MCR9705 Smoke and Heat Exhaust Control Unit

Similar documents
mcr PROLIGHT, mcr PROLIGHT PLUS

TECHNICAL MANUAL. Power and Control Panel mcr OMEGA

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

OPERATION AND MAINTENANCE MANUAL

FEC400 Series. Installation Manual

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Control box FSTronic DES-FS

CONTROL DEVICE SLIDETRONIC HD

Fire Control Panel FS4000

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

BSR Addressable Fire Detection control panel. Installation operation manual

Door Release Power Supply

AL800ULADA. NAC Power Extender. Installation Guide

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

Fire Control Panel FS4000

FEC403EN Installation Manual

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

DHR3. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer. INSTALLATION INSTRUCTIONS

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

OPERATIONAL AND MAINTENANCE MANUAL. Overpressure smoke control system for vertical exit paths mcr EXi

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

DH400. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer.

Instructions for the fan motor control system, SILVER C

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Monitoring Devices 11/1

AL600ULADA. NAC Power Extender. Installation Guide

SP-4004 OPTICAL-ACOUSTIC OUTDOOR SIREN sp4004_en 03/13

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Installation and Operation Instructions

AXIAL FAN User s manual. Quiet-dMEV 100 DC.

Public Safety DAS Annunciator Panel

Installation, Operating and Maintenance Manual

ELECTRONIC PARTS - CATALOGUE

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Control box FSTronic DES-FI

WARNING FIRE DOOR CLOSING

Beacon 410A Gas Monitor Operator s Manual

Smoke Vent Control Panel RZN 4202 V1

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Conventional Fire Alarm System 2014 V1.2

DUAL ZONE OUTDOOR PIR MS-12TE & MS-12FE

AXIAL FANS USER S MANUAL

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

NDC-F16. Access Control Panel. Installation Manual

2000 Series Sensors Installation Guide

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

4100U City and Relay Cards Installation Instructions

EKS EKS NI EKS NIS EKS NV EKS NV PH EKS NV PTC/PS

Instructions for the fan motor control system with integrated wiring terminals SILVER C

WSC 204 (WSC / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102)

RELEASE DEVICE CONTROLS

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

SCR100 User Manual. Version:1.1 Date:Dec 2009

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

Danfoss gas detection units

Model 4001 Series Single Channel Controller

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RMS/RPX Reader. User Manual

GAS SUPRESSION CONTROL PANEL:

Installation and Operating Instructions DÜRR Regeneration Unit for X-ray developers XR 24, XR24 II, XR 24 Nova, XR 24 Pro

External Wireless Sounder

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Installation and Programming manual INSTALLATION MANUAL E PROGRAMMING INSTALLAZIONE PROGRAMMAZIONE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

Operation and Maintenance Manual

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

INTELLIGENT AXIAL FAN user's manual

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

FX FIRE DETECTION SYSTEM

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

ESP TECHNOLOGIES LIMITED

SAFETY WARNINGS. Power cable to the alarm system. Automatic two-pole circuit breaker. Cable from power distribution board

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment

Simple Self-Diagnosis by Malfunction Code

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

EKA EKA NI EKA NIS EKA NV EKA NV PH EKA NV PTC/PS

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

Part 3 Troubleshooting

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Planning Instructions MEW01090 Revision 4

Fire Control Panel FS5100

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

A series of technical features make this gas detector extremely versatile, reliable, accurate, and safe.

Transcription:

MCR9705 Smoke and Heat Exhaust Control Unit Technical and Operating Documentation User Instruction Manual MERCOR SA Ul. Grzegorza z Sanoka 2 80-408 Gdańsk tel. (+48) 058 341 42 45, fax (+48) 058 341 39 85 Gdańsk, ver. 3.0-2008.07.09

Table of Contents USER INFORMATION... 2 INTRODUCTION... 3 ABOUT THE MCR9705 CONTROL UNIT... 4 MAINTENANCE... 8 ASSEMBLY AND START UP... 11 TECHNICAL SPECIFICATIONS.... 16 WARRANTY TERMS AND CONDITIONS.... 17 SERVICE... 18 Please keep this Instruction Manual inside the control unit, so that the information is always available when required. User information Thank you for selecting the MCR9705 control unit. Please, read these instructions carefully and follow the guidelines. This will ensure smooth and reliable operation of the device. MERCOR SA reserves the right to modify the product or the documentation without notice. We wish to ensure your full satisfaction with our products and we will be glad to provide You with professional service and assistance if necessary. MERCOR SA Page 2 of 18

Introduction The MCR9705 control unit is used in smoke exhaust systems to control the operation of: electrical actuators and in particular vent actuators in MCR-PROLIGHT and MCR-PROLIGHT+ product range, drive of automatic rolled curtains MCR KURTYNA, MCR PROSMOKE, electromagnetic door locks and in other MCR series products used for fire protection purposes, which require 24 V= power supply. The electrical MCR9705 unit should be installed near the smoke exhaust window or in the building supervision room. The unit is powered with 230 V AC voltage. The working DC voltage is 24 V on output terminals to which the devices of the electrical smoke exhaust control system are connected. The unit is equipped with batteries which ensure system operation for 72 hours after a power outage. After that time a single emergency opening of smoke vents is possible. The unit has the following features: automatic alarm release by a signal from a fire alarm control unit manual alarm release by alarm pushbuttons, automatic alarm release by smoke sensors, transmitting information about alarm (NO/NC signal), transmitting information about the defect of the system (NO/NC signal), transmitting information about vent opening (NO/NC signal), manual opening of a smoke vents for ventilation of the building during normal operation without activating the alarm status, automatic closing of smoke vents opened for ventilation, in case of rain or strong wind (when a weather monitoring unit with a wind-rain sensor is installed). The MCR9705 unit is equipped with an alarm buzzer and visual indicators of its operating status, which allows easy identification of the alarm s source or a system defect. Smoke exhaust vents which were opened in emergency mode can be closed (cancellation of the alarm state) providing that the cause of the alarm has been removed. If MCR9705 is equipped with manual pushbutton MCR RPO-1, remote operation and display of the unit s status is possible (defect and alarm signals, remote alarm reset and closing vents after the alarm). MCR9705 is performed in two series of type, which are based on modules : 5A and 8A, thanks to this it is possible to create complex systems [5A, 2x5A, 3x5A, 4x5A, 6x5A, 7x5A, 8x5A, 9x5A, 10x5A, 11x5A, 12x5A or 8A, 2x8A, 3x8A, 4x8A, 5x8A, 6x8A, 7x8A, 8x8A). Series of type 8A shall be used only for natural smoke and heat exhaust systems. Page 3 of 18

About the MCR9705 control unit 1 2 3 4 5 6 Fig. 1 Front panel of a control unit. On the front panel, there are LEDs which indicate the status of the control center: # Description Color Function 1 POWER SUPPLY green indicates that both power supplies are present 2 READY yellow indicates no alarm, system ready for operation 3 ALARM red optical emergency signal 4 FAULT yellow general system failure signal 5 VENT OPEN (DOOR CLOSED * ) yellow indicates that smoke vents are open or door closed* * doors closed (in remote door control systems). As a standard, the control center is equipped with a lock (6). Page 4 of 18

12 13 14 15 1 2 3 4 5 6 7 8 9 10 11 Fig. 2. Inside view of the control unit s door. On the inside of the control unit s door there s an alarm buzzer (16) and the optical indicator board. Optical indicators are used for the system diagnostics. Item Color Information 1 red alarm; source: sensor line 2 red alarm; source: pushbutton line 3 red alarm; source: external input terminal 4 yellow defect of the actuator line (line gap) 5 yellow defect of the sensor line (line gap) 6 yellow defect of the pushbutton line (line gap or short-circuit) 7 not installed 8 yellow disconnection of the actuator line (SW1-1) 9 yellow disconnection of the sensor line (SW1-2) 10 yellow disconnection of the pushbutton line (SW1-3) 11 yellow disconnection of the in/out connectors providing information about alarm and defect (SW1-4) 12 green power supply (same as on the front panel) 13 yellow ready (same as on the front panel) 14 yellow check testing the correct operation of signals 15 yellow Indication of open vent (same as on the front panel) Page 5 of 18

16 19 15 14 13 12 11 10 9 8 21 7 6 5 22 1 2 3 4 18 17 20 Fig. 3. Interior view of the control unit. There are three pushbuttons on the control s center casing: # Description Function 1 TEST optic and audio signalling check. 2 RESET alarm reset 3 CLOSE VENTS closing the vent Push down TEST button in order to check optical signals. Push down TEST and RESET buttons at he same time (or TEST and CLOSE VENTS) in order to check optical and audio alarm signals. Press and hold down the button for at least 1 second! At the bottom of the unit s PCB there is placed six-position switch SW1 (4), designed to set the functions of the control unit. Switch position Function SW1-1 Disconnection of the actuator line SW1-2 Disconnection of the sensor line SW1-3 Disconnection of the ROP pushbutton line SW1-4 Disconnection of the in/out relay contacts SW1-5 Full opening of the vents during non-emergency ventilation SW1-6 Activation of the mode door s control Note: the default setting for SW1-1 through SW1-6 is OFF position Page 6 of 18

Along the top edge of the module's PCB there are terminal strips which are used for the connection of the system s elements: No. Description Function 5 P6 Input for ventilation (U-up, D-down, - joint, closing contacts) 6 P7 input for wind/rain controls (closing contact) 7 P8 output for actuators (-,+) 8 P9 RPO(+,-) pushbutton line 9 P10 control input from ROP-1 (R,U) 10 P11 sensor s line (+,-) 11 P12 power supply of the alarm signal loop (+, -) 12 P13 external alarm input, 24V= relay 13 P14 alarm indication output - relay contact 14 P15 defect indication output - relay contact 15 P16 vent opening (door closing) indication output relay contact 16 P17 RPO-1 indication output (1, 2, 3) Moreover, in the bottom part of the PCB: 17 P4 positive pole of the battery 18 P5 negative pole of the battery For control units designed for the purpose of a smoke curtains, above the elements [7,21] there is additional 4 poles terminal strip for the power supply of MCR Kurtyna motors. 230 V 50 Hz power supply is connected to the terminal strip (19) in the top left corner of the assembly board (inside the control unit). On-board fuses: No. Description Function 20 FS1 batteries protection (6.3 A or 8 A * quick) 21 FS3 actuator s line protection (6.3 A or 8 A * quick) Overload circuit breaker FS2 (22) C 4 A or 6 A * on the assembly board provides protection for the 230 V mains circuit and the possibility for disconnecting power supply. In multi module centrals only the single overload breaker is used for the protection of all modules. * - fuses in MCR9705-8A Page 7 of 18

Normal operation MAINTENANCE On the front panel (Fig. 1) are placed following indicator lights: yellow LED - READY green LED - POWER SUPPLY Description of the optical LED indicators on the front panel: POWER SUPPLY` READY ALARM FAULT VENT OPEN UNIT STATUS + VENT OPEN - VENT CLOSED B ACTUATOR IN OPERATION - + ALARM + + - - NORMAL OPERATION - - B MAINS FAILURE + - - + DEFECT + - - - DISCONNECTION ANY STATUS + ON - OFF B BLINKS MCR9705 is a maintenance-free device. It requires constant 230 V mains power supply. In case of power shortage caused by mains failure, the installed batteries will ensure 72-hour emergency power supply. Any power outage exceeding 72 hours can result in permanent damage of the batteries. Non-emergency ventilation (daily ventilation) For smoke vents equipped with electrical smoke exhaust actuators and the system with ventilation pushbuttons, it is possible to open smoke vents for nonemergency ventilation of the building in the normal usage conditions. When the pushbuttons ( or ) are pressed and held down for at least 1 s, the vents are being opened or closed, respectively. Pushing the button will always cause the smoke vent to be closed completely. The function of the button depends on the position of the SW1 switch in the unit module (Fig. 3 item 4): SW1-5 OFF Smoke vent is being opened as long as the pushbutton is held down (default factory settings), SW1-5 ON Pushing the button will cause the smoke vent to open completely. Page 8 of 18

NOTE!! The ventilation function is inactive when an emergency alarm is active or if there s mains power outage! Automatic weather monitoring unit If the system is equipped with wind and/or rain sensor, the sensor will prevent from opening of the smoke vents for non-emergency, daily ventilation in adverse weather conditions. The wind/rain sensor will automatically close smoke vents (or prevent the vents from being opened by using the ventilation pushbutton) if the wind or atmospheric precipitation is too strong. Note! 1. In case of the ALARM signal, smoke vents will be opened regardless of weather conditions! 2. Do not use alarm buttons for non-emergency ventilation! Emergency alarm If the status of the unit is in the alarm state, the red ALARM diode on the front panel will light up, the buzzer will sound and the yellow VENT OPEN diode will blink to indicate operation of actuators. Once the smoke vents are opened, the VENT OPEN diode will stay on. Alarm release methods: Manual - break the glass of the smoke release pushbutton and push the button. Automatic depending on the type of sensors used, they will be automatically activated when the temperature rises or the smoke conditions will appear. Automatic release from an external source a signal from an external device (e.g. Fire Alarm Unit) is supplied to the alarm signal-in terminals of the control unit (Fig. 3 item 11, 12). The alarm will cause 24 V power outage on P13 terminals. Deleting an emergency alarm To delete the alarm status, one first needs to open the unit with the correct key and determine the source of alarm, using the optical indicators inside the unit (Fig. 2). Depending on the source of the alarm, remove it s cause and reset the alarm: After manual alarm release (the RPO line), replace the glass in the alarm pushbutton, delete the alarm either using the RESET button on the casing of the control unit or by using the ALARM RESET button in the RPO-1 unit (hold the button down for at least 1 s). The red ALARM diode will be turned off, and the yellow READY diode will light up. Page 9 of 18

After alarm release from a smoke sensor (the sensor line), delete the alarm using the RESET button. The sensor will not activate the alarm again if there s no longer excessive smoke/temperature. The red ALARM diode will be turned off, and the yellow READY diode will light up. After alarm release from an external source (in/out) one first needs to delete the alarm in the device which initiated the response of the MCR9705 control unit. Then delete the alarm using the RESET button. The red ALARM diode will be turned off, and the yellow READY diode will light up. If the cause of the alarm can t be removed (for example, when there s an alarm source failure), one needs to access the segment representing the relevant alarm source in the SW1 switch in the control centre module (Fig. 3 item 4) and adjust it from the OFF to the ON position (in accordance to the description on the optical signal board disconnection of the RPO/sensor/in-out line). In next step delete the alarm using the RESET button. The red ALARM diode will be turned off. The yellow READY diode will not light up. In this case CALL THE SERVICE Closing the vents after alarm release. To close the smoke exhaust vents, first cancel the alarm. When the alarm is being cancelled using the RPO-1 button, the vents shall be automatically closed. Once the alarm has been cancelled from the control unit, push and hold down for at least 1 s the CLOSE VENTS button in the control unit or the ventilation button The yellow VENT OPEN diode will begin to blink, indicating the operation of actuators. Once the smoke exhaust vents are closed, the VENT OPEN indicator will be turned off (about 5 min.) Diagnosis of the defects. Optical indicators (Fig. 2) placed on the inside part of the casing s door enable identification of the system s defects. A blinking DEFECT diode provides information about the mains failure or batteries failure. In this case, one has to check whether there s voltage (230 V) on the unit s terminals and the status of FS1 and FS2 cut-out fuses (see: page 7). If there is a signal indicating a defect in the actuator line, check the on board fuse FS3. Never change the default settings of the voltage potentiometer for the batteries In case of a system defect CALL THE SERVICE. Page 10 of 18

Assembly and start up 1. Attach the unit near the devices that will be controlled, by appropriate metal connectors that must be selected in accordance with the substrate material. Note: do not drill through the unit's casing in case of damage of any electronic components caused by dust/debris, complaints will be disregarded. 2. Sensors line - 2 leads (e.g. YnTKSY) from P11 terminals. Terminal resistor 5,1 kω in the base of the last sensor. The maximum number of sensors is limited in accordance with the list of technical parameters. 3. Smoke exhaust pushbuttons line (RPO) - 7 leads from P9 (alarm closing contact), P10 (control inputs) and P17 terminals (indicator output). Terminal resistor 10 kω in the last pushbutton. The maximum number of pushbuttons in accordance with the technical parameters. 4. Actuators line - 2 leads in silicone insulation (feature PH30, for example HLGs), from P8 terminals. Terminal resistor 10 kω in the last assembly box. The line is protected by a 6,3 A or 8 A fuse (FS3). The maximum number of actuators in accordance with the technical parameters. Only specific leads shall be used, leads that are compatible with actual regulations. Attention: In case of multi module centrals do not connect galvanized outputs [to actuators] of different modules. 5. Ventilation - pushbuttons for ventilation (manual flap control- upwards, downwards) 3 leads (e.g. YTKSY or YDY) from P6 terminals. It is possible to connect several pushbuttons in parallel. 6. Automatic weather monitoring unit for closing the vents in case of a strong wind/ heavy rain - 2 leads (e.g. YTKSY or YDY) from P7 terminals. 7. External alarm input to the 24 V relay coil 2 leads (e.g. YnTKSY) from P13 terminals. If the device which activates the alarm (fire alarm control unit) has a 24 V output, it shall be connected directly to the P13 terminal. Loss of voltage at the P13 terminal will activate the alarm. If the device which activates the alarm is equipped with a voltage-free null contact (NC), we have to use the loop power supply available on the P12 terminal (see drawing). The P12 terminal is short-circuit resistant and can carry a load of maximum two relays. Once the line is connected remove the H1 jumper which blocks the external alarm. 8. Voltage-free output NC (or NO) for information about alarm 2 leads (e.g. YnTKSY) from P14 terminals. The H2 jumper allows to select NC (default) or NO output. Page 11 of 18

9. Voltage-free output NC (or NO) for information about defect 2 leads (e.g. YnTKSY) from P15 terminals. The H3 jumper allows to select NC (default) or NO output. 10. Voltage-free output NC (or NO) for information about vent opening 2 leads (e.g. YnTKSY) from P16 terminals. The H4 jumper allows to select NC (default) or NO output. 11. Mains 230 V, 50 Hz should be connected to the terminal strip on the unit assembly board. The power supply for the unit should be separate (units only on the mains line), protected by means of a properly marked overload circuit breaker in the switching station. The recommended circuit breaker: I = number of control units * 4 A, or * 6A for series of type 8A. It is not recommended to connect more than eight units on a single line. Do not protect the line by means of a GFCI (RCCB) circuit breaker. 12. 24 V power supply from batteries (P4, P5). The batteries should be connected in series, taking polarity into account. Make the connection after the control unit has been launched by use of mains power supply. 13. Large systems connecting multiple control units. In order to increase the number of sensors, ROP buttons or actuators connected to the system, one can connect multiple control units. To relay an alarm from one control unit to another, use the P14 alarm output terminal and the P13 alarm input terminal with P12 power supply. Do not connect output lines [to actuators] of different modules. Control units can be connected together into ventilation sections. To do this, connect in parallel the P6 ventilation terminals of all control units in a section: U-up, D-down, ground-joint. Connect the weather monitoring unit only to one (any one) control unit in the section, to P7 terminals. When connecting the weather monitoring unit to more than one ventilation section, connect individual units in parallel. Important! - connect the P7 terminals on the left to one line, and the ones on the right to the other line - do not cross! 14. Remote door controls. The control unit is also adapted to operat in the remote door control mode. To switch on the door control mode, use the SW1-6 switch (set it to ON). Connect electromagnetic door locks to the P8 terminals. 15. Start-up. Before switching on the power supply, check if the leads are connected properly. Note: the leads should be placed and connected in accordance with relevant standards and basic rules for wiring. First switch on the 230 V mains voltage, and only then connect the batteries. The reverse order is not recommended because of a large current surge that occurs during the charging of the condenser in the power supply adaptor. Page 12 of 18

In a correctly operating unit, the following LED indicator are on: READY, POWER SUPPLY, and VENT OPEN. When the CLOSE VENTS button is pressed, the VENT OPEN diode begins to blink and then switches off after about 5 minutes. When the actuator is in operation, the VENT OPEN diode keeps blinking. In order to check the operation of ventilation, the weather monitoring unit should be disconnected. The weather monitoring unit blocks ventilation for several minutes after the wind has ceased, and in case of rain the sensor needs to get dry, which takes even more time. The LEDs on the inside of the unit s door enable detailed defect identification. To test their operation, press the TEST button and hold it down for about 1 s. To test the operation of the buzzer, press simultaneously the TEST and RESET buttons. Note: in order to connect the unit you should use leads which satisfy the requirements of current regulations. FP CU 5,1k 1 3 4 1 3 4 MCRP054 P9 VENT OPEN DE FECT ALARM ALARM LOOP SUPPLY DETECTOR WIND\RAIN VENT. PUSH- BUTTON OUT IN LINEs DRIVES VENTILATION Diagram 1. Typical configuration of a smoke exhaust system equipped with the MCR9705-5A control unit. FP CU fire protection control unit OCD optical smoke detector (eg. KL731) RPO manual call point MCR RPO-1 PM connection box ME electromechanical motor CP - weather monitoring unit MCRP054 LT - ventilation pushbutton Page 13 of 18

FP CU 5,1k 1 3 4 PM ME 1 3 4 1 2 3 4 1 2 3 4 VENT DEFECT ALARM ALARM OPEN LOOP DETECTOR SUPPLY OUT IN LINEs DRIVERS Diagram. 2. Typical connection of smoke curtain to control unit MCR 9705 (Execution for curtains). Elements: OCD optical smoke detector (sensors should be connected according to advice of a manufacturer) RPO manual call point MCR RPO-1 PM connection box ME electromechanical motor 24 V = curtain MCR KURTYNA PROSMOKE Attention!: 1. Not all the elements of the system (in particular the connection with fire protection control unit) must be present in the smoke exhaust system. 2. Central unit or module operating with smoke curtain can not be connected simultaneously to smoke vent s actuators, weather central unit or ventilation push buttons. Page 14 of 18

5,1 1 3 4 1 3 4 VENT OPEN DEFECT ALARM ALARM LOOP SUPPLY DETECTOR WIND\ RAIN VENT. PUSH- BUTTON VENT DEFECT OPEN ALARM ALARM LOOP SUPPLY OUT IN LINEs DRIVES VENTILATION OUT IN LINEs DRIVES VENTILATION DETECTOR WIND\ RAIN VENT. PUSH- BUTTON Diagram. 3. Passing the alarm signal between modules or central units. Attention: 1. Remove jumper H1 in controlled module! 2. Controlled module is activated by the alarm signal from steering module. Page 15 of 18

Technical specifications. Item Value Base type: 5 A 8 A Power supply voltage basic power supply 230 V 10% 50 Hz 15% Rated power 150 VA 250 VA Output voltage (power supply for actuators) 24V DC, max. 5,2 A 24V DC, max. 8 A Stand-by power supply 2 batt. (min. 3,2 Ah, 12 V) connected in series Charging voltage for set of batteries 27,5 V 0,2 V @20 C Working temperature range -5 C.. +50 C Maximum number of sensors in line: - NOTIFIER - POLON-ALFA - ARITECH, GE Security Maximum number of MCR RPO-1 pushbuttons Maximum number of actuators by type: MCR L MCR L K05x MCR L KT10x i KR10x MCR L KRT20x MCRW 081 MCRW 10x MCRW 16x MCRW 20x MCRW 26x MCRW 40x MCRW 60x MCRW 80x other types of electric actuators depending upon consumed and maximum current Maximum number of electromagnetic door locks by type: MCR TE 50 MCR TE 100 Operation time without mains voltage, in READY mode 2 pcs. 10 szt 5 szt 2 szt 6 pcs. 5 pcs. 3 pcs. 2 pcs. 2 pcs. 1 pcs. - - 40 pcs. 30 pcs. 10 szt. 8 szt. 8 pcs 4 szt. minimum 72 hours* Load for relay outputs max. 100 ma, 24 V Protection level for housing IP 54 Dimensions (H x W x D) for 5 A or 8 A model 300 x 300 x 150 mm * After this time the unit may open actuators once and indicate alarm for 30 minutes. 3 pcs. 16 szt 8 szt 2 szt 10 pcs. 8 pcs. 5 pcs. 4 pcs. 3 pcs. 2 pcs. 1 pcs. 1 pcs. 40 pcs. 30 pcs. Page 16 of 18

Range of MCR9705 control unit based on 5 A simple module: Type of control unit Makeup Housing dim. [mm] Rated power [VA] MCR9705-5A 1* 5 A (base size) 300x300x150 150 MCR9705-10A 2* 5 A 400x400x200 300 MCR9705-15A 3* 5 A 600x600x200 450 MCR9705-20A 4* 5 A 600x600x200 600 MCR9705-25A 5* 5 A 800x600x300 750 MCR9705-30A 6* 5 A 800x600x300 900 MCR9705-35A 7* 5 A 1000x600x400 1050 MCR9705-40A 8* 5 A 1000x600x400 1200 MCR9705-45A 9* 5 A 1000x800x400 1350 MCR9705-50A 10* 5 A 1000x800x400 1500 MCR9705-55A 11* 5 A 1000x800x400 1650 MCR9705-60A 12* 5 A 1000x800x400 1800 Range of MCR9705 control unit based on 8 A simple module: Type of control unit Makeup Housing dim. [mm] Rated power [VA] MCR9705-8A 1* 8 A (base size) 300x300x150 250 MCR9705-16A 2* 8 A 400x400x200 500 MCR9705-24A 3* 8 A 600x600x200 750 MCR9705-32A 4* 8 A 600x600x200 1000 MCR9705-40A 5* 8 A 800x600x300 1250 MCR9705-48A 6* 8 A 800x600x300 1500 MCR9705-56A 7* 8 A 1000x600x400 1750 MCR9705-64A 8* 8 A 1000x600x400 2000 Warranty terms and conditions. 1. MERCOR grants a 12-month quality guarantee for equipment, starting from the date of purchase, unless the agreement provides otherwise. 2. If during the term of guarantee any physical defects of the equipment become evident, MERCOR shall remove them within 21 days of the written notification, subject to paragraph 5. 3. In the event of defects resulting from inappropriate operation of the equipment or due to other reasons stated in par. 6, the Buyer/Guarantee Holder shall bear the costs of their removal. 4. Liability under the Guarantee covers only defects resulting from causes inherent in the equipment sold. 5. MERCOR reserves the right to lengthen the repair time in the event of complicated repairs or those that require non-standard sub-assemblies [elements] or spare parts to be purchased. 6. The guarantee does not cover: damages and breakdowns of the equipment due to inappropriate operation, user s interference, lack of maintenance or periodic servicing; Page 17 of 18

equipment damages resulting from causes other than those that MERCOR is responsible for, in particular: acts of God such as torrential rainfall, flood, hurricane, flooding, stroke of thunder, overvoltage in the mains, explosion, hail, fall of aircraft, fire, avalanche, landslide and secondary damages due to the above-listed causes. Torrential rain is defined as rain with an efficiency index of at least 4 (or 5 in Chomicz scale or torrential rain grade IV (A 4 )). Should it be impossible to determine the index mentioned in the previous sentence, the actual condition and the degree of damage at the place of its origin proving that it is the consequence of torrential rain will be considered. Hurricane is defined as wind blowing at the speed of at least 17.5 m/s (damages are deemed to have been caused by hurricane if the effects of hurricane have been found in the immediate neighborhood); damages due to failure to immediately report the defect discovered; worsened quality of coating due to the natural ageing process (fading, oxidation); defects due to using abrasive or aggressive cleaning products; parts liable to natural wear and tear during operation (e.g. seals) unless a manufacturing fault has occurred; damages due to aggressive external factors, especially chemical and biological ones. 7. Each defect under guarantee should be reported to a local representative of MERCOR immediately, i.e. within 7 days of its discovery. 8. The Buyer/Guarantee Holder is responsible for proper operation and maintenance of the equipment and for regular (min. twice a year) servicing. 9. The Guarantee shall expire forthwith if: The Buyer/Guarantee Holder makes design modifications on his own without consulting MERCOR SA, Maintenance or periodic servicing are not done in due time or are performed by unauthorized persons or a service center not authorized by MERCOR, or the equipment is operated in the wrong way, Any interference of unauthorized persons except activities connected with normal operation of the equipment. 10. Moreover, in the cases specified in par. 9, MERCOR has no warranty obligations. Service 1. The equipment should undergo regular servicing every 6 months during the whole period of its operation. 2. The servicing should be conducted by companies with proper authorization of MERCOR or its local representative. 3. Please contact a local representative of MERCOR for information about maintenance. Page 18 of 18