
System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Location Requirements

System 350 W351P Electronic Proportional Plus Integral Humidity Control

Surface-Mounted NS Series Network Sensors without LCD

Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD

CD-Px Series Duct Mount CO 2 Transmitters

TEC3000 Series Stand-Alone and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

MR3CCUHV Temperature/Defrost Control

W43A Humidistat. Features and Benefits

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

WRS-TTx Series Wireless Room Temperature Sensors

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

A99B Series Temperature Sensors

T600HCx-3 Single-Stage Thermostats

TEC2100 Series Networked Thermostats

A19, A28 Series Thermostats for Agricultural Buildings

TEC210x-2 Series Networked Thermostats

CP CP

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

TEC1100 Series Thermostats

VENTURI NOZZLE SYSYTEM Specification Sheets ALL STAINLESS STEEL COMPRESSED AIR NOZZLE HUMIDIFIERS. With ON/OFF or Proportional Controls

F261 Series Fluid Flow Switches

P266 Series Single-Phase Condenser Fan Speed Control

T500 Series Non-Programmable Thermostats

ACT2-CS Convenience Store Controller

Installation Instructions

AB Parts. ControlNet Coax Tap. Installation Instructions. (Cat. Nos TPR, -TPS, -TPYR, -TPYS) What s in This Document

Powers TM Controls ET 134 Line Voltage Room Thermostats

Technical Instructions Document No P25 ET September 28, ET 141 Electric Surface Mounted Thermostat.

TM-3100 Series Room Temperature Sensor

FS80-C Flow Switch. Features and Benefits. Allows user select the setting according the needs of system

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

ELECTRONIC HUMIDISTAT: H200

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC)

TEC3000 Series Proportional Fan Coil and Zoning Thermostat Controllers with Dehumidification Capability

TRUERH Series HE-67xx Humidity Element with Temperature Sensor

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats

Schneider Electric Erie T155 Series

Installation Instructions If you have questions, call 800-GE-CARES or visit our website at:

Power Supply Display Module PSDM. Installation and Operation Manual

ET10 Series Stand-alone LCD Fan Coil Thermostat

ELECTRONIC HUMIDISTAT: H270

T7079A,B Solid State Remote Temperature Controllers

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Fan Coil Relay Packs

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

Occupancy Sensor OCS 100W Setup Guide

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC)

Powers Controls Low Temperature Detection Thermostat

YP7899C SERIES Burner Management Panel

Installation Instructions

CR Series Command Relays

Powers Controls ET 134 Low Temperature Detection Thermostat

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

SAFETY INFORMATION AND WARNINGS

CR7075 Two-Stage Lighting Controller

INSTALLATION GUIDE AND OWNER S MANUAL. AccuMix II ELECTRIC INSTANTANEOUS WATER HEATER WITH ASSE 1070 APPROVED MIXING VALVE

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Series P215LR/BR Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter)

T125-E. Electric Fan Coil Thermostat. Product Bulletin. Operation. Appearance. Installation, Service and Maintenance

Series A28 Two stage Thermostats. Feature and Benefits

PEDESTAL INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION DU PIÉDESTAL

Product ID. General. TE CONNECTIVITY SENSORS /// EXxxHyy Ex-Atex & NA 09/2017 Page 1

Modus Model DA General Eastern Low Differential Pressure Alarm Controller

T4398A,B Precision Electric Heating Thermostat

GARAGE DOOR OPENER KIT

INSTALLATION INSTRUCTIONS

Compact I/O End Caps/Terminators

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

Smoke Control Listed LCM-OAVS VAV with HW Reheat, Two Venturi Air Valves (One Exhaust, One Supply) including BTU Compensation

Stopper Station Series Push Button Models SS2xx2, SS2xx5, SS2xx9

INSTALLATION GUIDE AND OWNER S MANUAL

TC-5231 Series, TC-5232, & TC-5241 Series

INSTRUCTION MANUAL MM-615E. Series FS1 High Sensitivity Liquid Flow Switch

MBCE-110/230UV Flame Sensor Module

Stopper Station Series SS-2008 Push Button Pneumatic Timer Button

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

INSTALLATION & USER MANUAL

POINT I/O Field Potential Distributor Module

Automatic Humidity Controller. Model 512 (Revision C) Operating Manual

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

NS Series Network Sensors

Technical Manual for the Strobe - SM87 HXB

Certificate of Compliance

A11 Series Low Temperature Cutout Controls

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

Model 4001 Series Single Channel Controller

Tetra MAX. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

Installation Instructions

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

RLD-H10P Refrigerant Leak Detector

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

Stopper II Heated Enclosure

JDDT1 - Single Stage Digital Thermostat

Wireless Outdoor Air Reset Adaptor PN:

! WARNING. Before using product, read and understand instructions.

Transcription:

FANs 930, 125 Product/Technical Bulletin S350 Issue Date April 8, 2014 System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage s The S350A, S351A, and S352A Stage s are intended to be used with System 350 controls. Each of these stage modules plugs into the respective control module to add multiple-stage capability. These stage modules have Single-Pole, Double-Throw (SPDT) relay output with Light-Emitting Diode (LED) indication. As are all System 350 products, the stage modules are housed in NEMA 1, high-impact thermoplastic enclosures. The modular design provides easy, plug-together connections for quick installation and future expandability. Figure 1: System 350 Stage Features and Benefits Modular Design Plug-together s and 35 mm DIN Rail Mounting Selectable Mode of Operation Adjustable Adjustable Offset Permits system to be configured to equipment, with convenient, future expansion made easy Eliminates wiring between modules and reduces installation costs Provides independent relay energization, either above or below setpoint, for cooling/heating (S350A), dehumidification/humidification (S351A), or direct acting/reverse acting (S352A) Enables user to match the range of temperature, humidity, or pressure stage modules to specific application requirements Allows multiple stage sequencing of 1-30F (0.5-17C ) (S350A), 2-30% RH (S351A), or 2-50 psi (S352AA-2) 2014 Johnson Controls, Inc. 1 Part No. 24-7664-1, Rev. E www.johnsoncontrols.com Code No. LIT-930080

A pplication The S350A, S351A, and S352A Stage s receive power, setpoint, and sensor input from the respective System 350 control modules. When connected, the individual modules act as a multistage control system. The maximum number of stages that can be used in a system varies with the control module type (temperature, humidity, or pressure) and stage module design. Refer to Table 1 or Table 2 to determine the maximum number of stages that may be used with each control module. When mixing stage module designs, always use the lower number. Note: When using an external transformer, the Y65 Series or other 40 VA Class 2 transformers are recommended. Table 1: Maximum Number of Add-on s when Powered by a Y350R Power Control A350A A350B A350E No. 9 6 4 A350P 4 2 A350R A350S 9 6 4 Stage Model Numbers with 2 S350Ps with 2 S350Ps Display No. Model Number 1 D350 1 D350 2 D350s W351A 5 S351As 1 D351 W351P 4 S351As 1 D351 P352AB 5 S352As 1 D352A P352PN 4 S352As 1 D352A Table 2: Maximum Number of Add-on s when Powered by an External Transformer Control A350A A350B A350E No. 9 8 7 A350P 9 8 A350R A350S 7 9 8 7 Stage Model Numbers with 2 S350Ps with 2 S350Ps with 2 S350Ps Display No. Model Number 1 D350 1 D350 2 D350s W351A 9 S351As 1 D351 W351P 9 S351As 1 D351 P352AB 9 S352As 1 D352A P352PN 9 S352As 1 D352A Notes: This bulletin only refers to the S350A, S351A, and S352A Stage s. For information on the S350C refer to the System 350 TM S350C Temperature Slave Stage Product/Technical Bulletin (LIT-930084). For information on the S350P refer to the System 350 TM S350P Proportional Plus Integral Temperature Stage Product/Technical Bulletin (LIT-930086). For information on the D350, D351 and D352 refer to the System 350 TM D350 Display s Product/Technical Bulletin (LIT-930070). 2 S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin

O peration The S350A, S351A, and S352A Stage s provide SPDT relay output. A front panel LED lights to indicate when the relay is energized. IMPORTANT: Use the S350A, S351A, and S352A Stage s only as an operating control. Where failure or malfunction of the modules could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the modules. IMPORTANT: Utiliser ce S350A, S351A, and S352A Stage s uniquement en tant que dispositif de contrôle de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du modules risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du modules. Offset Adjustment The offset adjustment determines the amount of offset from the control module setpoint at which the stage module relay de-energizes. Operation Mode Selection The S350A, S351A, and S352A utilize jumpers (at jumper terminal J2) to select the operation mode. (See Adjustments section and Figures 3, 4, and 5.) With the jumpers positioned horizontally, the stage module is set for Cooling (S350A), Dehumidification (S351A), or Direct Acting (DA) (S352A) operation. In this mode the relay and LED indicator de-energize when the sensed temperature, humidity, or pressure drops to the setpoint plus offset value. Note: The S350A, S351A, and S352A Stage s are configured with the jumpers in the horizontal position at the factory. Refer to Figures 6, 7, and 8 for examples of S350A, S351A, and S352A applications. D imensions Mounting Slots For No. 6 Screws 1-1/2 (40) 1/8 (4) 2-15/16 (75) 7/16 (11) DIN Rail Mount 5 (127) 2-3/8 (61) 1-3/16 (31) S350 JOHNS CTROLS O 2-3/8 (61) 7/8 (22) Conduit Hole 7/8 (22) Figure 2: System 350 Stage Dimensions, in. (mm) Adjustment is defined as the difference in degrees, % RH, or psi between energization and de-energization of the stage module s relay. S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin 3

Mounting Each System 350 Stage is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting. Four key-slot mounting holes on the back of the control case are provided for surface mounting. (See Figure 2.) The modules are not position sensitive, but should be mounted for convenient access to wiring and adjustments. Note: When mounting any System 350 module to rigid conduit, attach the hub to the conduit before securing the hub to the control enclosure. Adjustments Refer to the following steps for adjusting stage module settings. (See Figures 3, 4, and 5.)! WARNING: Risk of Electrical Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. AVERTISSEMENT: Risque de décharge électrique. Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles. 3. Set the mode of operation by positioning the jumpers (at jumper terminal J2) for Cooling, Dehumidification, or Direct Acting mode. Position the jumpers vertically for Heating, Humidification, or Reverse Acting mode. Note: The S350A, S351A, and S352A Stage s are configured with the jumpers in the horizontal position at the factory. 4. Adjust the differential using the potentiometer marked DIFF to the desired setting (the difference in degrees, % RH, or psi between energization and de-energization of the stage module s relay). 5. Adjust the offset using the potentiometer marked SET to the number of degrees, % RH, or psi from the System 350 control s setpoint at which the stage relay de-energizes (above setpoint with Cooling, Dehumidification, or Direct Acting mode selected, or below setpoint with Heating, Humidification, or Reverse Acting mode selected). 6. Replace the cover on the stage module and fasten in place with screws. 7. Restore power to system. Energized LED Indicator Offset Cover Screw 1 of 4 N.C. Output Terminals Jumper Position at J2 Heating Cooling Figure 3: Interior View of S350A Stage 1. Ensure all power to system is off. Each stage module may be receiving separate power sources. Make sure all power sources to each stage module are off. 2. Remove the stage module cover by loosening the four captive cover screws. 4 S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin

Offset Energized LED Indicator Cover Screw 1 of 4 Jumper Position at J2 Humidification Dehumidification Offset Energized LED Indicator Cover Screw 1 of 4 Jumper Position at J2 Reverse Acting Direct Acting N.C. Output Terminals Figure 4: Interior View of S351A Stage N.C. Output Terminals Figure 5: Interior View of S352A Stage S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin 5

Higher Temperature Setpoint Temperature Lower Temperature SET SET = Energized = De-energized SET A350 S350A Stage 1 Stage 2 Cooling SET S350A Stage 3 S350A S350A Stage 4 Stage 5 Heating Higher Pressure Setpoint Pressure Lower Pressure P352AB Stage 1 Direct S352A Stage 2 SET = Energized = De-energized SET S352A Stage 3 Reverse S352A Stage 4 SET Figure 6: Example of a Heating/Cooling Application Using One A350 and Four S350As Higher Humidity Setpoint Relative Humidity Lower Humidity W351 Stage 1 S351 Stage 2 Dehumidify = Energized = De-energized SET SET S351 S351 Stage 3 Stage 4 Humidify SET Figure 7: Example of a Humidification/Dehumidification Application Using One W351 and Three S351As Figure 8: Example of a Reverse Acting/Direct Acting Application Using One P352AB and Three S352As W iring Refer to the following guidelines and wiring diagrams for proper wiring and terminal designations (See Figures 9, 10, and 11.) Note: For information on connecting to an external transformer refer to the applicable control bulletin.! WARNING: Risk of Electrical Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. AVERTISSEMENT: Risque de décharge électrique. Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles. 6 S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin

IMPORTANT: Make all wiring connections in accordance with the National Electrical Code and all local regulations. Use copper conductors only. Do not exceed the control s electrical ratings. The stage modules plug into the control and other add-on modules via 5-pin connectors located on either side of each module. Wiring is made at the Normally Open ()/Normally Closed (N.C.) relay terminal strip. (See Figures 3, 4, and 5.) Shield (Connect only to on A350) A350 Sensor Isolate and tape. (Do not ground this end of cable shield.) Y350R S350A S350A S350A D350 Wire Terminal Block 24V VDC 120 VAC Load Load Load Load Figure 9: Typical Multistage Temperature Control System Using 120 VAC Power Supply Transmitter VDC Shield (Connect only to on W351) Isolate and tape. (Do not ground this end of cable shield.) W351 Y350R S351A S351A S351A D351 Wire Terminal Block 24V VDC 120 VAC Load Load Load Load Figure 10: Typical Multistage Humidity Control System Using 120 VAC Power Supply S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin 7

Wiring Harness P399 Transducer VDC Shield (Connect Isolate and tape. (Do not ground only to on P352AB) this end of cable shield.) P352AB Y350R S352A S352A S352A D352A Wire Terminal Block 24V VDC 120 VAC Load Load Load Load Figure 11: Typical Multistage Pressure Control System Using 120 VAC Power Supply 8 S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin

Checkout Procedure Before applying power, make sure installation and wiring connections are according to job specifications. After necessary adjustments and electrical connections have been made, put the system in operation and observe at least three complete operating cycles before leaving the installation. T roubleshooting If the control system does not function properly, first verify that the control, power, and display modules are all operating correctly (refer to the respective literature). Then inspect the stage modules for proper operation. Check that the proper operating mode (Cooling/Heating, Dehumidification/Humidification, or Direct Acting/Reverse Acting) has been selected on each stage module. (See Adjustments section and Figures 3, 4, and 5.) Then perform the following procedures to determine the problem. 1. Verify the system has power. 2. Note the offset and differential settings on the stage module. 3. Turn the setpoint dial on the control module to minimum. 4. Increase the setpoint by slowly adjusting the setpoint dial until the stage relay LEDs turn On and Off as shown in Tables 3, 4, or 5. Table 3: S350A Troubleshooting Operation Mode LED Status Setpoint Dial Setting Cooling On Closed (Ts)* - offset - differential Cooling Off Open (Ts) offset Heating On Closed (Ts) + offset + differential Heating Off Open (Ts) + offset *(T s ) = sensed temperature Table 4: S351A Troubleshooting Operation Mode LED Status Setpoint Dial Setting Dehumidify On Closed (RH T )* -offset - differential Dehumidify Off Open (RH T ) - offset Humidify On Closed (RH T ) + offset + differential Humidify Off Open (RH T ) + offset *(RH T ) = actual relative humidity at transducer Table 5: S352A Troubleshooting Operation Mode LED Status Setpoint Dial Setting Direct On Closed (psi T )*- offset - differential Direct Off Open (psi T ) - offset Reverse On Closed (psi T ) + offset + differential Reverse Off Open (psi T ) + offset *(psi T ) = actual pressure at transducer 5. If the relays do not perform as indicated in Tables 3, 4, or 5, adjust the stage module s differential and offset potentiometers to minimum and repeat Steps 1 through 3. 6. If the relays still do not turn on and off, replace the defective stage modules. Note: There is the unlikely possibility that a defect in one stage module could cause defective symptoms in all modules. Plug each stage into the control individually and check the performance of each as explained above. Repairs and Replacement Do not make field repairs or perform calibration. Sensors and replacement controls are available through your local Johnson Controls representative. S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin 9

Ordering Information Table 6: Ordering Information Item S350A Temperature Stage Product Code Number S350AA-1C S350AB-1C Description Temperature Stage with Fahrenheit Scale Temperature Stage with Celsius Scale S351A Humidity Stage S351AA-1C Humidity Stage with percent RH Scale S352A Pressure Stage S352AA-2C Pressure Stage with psi Scale S pecifications Product S350AA: Temperature Stage with Fahrenheit Scale S350AB: S351AA: S352AA-2: Temperature Stage with Celsius Scale Humidity Stage with Percent RH Scale Pressure Stage with psi Scale Input Voltage S350AA: Provided by the A350 S351AB: Provided by the W351 S352AA-2: Provided by the P352AB Power Consumption Output Electrical Ratings Adjustment Range 1.0 VA maximum SPDT Enclosed s 10 Ampere Non-inductive, 125 VA Pilot Duty, 24/240 VAC 1/2 hp 120/240 VAC S350AA: 1 to 30F S350AB: 0.5 to 17C S351AA: 2 to 10% RH S352AA-2: 2 to 50 psi Offset Range S350AA: 1 to 30F S350AB: 0.6 to 16.7C S351AA: 2 to 30% RH S352AA-2: 2 to 50 psi Ambient Temperature Operating: -30 to 150 F (-34 to 66 C) Shipping: -40 to 185 F (-40 to 85 C) Ambient Humidity Material Mounting 0 to 95% RH (Non-condensing) Case, Cover: NEMA 1 High Impact Thermoplastic Wall or DIN Rail Agency Listing UL Listed, CCN XAPX, File E27734 UL Listed for Canada, CCN XAPX7, File E27734 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls/Penn Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. Copyright 2014 by Johnson Controls, Inc. All rights reserved. 10 S350A Temperature, S351A Humidity, and S352A Pressure Stage s Product/Technical Bulletin