TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

Similar documents
Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

EVERWATCH FACE VELOCITY MONITOR MODEL 8610

PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM

Contamination Control for Electronic and Semiconductor Applications

Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include:

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

The New DUSTTRAK II and DRX Aerosol Monitors

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

The New DUSTTRAK II and DRX Aerosol Monitors

SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS BAC

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

SUREFLOW ROOM PRESSURE CONTROLLER MODELS BAC

Contamination Control for Life Science Applications

RPM1600 Series Room Pressure Monitors

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

HVAC Controls Laboratory. Model EVERWATCH Face Velocity Monitor. Operation and Service Manual. P/N , Revision E October 2002

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

RS485 MODBUS Module 8AI

CONTAMINATION CONTROL FOR ELECTRONIC AND SEMICONDUCTOR APPLICATIONS

Critical Environments. Model FHC50/FHM10. Fume Hood Controller/Monitor. Operation and Service Manual. P/N , Revision B October 2010

FlameGard 5 UV/IR HART

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

FlameGard 5 MSIR HART

Database for CTS6000 MODBUS

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

F Technical Bulletin SC 370 SMART Modbus Interface

MicroTech Unit Ventilator

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

CLEANROOM MONITOR CR3A Network - Installation Instructions

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Carbon Monoxide Transmitter

Open Protocol Data Communications

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Manual for the integration in BMS/GTC

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

Modbus RTU RS485 Manual

/8 DIN Level Indicator

Gas Detection System TOX ALARM DG2000-Garage

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

MO n : 12JMC rév A

4590 Tank Side Monitor. Service Manual. WM550 Communication Protocol. Software Versionv2.03 SRM011FVAE0808

For Raychem ACS-30 Controls Systems

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

LD5100 USER GUIDE RLE TECHNOLOGIES

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

Metasys Integrator TITUS Application

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

CTT8 TEMPERATURE MONITOR DEVICE

Instruction Bulletin

TP488-IV 8 Channel Scanning Monitor Operation and Instruction Manual

Modbus TCP/IP Option Instruction Manual

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

Figure 1. Proper Method of Holding the ToolStick. Figure 2. Improper Method of Holding the ToolStick

ModBus DE-1 INSTALLATION AND USER MANUAL

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

Temperature Controllers

1600 Gas Controller. User s Manual. Industrial Scientific Corporation. Version 3.2 September 1, 2006

Instruction Manual. TEC-910 High Limit Control Microprocessor Based Limit Controller

MicroTech Series 200 Centrifugal Chiller

DTSX200 Communications(Modbus) Guide

P2267 NETWORK INTERFACE

Sales and Engineering Data Sheet ED

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

AFA1000/1 MK3 Airflow Monitor

1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network.

EASY ZONE TOUCH. User Manual. 6 Zone Control System with Active Temperature Management. Ver 1.0

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Technical Handbook. Sieger DX100 Series Termination Units

CONTROL UNIT: REFERENCE MANUAL

SyringeHeater.com. Syringe Heater. Thermo-Kinetic Heat Clamping. Model: HEATER-KIT-1LG HEATER-KIT-5SP

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

USER MANUAL FOR OPERATING SYSTEM

Trident User s Manual

Series Temperature Controller Instruction Sheet

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Nov 08 PRODUCT SPECIFICATION SHEET

SEQUENCE OF OPERATIONS

SCAN200E USER S MANUAL

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

OVEN INDUSTRIES, INC.

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0)

OWNER S OPERATION MANUAL

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device

Technical data Humidity Temperatur General data Electrical data Two designs duct version (LK) wall mounting

Transcription:

Critical Environments TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106 Modbus communications are installed in all Model 8630 hospital room pressure controllers and premium monitors. This document provides the technical information needed to communicate between the host DDC system and Model 8630 units. This document assumes the programmer is familiar with Modbus protocol. Further technical assistance is available from TSI if your question is related to TSI interfacing to a DDC system. If you need further information regarding Modbus programming in general, please contact: Modicon Incorporated One High Street North Andover, MA 01845 Phone (508) 794-0800 The Modbus protocol utilizes the RTU format for data transfer and Error Checking. Check the Modicon Modbus Protocol Reference Guide (PI-Mbus-300) for more information on CRC generation and message structures. The messages are sent at 9600 baud with 1 start bit, 8 data bits, and 2 stop bits. Do not use the parity bit. The system is set up as a master slave network. The TSI units act as slaves and respond to messages when there correct address is polled. Blocks of data can be written or read from each device. Using a block format will speed up the access time for each device. The size of the blocks is limited to 20 bytes. This means the maximum message length that can be transferred is 20 bytes. The typical response time of the device is around 0.05 seconds with a maximum of 0.1 seconds. Unique to TSI The list of variable addresses shown below skips some numbers in the sequence due to internal Model 8630 functions. This information is not useful to the DDC system and is therefore deleted. Skipping numbers in the sequence will not cause any communication problems. Occasionally an asterisk (*) will accompany a flow variable name. This designates that the flow station could be mounted in either supply or exhaust duct, but the variable name states it is the supply flow. If the TSI is a registered trademark of TSI Incorporated. TSI logo and PRESSURA are trademarks of TSI Incorporated. Modbus is a trademark of Modicon Incorporated.

flow station is located in the exhaust, the DDC system will need a name change to properly display on the DDC screen. All variables are outputted in English units: feet per minute, CFM, or inches H 2 O. If the DDC system is to display different units, the DDC system needs to make the conversion. RAM s RAM variables use the Modbus command 04 Read Input Registers. RAM variables are read only variables, that correspond to what is shown on Digital Interface Module (DIM) display. TSI offers a number of different models, so if a feature is not available on a unit, the variable is set to 0. Name Address Information Provided to Master System Integer DDC system receives Velocity 0 Velocity of room pressure Displayed in feet per minute. Pressure 1 Room pressure Displayed in inches H 2 O. Host DDC system must divide value by 100,000 to report pressure Flow Rate 2 Flow (CFM) measured by the Displayed in CFM. exhaust duct flow station ACPH 3 Calculated room air changes Displayed in number per hour. Host DDC system must divide value by 10 to report ACPH Supply Flow Rate* 4 Flow (CFM) measured by the Displayed in CFM. supply duct flow station Second Velocity 5 Second sensor velocity of room Displayed in feet per minute. pressure Second Pressure 6 Second sensor room pressure Displayed in inches H 2 O. Host DDC system must divide value by 100,000 to report pressure Setpoint 7 Active control setpoint Displayed in feet per minute. Status Index 8 Status of PRESSURA device 0 Normal 1 Low Alarm 2 High Alarm 3 Min Exh Alm 4 Min Sup Alm 5 Sec Low ALM 6 Sec High ALM 7 Data Error 8 Emergency Control Mode 9 Control mode device is in 0 Negative 1 Positive 2 No Isolation Control Output 13 Control output value 0 to 255 will be displayed. EXAMPLE of 04 Read Input Registers function format This example reads variable addresses 0 and 1 (Velocity and Pressure). QUERY RESPONSE Field Name Example # 2 Field Name Example # 1 Slave Address 01 Slave Address 01 Function 04 Function 04 Starting Address Hi 00 Byte Count 04 Starting Address Lo 00 Data Hi Addr0 00 No. of Points Hi 00 Data Lo Addr0 64 (100 ft/min) No. of Points Lo 02 Data Hi Addr1 00 Error Check (CRC) -- Data Lo Addr1 64 (0.00100 H 2 0) 2

XRAM s These variables can be read using Modbus command 03 Read Holding Registers. They can be written to using Modbus command 16 Preset Multiple Regs. These variables are the same menu items that are configured from the PRESSURA keypad. The calibration and control items are not accessible from the DDC system. This is for safety reasons, since each room is individually setup for maximum performance. TSI offers a number of different models, so if a feature is not available on a unit, the variable is set to 0. Name Address Input Provided to Master System Integer DDC system receives Software Version (read only) 0 Current software version 1.00 = 100 Hospital Device 1 PRESSURA Model 1 8630-SM 3 8630-SC (read only) 2 8630-PM 4 8630-PC Emergency Mode 2 Emergency Mode Control 0 Leave emergency mode 1 Enter emergency mode Value will return a 2 when read Negative Setpoint 3 Negative pressure control setpoint Displayed in feet per minute. Positive Setpoint 4 Positive pressure control setpoint Displayed in feet per minute. Min Flow Setpoint 5 Minimum flow exhaust control setpoint Displayed in CFM. Damper Position 6 Damper position when DIM is in no isolation mode 0 to 255 will be displayed. 150 is approximately 1/2 open. Negative Low Alarm 7 Negative low pressure alarm setpoint Displayed in feet per minute. Negative High Alarm 8 Negative high pressure alarm setpoint Displayed in feet per minute. Positive Low Alarm 9 Positive low pressure alarm setpoint Displayed in feet per minute. Positive High Alarm 10 Positive high pressure alarm setpoint Displayed in feet per minute. Min Flow Alarm 11 Minimum exhaust flow alarm Displayed in CFM. Min Supply Alarm 12 Minimum supply flow alarm Displayed in CFM. Sec Low Alarm 13 Second sensor low alarm Displayed in feet per minute. Sec High Alarm 14 Second sensor high alarm Displayed in feet per minute. Averaging Index 15 Display averaging period 0.75 sec. 4 5 Sec. 1 1 Sec. 5 10 Sec. 2 2 Sec. 6 20 Sec. 3 3 Sec. 7 40 Sec. Units Value 16 Current pressure units displayed 0 Feet per minute 1 meters per second 2 inches of H 2 O 3 Pascal 4 millimeters H 2 O Alarm Mode 17 Latched or unlatched alarms 0 Unlatched 1 Latched Audible Alarm 18 Audible alarm indication 0 OFF Alarm Delay 19 Time delay before audible alarm sounds Host DDC system must divide value by 10 to report alarm delay Mute Delay 20 Length of time alarm is muted when mute key is pressed Host DDC system must divide value by 600 to report alarm delay 3

XRAM s (cont.) Name Address Input Provided to Master System Integer DDC system receives Output Range 21 Room pressure analog output range 0 Low 1 High Output Mode 22 Analog output signal 0 4 to 20 ma 1 0 to 10 Volt Elevation 23 Elevation above sea level 0 to 10,000 feet. Displayed in 1,000 feet increments. Duct Area 24 Duct area in square feet Host DDC system must divide value by 1,000 to report duct area Room Volume 25 Room volume in cubic feet (needed for ACPH calculation) 0 to 20,000 cubic feet. Displayed in 10 cubic foot increments. Supply Duct Area* 26 Supply duct area in square feet Host DDC system must divide value by 1,000 to report supply duct area Second Sensor 27 s second room pressure sensor 0 Off ACPH Flow Channel 28 Set ACPH flow calculation 0 Exhaust 1 Supply Program Control 29 Changes room pressure control mode 0 Negative 2 No Isolation Mode 1 Positive 3 Key switch Control Action 32 Control output signal direction 0 Reverse 1 Direct Network Protocol 36 Network Protocol for RS-485 0 Modbus Communications 1 Cimetrics Network Address 37 Communication address of device Range is 1 to 247 Set Code 48 Setpoint menu access code enable 0 Off Alarm Code 49 Alarm menu access code enable 0 Off Conf Code 50 Configure menu access code enable 0 Off Cal Code 51 Calibration menu access code enable 0 Off Control Code 52 Control menu access code enable 0 Off Interface Code 53 Interface menu access code enable 0 Off Diagnostic Code 54 Diagnostic menu access code enable 0 Off 4

EXAMPLE of 16 (10 Hex) Preset Multiple Regs function Format This example changes the positive set point to 100 ft/min. QUERY RESPONSE Field Name Example # 2 Field Name Example # 2 Slave Address 01 Slave Address 01 Function 10 Function 10 Starting Address Hi 00 Starting Address Hi 00 Starting Address Lo 04 Starting Address Lo 04 No. of Registers Hi 00 No of Registers Hi 00 No. of Registers Lo 01 No of Registers Lo 01 Data Hi 00 Error Check (CRC) -- Data Lo 64 Error Check (CRC) -- TSI Incorporated 500 Cardigan Road, Shoreview, MN 55126 U.S.A USA Tel: +1 800 874 2811 E-mail: answers@tsi.com Website: www.tsi.com UK Tel: +44 149 4 459200 E-mail: tsiuk@tsi.com Website: www.tsiinc.co.uk France Tel: +33 491 11 87 64 E-mail: tsifrance@tsi.com Website: www.tsiinc.fr Germany Tel: +49 241 523030 E-mail: tsigmbh@tsi.com Website: www.tsiinc.de India Tel: +91 80 41132470 E-mail: tsi-india@tsi.com China Tel: +86 10 8260 1595 E-mail: tsibeijing@tsi.com Singapore Tel: +65 6595 6388 E-mail: tsi-singapore@tsi.com Contact your local TSI Distributor or visit our website www.tsi.com for more detailed specifications. 11/13/2009 LC-106 Rev A. Copyright 2009 by TSI Incorporated Printed in U.S.A