JADE Economizer with W7220-PCMOD Tool and Prestige IAQ 2.0 Thermostat

Similar documents
JADE Economizer Module (MODEL W7220)

Siemens Thermostats. RDY2000BN Thermostat

1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network.

TV2 Room Pressure Monitor Quick Start Guide

Zoning System for Residential Communicating, Variable Air Volume Heating/Cooling Systems

INSTALLATION, OPERATION & QUICK START GUIDE

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

Halton SAFE / 7.14 user guide and installation instructions

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING


HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Feature Summary. I. System

IntelliSync Thermostat / Mobile App Frequently Asked Questions

VisionPRO 8000 with Wi-Fi

1.1 Ethernet Remote Annunciator Controller (RAC) using the up to 4 ATC-300+ connected via RS-485 to TCP/IP gateway

TEC210x-2 Series Networked Thermostats

Introduction. OM-THA2

THX9321R5030/U Prestige 2.0 HD High-definition Color Touchscreen Thermostat, RedLINK enabled

Brivis Touch Controller. Installer Manual

prestige Control Application Supplement - TriMax

TEC2100 Series Networked Thermostats

Parts Catalog

i-vu CCN 4.0 Owner s Guide

INSTALLATION INSTRUCTIONS

MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS

H&O DIE SUPPLY, INC SPR-2000-JR. Programmable Fluid Controller Interstate 20 Kennedale, TX 76060

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

Autoclave Operations Manual

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Added password for IP setup page : Password must be in IP format!

MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS

Monitoring Solutions

prestige Control Application Supplement - TriMax

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 16 ADVANCED AUTOMATIC CONTROLS DIRECT DIGITAL CONTROLS (DDCS) AND PNEUMATICS

TV2 Clean Room Monitor

ComfortNet CTK04 Featuring the RedLINK Suite of Home Comfort Solutions

INSTALLATION INSTRUCTIONS MODELS RXRD-01MDDAM3 VERTICAL AIRFLOW ECONOMIZERS

Fingertip control, optimum efficiency, total comfort and clear reporting. warmafloor.co.uk

SC-F3G User Manual 1.0

SCAN200E USER S MANUAL

Description of the. controllers. Description of the. system extension possibilities. RS communication. Front panel made of glass. Control of 2 valves

1.1 Remote Annunciator Controller (RAC) and 1 Switch (ATC-600/800) via Modbus TCP/IP Ethernet Gateway

My Visonic SMS App User Guide

CONTENTS. Installation Guide. VT7200 Series

Ion Gateway Cellular Gateway and Wireless Sensors

ECONOMIZER CONTROLLER ET-858

- Data Brochure Universal Reset Module 422

Fire Alarm System Inspection and Testing Report

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

T5000 LCD Digital Fan Coil Thermostat

Omniguard 4: Features

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT )

Tri-Stack Smart System

Solve Complex Comfort Challenges.

Operating Instructions READ AND SAVE THESE INSTRUCTIONS

Technical Reference Manual Design and Application Guide for Honeywell Economizer Controls

AirFlow Sensor for Dry Contact connection

Covidien Articulating Absorba Tack Foil Pouch Leak Tester Owner s Manual IPE SN Rev 1

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

Table of Contents. Appendix A Special Characters 31

L CONNECTION NETWORK Commercial Controls

prestige Control Application Supplement WARNING

Cold chain monitoring technologies. Facility monitoring

WARNING IMPORTANT. iharmony Zoning System CONTROLS KITS AND ACCESSORIES. Installation Instructions for the iharmony Zoning System (10C16)

RedLINK Connects RedLINK Wireless Comfort Systems

Product Manual SZ1009

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

EL-TSTAT-8820 Safety & Installation Instructions

Commercial Touchscreen Thermostat

Specification/ Data Sheet

Echopod Set-Up with a MegaTron

NFPA Changes

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

LONE WORKER SAFETY HOW DO YOU PROTECT YOUR LONE WORKERS? EMPLOYEE CHECK-IN SYSTEMS DON T WORK! YOU NEED AN IMMEDIATE NOTIFICATION SYSTEM

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

Table of Contents. i-vu CCN Standard 4.2

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

APPLICATION DATA SHEET

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

Model 4880 Status Output Display Module Manual

Tstat9. Bacnet Thermostat

SEQUENCE OF OPERATIONS

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

RCS Residential Control Systems Inc.

Setting the New Standard in Chiller Technology ±0.1 C ZEROPOINT CHILLER SERIES

Application Manual Loop Water Controller

OVEN INDUSTRIES, INC.

T-32-TS Touchscreen Thermostat. Installation Manual

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Transcription:

JADE Economizer with W7220-PCMOD Tool and Prestige IAQ 2.0 Thermostat The JADE controller is a digital unit with economizing, demand control ventilation, and auto calibration strategies used to provide energy savings and comfort for the occupants of small commercial buildings. JADE automatically recognizes the following components that are wired to it: Outdoor enthalpy or dry bulb CO2 for demand control ventilation Mixed air for supply air comfort control and Actuators to control the dampers. After the first 60 minutes of power on, Jade will change from a setup mode to an operation mode and will control the ventilation and free cooling to the building. Alarm Mode for Failed Components on the JADE economizer system If a sensor or actuator fails to respond to JADE during the operation mode, the JADE controller has the ability to send a 24 Vac signal, communicating that there is an alarm in the system. This is accomplished by programming the AUX1 O (out) terminal to SYS in the System Setup Menu on the JADE controller. The building operator is able to address the alarm in three ways: Connect a light or audio alarm to the AUX1 O out to turn on a visual or audible alarm in the space, where a building operator will notice there is an alarm on the system. Connect JADE to a W7220-PCMOD tool in the mechanical room, using the two-wire communication terminals (s-bus) and a personal computer to monitor the system. Use a Prestige IAQ 2.0 thermostat to alarm the occupants that there is a system alarm. The options of connecting a visual or audio alarm to the SYS output when an alarm occurs would normally not be used in an occupied space; these types of alarm systems would be in a warehouse or computer lab. Using the W7220-PCMOD tool to monitor the occupancy, damper position and status of the sensors in the system allows the building operator to keep a constant or periodic audit record of the economizer system. The PCMOD tool is connected to the JADE controller via two non-polarity wires and to a personal computer via USB cable to log the selected data. A Prestige IAQ 2.0 thermostat can be used in the system alone or in conjunction with the W7220- PCMOD tool, to alert building occupants when there is an alarm in the economizer system. The wiring diagram for the system is shown in Figure 1.

You will need the following components: W7220A1000 JADE economizer (plus sensors and actuator(s)) R8222N1011 DPDT relay THX9421R5021WW/U Prestige IAQ 2.0 2-wire Thermostat THM5421R1021/U Equipment Interface Module Prestige IAQ 2.0 thermostat and Equipment Interface Module can be purchased in a kit YTHX9421R5085WW/U To program the Prestige IAQ 2.0 thermostat for JADE controller alarms: 1. Power thermostat> press Menu> press Installer options>input password> press Create Setup>select options through set up step 6000. Note: The password is the date code located on the back of the thermostat. The date code can also be found in Menu>Equipment Status. 2. At Installer Setup 6000 (Select the Dry Contacts in the System)> select Custom Alert. 3. At Installer Setup 6170, select the terminals wired to the dry contact device (S1 or S2). Connect a Normally Open Relay Contact to the S1 or S2 terminals.

4. At Installer Setup 6180 (Custom Alert Dry Contact Setup, select Normally Open. 5. At Installer Setup 6190 (Customer Alert Name) >press to edit> type up to 40 characters ex: Economizer Alarm (this will display on the thermostat home screen in an orange box when there is an alarm on the Jade controller)

6. At Installer Setup 6200 (Customer Alert Message) >press to edit> type up to 140 characters ex: Call for Service 1-800-555-1212 7. If the occupants clear the alert, the building operator can recover the last 25 alarms in the Alerts Log. The Alerts Log is located in the Menu>Installer Options>Data Logs>Alerts Log JADE, Prestige IAQ 2.0 and the W7220- PC MOD tool bring the entire package of a comfortable and well ventilated environment together for the occupants. An energy efficient building with economizer and demand control ventilation for the owner and time savings for the service technician. The system will notify the occupants in the building of an economizer alarm via the Prestige IAQ 2.0 thermostat and occupants will call for service. When the technician arrives he can use the W7220-PC MOD tool to read the alarms on his personal computer without going up to the unit on the roof, he will know within minutes of his arrival what the alarm is and how to repair it, prior to going up on the roof. The building

owner will increase their energy savings, provide a well ventilated space for the occupants and the service technicians will be able to make more calls and service more customers. Figure 1