Similar documents
NFPA 80 Overview January 21, 2016

Committee Input No. 1-NFPA [ Chapter 2 ]

NFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.

About the Instructor & Presenter:

Swinging Egress and Fire Doors

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

WHAT TO EXPECT DURING A FIRE DOOR INSPECTION

Developing a Healthcare Facility Fire Door Inspection Program

Fire Rated Door Assemblies: Compliant Designs

Laura Frye, AHC, CSI, CCS, FDAI Technical Director, DSSF Director of Certification, DHI

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Fire and Smoke Door Inspections Qualified Training 02/03/17

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Design, Installation, Inspection, and Maintenance

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

AHCA Seminar: Inspecting and Maintaining Swinging Egress and Fire Door Assemblies

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 6-NFPA [ Section No. 2.2 ]

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

SECTION OVERHEAD COILING FIRE DOORS

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

NFPA 30 FLC-SWC First Revisions Page 1 of 10 11/6/2015 9:21 AM. First Revision No. 208-NFPA [ Section No ]

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

SAF-BCF SECOND REVISIONS WITH STATEMENTS

STANDARD FOR FIRE RATED ROLLING DOOR ASSEMBLIES

Iowa State Fire Marshal

26 of 128 9/23/2014 9:25 AM

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

SECTION AIR DUCT ACCESSORIES

University of Rochester October 17, 2008 Brooks Landing Business Center

NFPA 37 Public Comment Responses Page 1 of 32

First Revision No NFPA [ Section No ]

1 of 4 10/26/2015 1:58 PM. Committee Input No NFPA [ Section No ]

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 1-NFPA [ Chapter 2 ]

DIVISION 10 SPECIALTIES

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

SECTION Overhead Coiling Doors

Public Comment No. 1-NFPA [ Section No ]

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

2. Interior doors shall be not less than 18 gauge steel.

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

TECHNICAL COMMITTEE MEMBERS PRESENT


PART 1 GENERAL 1.01 SUMMARY

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

CHAPTER 8 CHIMNEYS AND VENTS

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

SECTION DOOR HARDWARE

Regulatory Reform (Fire Safety) Order 2005

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Report on First Revisions with Statement June 2014 NFPA 101

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

REPORT HOLDER: SMOKE GUARD, INC. 287 NORTH MAPLE GROVE ROAD BOISE, IDAHO EVALUATION SUBJECT:

PART 1 GENERAL 1.01 SUMMARY

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

PART 1 GENERAL 1.01 SUMMARY

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 10 - SPECIALTIES


CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA


The Physical Environment Portal: Module 5, LS Leadership

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.

FIRE & LIFE SAFTEY STANDARD

CHIMNEYS AND VENTS CHAPTER 8

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

SPECIFICATION SECTION : FIRE RATED GLASS & FRAMING SuperLite TM I-XL minute SuperLite TM I-XL IGU minute PART 1 GENERAL

Throughout standard remove references to the following and replace with the following:

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

Hands On Training for Fire Door Products and Fire Door Assemblies

SECTION DOOR HARDWARE

SECTION WET-PIPE SPRINKLER SYSTEMS

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

PART 1 GENERAL 1.01 SUMMARY

CHAPTER 8 CHIMNEYS AND VENTS

Changes for the New Edition. Senior Engineer, NFPA NFPA

Transcription:

Page 1 of 31 Second Revision No. 1-NFPA 80-2014 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A36/A36M, Standard Specification for Carbon Structural Steel, ASTM A36/A36M-082012. ASTM D4157, Standard Test Method for Abrasion Resistance of Textile Fabrics (Oscillatory Cylinder Method), 20102013. ASTM D5034, Standard Test Method for Breaking Strength and Elongation of Textile Fabrics (Grab Test), 2009 (2013). ASTM D6193, Standard Practice for Stitches and Seams, 2011. ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, 2012a. Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Tue Sep 30 13:11:34 EDT 2014 : Reference standards updates. Response Message: Public Comment No. 30-NFPA 80-2014 [Section No. 2.3.2] Public Comment No. 34-NFPA 80-2014 [Section No. 2.3.2] Page 1 of 43

Page 2 of 31 Second Revision No. 2-NFPA 80-2014 [ Section No. 2.3.6 ] 2.3.6 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. ANSI/UL 9, Standard for Fire Tests of Window Assemblies, 2009, revised 2009. ANSI/UL 10A, Standard for Tin-Clad Fire Doors, 2009, revised 2009. ANSI/UL 10D, Fire Tests for Fire Protective Curtains, 20092014. ANSI/UL 14C, Swing Hardware for Tin-Clad Fire Doors Mounted Singly and in Pairs, 2006, revised 2013. ANSI/UL 33, Standard for Heat Responsive Links for Fire-Protection Services, revised 2010. ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011. ANSI/UL 555, Standard for Fire Dampers, 2006, revised 2013. ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems, 2003, revised 2013. Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Tue Sep 30 13:20:12 EDT 2014 : Referenced standards update. Response Message: Page 2 of 43

Page 3 of 31 Second Revision No. 8-NFPA 80-2014 [ New Section after 3.3.57 ] 3.3.58 Fire Protective Curtain Assembly. An assembly typically consisting of a fabric curtain, a bottom bar, guides, a coil, and an operating and closing system. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 12:08:16 EDT 2014 Committee Statement: Response Message: The definition is a result of the work of a task group that was established during the First Draft meeting to further explore and evaluate the necessary requirements for fire and smoke curtains. The language is an expansion of the work completed at the First Draft meeting and is in response to the developed committee inputs. The task group worked together to develop requirements that address the installation, inspection, and testing of these fire and smoke curtain products. Page 3 of 43

Page 4 of 31 Second Revision No. 4-NFPA 80-2014 [ Section No. 3.3.110 ] 3.3.111 Sill. TheA structural component of the building that forms the bottom part of an opening over which a fire door closes. Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Tue Sep 30 13:38:44 EDT 2014 Committee Statement: Change further clarifies the definition of sill, which was added in the 2013 edition. Response Message: Public Comment No. 39-NFPA 80-2014 [Section No. 3.3.110] Page 4 of 43

Page 5 of 31 Second Revision No. 5-NFPA 80-2014 [ New Section after 3.3.125 ] 3.3.127 Threshold. A builders hardware component that is installed beneath a closed door. Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Tue Sep 30 13:47:16 EDT 2014 Committee Statement: The term "threshold" is used in several places in the standard and the definition clarifies its use. The committee had proposed, via a Committee Input during the First Draft stage, to add the term "thresholds" to the title of Section 4.8.2. It was decided to not make this change, but to add a definition in Chapter 3 to clarify the intent of the term "threshold" throughout the document. Response Message: Public Comment No. 38-NFPA 80-2014 [New Section after 3.3.125] Page 5 of 43

Page 6 of 31 Second Revision No. 16-NFPA 80-2014 [ Section No. 4.3.4 ] 4.3.4 The label described in 4.3.3 shall address the reinforcements necessary for the fire exit deviceshardware, and the complete fire door assembly shall have been tested for egress panic load requirements. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 14:57:33 EDT 2014 Committee Statement: Response Message: The language in this section incorrectly referred to 'exit devices' when the correct terminology, as stated in Section 4.3.3, is 'fire exit hardware.' Page 6 of 43

Page 7 of 31 Second Revision No. 18-NFPA 80-2014 [ Section No. 4.8.6 ] 4.8.6* Where permitted by the individual door assembly listing, expansion anchors used in concrete, brick, or filled concrete masonry unit walls shall meet the following conditions: (1) Expansion anchors shall be manufactured from steel and shall be zinc-coated or cadmium-coated. (2) Expansion anchors shall conform to Federal Specification A-A-1923A, Shield Expansion (Lag, Machine and Externally Threaded Wedge); A-A-1924A, Shield, Expansion (Self Drilling Tubular Expansion Shell Bolt); or A-A-55614, Shield, Expansion (Non-Drilling Expansion Anchors). (3) The compressive strength of the concrete shall not be less than 2000 psi (13,790 kpa), and the bolt load shall not exceed 1 4 of the proof test load. (4) Where used in brick or filled concrete masonry unit walls, the bolt load shall not exceed 1 12 of the proof test load. (5) No expansion anchor shall be set closer tothe distance from the edge of the wall opening than 6 times the diameter of the anchor or closer to another anchor than 8to the center of an expansion anchor shall be at least six times the diameter of the anchor. The distance between expansion anchors shall be at least eight times the diameter of the anchor. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:02:43 EDT 2014 Committee Statement: Response Message: Editorial correction. The current language was missing words was not clear. Page 7 of 43

Page 8 of 31 Second Revision No. 15-NFPA 80-2014 [ Section No. 5.5.7 ] 5.5.7 When fastener holes are left in a door or frame due to changes or removal of hardware or plant-ons, the holes shall be repaired by the following methods: (1) Install steel fasteners that completely fill the holes. (2) Fill the screw or bolt holes with the same material as the door or frame. (3) Fill holes with material listed for this use and installed in accordance with the manufacturer's procedures. 5.5.8 Holes, other than those as described by 5.5.7, shall be treated as a field modification in accordance with 5.1.4. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 14:52:25 EDT 2014 Committee Statement: Response Message: The changes to this section were proposed at the First Draft stage via a committee input. There are currently products available that are listed for repairing holes in fore doors. The revised language allows for these listed products. The intent of Section 5.5.7 was originally to apply to fastener holes. However, as written, the section could have applied to all holes, of all shapes and sizes, in a fire door. Revisions clarify the intent of the section. Page 8 of 43

Page 9 of 31 Second Revision No. 26-NFPA 80-2014 [ Section No. 6.3.1.7 ] 6.3.1.7* Clearances. 6.3.1.7.1* The clearances between the top and vertical edges of the door and the frame and between the meeting edges of doors swinging in pairs shall be 1 8 in. ± 1 16 in. (3.18 mm ± 1.59 mm).clearances dimensions between doors and frames and meeting stiles of paired doors shall be measured on the pull side of the assemblies. 6.3.1.7.2* Clearances shall be measured from the pull face of the door(s).the clearances between the top and vertical edges of the doorhollow metal doors and the frame, and between the meeting edgesstiles of doors swinging in pairs, shall be 1 8 in. ± 1 16 in. (3.18 mm ± 1.59 mm). 6.3.1.7.3 High-pressure decorative laminate (HPDL)-faced doors, 1 3-hour-rated flush wood doors, and stile and rail wood doors installed in hollow metal door frames shall not have clearances greater than 1 8 in. ± 1 16 in. (3.18 mm ± 1.59 mm) between the door and frame and the meeting stiles of paired doors. 6.3.1.7.4* HPDL-faced doors, flush wood doors, and stile and rail wood doors with fire ratings greater than 1 3 hour shall not have clearances greater than 1 8 in. (3.18 mm) between the door and frame, regardless of the door frame construction, and the meeting stiles of paired doors. 6.3.1.7.5* Door leaves constructed of other materials shall not have clearances greater than 1 8 in. (3.18 mm) between the top and vertical edges of doors and meeting stiles of paired doors, unless otherwise permitted in the door frame, door, and latching hardware manufacturers published listings. Supplemental Information File Name 80_SR_26_Annex_A.docx 80_SR_26_Fig._A.6.3.1.7.4.png 80_SR_26_Fig._A.6.3.1.7.png Description Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:57:47 EDT 2014 Page 9 of 43

Page 10 of 31 Committee Statement: The second revision requirements resolves issues that were created by the first revision change, which removed the 1/8-inch maximum clearance for wood fire doors and allowed an additional 1/16-inch clearance. The first revision language does not reference any type of door or door frame construction, allowing the additional clearance for all types of swinging fire doors with builders hardware. There are significant dimensional and design differences between labeled door frames that are constructed of different materials (e.g., hollow metal, press steel, wood, composite, fiberglass reinforced polyester, and aluminum), which might not perform as needed under fire test, or actual fire, conditions. Accordingly, the second revision clarifies the different types of door frame construction and establishes the maximum clearance dimensions for each type door assembly. Response Message: The change made during the First Draft stage was predicated on receiving technical justification from actual fire door testing that supported allowing an additional 1/16-inch clearance for wood fire doors; that testing did not take place during this revision cycle. When and if that testing takes place, provided it proves the additional clearance is acceptable, the committee may seek to issue a change to the document in the form of a tentative interim amendment (TIA) or as a change to the 2019 edition of NFPA 80. Page 10 of 43

A.6.3.1.7 The clearance dimension between the door(s) and the door frame affects the assembly s ability to form a suitable barrier under fire conditions. NFPA 252, UL 10B, Standard for Safety Fire Tests of Door Assemblies, and UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies, specify the clearance dimensions between the doors and frames and the meeting stiles of paired doors to be no greater than 1/8 in. (3.18 mm) for door assemblies subjected to fire tests conducted by one of the nationally recognized testing laboratories, regardless of the door or frame material; no over-tolerance for the clearance dimension is permitted. When the clearance gaps along the vertical and top edges of doors and between meeting stiles of paired doors exceed the prescribed dimensions, the assembly s ability to perform like the test unit is reduced and the assembly should not be expected to provide the same level of protection. Another element that affects the performance of a fire door assembly is the door stop on the frame -- the portion of the frame that door leaf closes against. Typically, door frames that are constructed of hollow metal materials (e.g., 18, 16, and 14 gage steel) have an integral door stop that is 5/8 in. (15.88 mm) high. Other types of labeled door frames have door stops that range between 1/2 in. (12.7 mm) to 5/8 in. (15.88 mm). When the clearance between the door and frame is greater than 1/8 in. (3.18 mm) and the height of the door stop is less than 5/8 in. (15.88 mm), the doors might not be adequately supported under fire conditions, causing the assemblies to fail prematurely. The clearance dimension between the edges of the doors and the door frames affect the amount of latch bolt engagement of the latching door hardware devices. When the clearance between the door and frame is too great, the latching hardware devices might not be able to positively latch and hold the doors closed under fire conditions. (See Figure A.6.3.1.7. ) <Insert Figure A.6.3.1.7> Figure A.6.3.1.7 Category A Positive Pressure Tested Flush Wood Door Installed in a Typical Hollow Metal Door Frame with 5/8 in. (15.88 mm) High Door Stop. A.6.3.1.7.1 See Figure A.6.3.1.7.1 for more information regarding clearances and the pull face of the door assembly. The clearance dimension along the vertical edges and across the tops of doors and the door frames and between meeting stiles of paired doors should not exceed the maximum dimension or be less than the minimum dimension specified in 6.3.1.7.2 through 6.3.1.7.5 when measured at any point. Figure A.6.3.1.7.1 Pull Face of a Swinging Pair of Doors. Page 11 of 43

A.6.3.1.7.2 Hollow metal fire doors are comprised of 20 (0.8 mm), 18 (1.0 mm), 16 (1.3 mm), and 14 (1.7 mm) gage steel face sheets that are required to be installed in hollow metal door frames or channel iron frames. The steel face sheets rapidly expand when subjected to the extreme temperatures of a fire; therefore, a minimum clearance of 1/16 in. (1.59 mm) between the doors and frames and meeting stiles of paired doors is required to allow for the expansion of the doors. Due to the expansion properties of hollow metal fire doors, the clearance dimension between the doors and frame and meeting stiles of paired doors is permitted to exceed 1/8 in. (3.18 mm) by no more than 1/16 in. (1.59 mm) under normal operating conditions. A.6.3.1.7.4 When wood fire doors are subjected to the extreme temperatures of a fire, the doors shrink in size, rather than expand, as the moisture in the wood evaporates, reducing the need for a minimum clearance dimension requirement between the doors and frames and meeting stiles of paired doors. A minimal amount of clearance is needed for operational purposes. Wood fire doors with mineral core construction (e.g., 3/4 hour, 1 hour, and 1 1/2 hour ratings) are comprised of outer hardwood vertical stiles that are nominally 1/2 in. (12.7 mm) to 5/8 in. (15.88 Page 12 of 43

mm) thick (before prefitting/trimming the door in height and width) and laminated to inner highdensity material stiles that are approximately 1 in. thick. Consequently, since the hardwood outer stiles are subject to being consumed during a fire, the maximum clearance dimension between the doors and frames and the meeting stiles of paired doors should be not be greater than 1/8 in. (3.18 mm). Category A positive pressure rated mineral fire doors usually include a layer of intumescent material laminated between the outer wood stile and the inner high density material stile. (See Figure A.6.3.1.7 and Figure A.6.3.1.7.4. ) <Insert A.6.3.1.7.4> Figure A.6.3.1.7.4 Typical Internal Construction of Mineral Core, Category A Positive Pressure Flush Wood Doors (actual dimensions and composition of individual components vary by manufacturer). A.6.3.1.7.5 Other materials used in the production of labeled fire doors include fiberglass reinforced polyester (FRP) and aluminum. In the case of the latter, some models of swinging fire doors are manufactured as units that are comprised of the door frame, door(s), pivots, and glazing materials. Latching hardware and closing devices are usually separate components from other manufacturers. Page 13 of 43

Page 14 of 43

Page 15 of 43

Page 11 of 31 Second Revision No. 7-NFPA 80-2014 [ New Section after 6.4.8 ] 6.4.9 Thresholds. When used, thresholds shall be noncombustible or listed. Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Submittal Date: Tue Sep 30 19:21:55 EDT 2014 Committee Statement: Response Message: With the addition and clarification of the definitions of sills and thresholds, limitations on the use of thresholds for swinging doors need to be added. Page 16 of 43

Page 12 of 31 Second Revision No. 20-NFPA 80-2014 [ Section No. 17.1.2.1 ] 17.1.2.1 Fire windows shall be tested in accordance with NFPA 257andor ANSI/UL 9, Standard for Fire Tests of Window Assemblies, for the required fire protection rating of the window opening. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:05:38 EDT 2014 Committee Statement: Response Message: Editorial clarification. Windows are tested to either NFPA 257 or UL 9, not both. Page 17 of 43

Page 13 of 31 Second Revision No. 13-NFPA 80-2014 [ Section No. 19.5 ] 19.5* Periodic Testing. 19.5.1 Testing Frequency. Each damper shall be tested and inspected 1 year after acceptance testing. 19.5.1.1 The test and inspection frequency shall then be every 4 years, except in buildings containing a hospital, where the frequency shall be every 6 years.each damper shall be tested and inspected 1 year after acceptance testing. 19.5.1.2 The test and inspection frequency shall then be every 4 years, except in buildings containing a hospital, where the frequency shall be every 6 years. 19.5.2 Periodic Testing for Fusible Link Operated DampersTest Method. 19.5.2.1 For other than dynamic fire dampers, the fan shall be in the off position during testing.all tests shall be completed in a safe manner by personnel wearing personal protective equipment. 19.5.2.2* Periodic Testing for Fusible Link Operated Dampers. The fusible link shall be removed with the damper in the full-open position. 19.5.2.2.1 Fusible links or other moveable parts shall not be painted or coated, unless listed by the testing agency. 19.5.2.2.2 The fan shall be permitted to be shut off during testing. 19.5.2.2.3* The fusible link shall be removed or activated with the damper in the fully open position. 19.5.2.2.4 With the fusible link removed or activated, the damper shall close completely without assistance. 19.5.2.2.5 Where the damper is designed with a latch to hold the damper in the fully closed position, the operation of the latch shall be confirmed. 19.5.2.2.6 At the completion of the test, the damper shall be returned to the fully open position, and the fusible link shall be reinstalled or replaced. 19.5.2.2.7 If the link appears damaged, it shall be replaced with a functionally equivalent link. 19.5.2.2.8 At the completion of the test, it shall be verified that the damper is unobstructed and in a fully operational mode. 19.5.2.3 Periodic Testing for Dampers that Do Not Use a Fusible Link to Operate. Once the fusible link is removed, it shall be verified that the damper closes completely without assistance. 19.5.2.3.1* General. Fans shall not be permitted to be shut down during the test. 19.5.2.3.2 Dampers with Motorized Actuators. Testing of dampers with actuators shall comply with the following procedure: Page 18 of 43

Page 14 of 31 (1) Visually confirm that the damper is in the fully open position. (2) Verify that all obstructions, including hands, are out of the path of the damper blades and then remove electrical power or air pressure from the actuator to allow the actuator s spring return feature to close the damper. (3) Visually confirm that the damper closes completely. (4) Reapply electrical power or air pressure to reopen the damper. (5) Visually confirm that the damper is in the fully open position. 19.5.2.4 Confirmation that the damper latches properly shall be verified where the damper is designed with a latch to hold the damper in the full-closed position. 19.5.2.5 The damper shall be returned to the full-open position and the fusible link shall be replaced. Where the link appears damaged, it shall be replaced with a functionally equivalent fusible link. 19.5.3 Documentation. 19.5.3.1 Testing of dampers with position indication wired to indication lights, control panels, or Building Automation System (BAS) shall comply with the following procedure: The signal from the damper s position indication device shall be used to confirm that the damper is in the full-open position. The damper shall be commanded to the closed position. The signal from the damper s position indication device shall be used to confirm that the damper reaches its full-closed position. The damper shall be commanded to the open position. The signal from the damper s position indication device shall be used to confirm that the damper reaches its full-open position. All inspections and testing shall be documented, indicating the location of the damper, date of inspection, name of inspector, and deficiencies discovered. The documentation shall have a space to indicate when and how the deficiencies were corrected. 19.5.3.2 Testing for Dampers Without Position Indication. Testing of dampers without position indication shall comply with the following procedure: It shall be confirmed visually that the damper is in the full-open position. It shall be verified that all obstructions, including hands, are out of the path of the damper blades and then electrical power or air pressure shall be removed from the actuator to allow the actuator s spring return feature to close the damper. It shall be confirmed visually that the damper closes completely. Electrical power or air pressure shall be reapplied to reopen the damper. It shall be confirmed visually that the damper is in the full-open position. All documentation shall be maintained for at least three test cycles and made available for review by the AHJ. 19.5.3.3 Periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105. 19.5.4 Documentation. Page 19 of 43

Page 15 of 31 19.5.4.1 All inspections and testing shall be documented, indicating the location of the ceiling radiation damper, fire damper, or combination fire/smoke damper; date of inspection; name of inspector; and deficiencies discovered. 19.5.4.2 The documentation shall have a space to indicate when and how the deficiencies were corrected. 19.5.5 All documentation shall be maintained and made available for review by the AHJ. 19.5.6 Periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105. 19.5.7 The damper frame shall not be penetrated by any foreign objects that would affect fire damper operations. 19.5.8 The damper shall not be blocked from closure in any way. 19.5.9 The fusible link shall be reinstalled after testing is complete. 19.5.9.1 If the link is damaged or painted, it shall be replaced with a link of the same size, temperature, and load rating. 19.5.10 All inspections and testing shall be documented, indicating the location of the ceiling radiation damper, fire damper, or combination fire/smoke damper, date of inspection, name of inspector, and deficiencies discovered. 19.5.10.1 The documentation shall have a space to indicate when and how the deficiencies were corrected. 19.5.11 All documentation shall be maintained and made available for review by the AHJ. 19.5.12 Periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105. Supplemental Information File Name 80_SR_13_Annex_A.docx 80_SR_13_Section_19.5_edited.docx Description Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 13:27:23 EDT 2014 Page 20 of 43

Page 16 of 31 Committee Statement: The revised provisions for the periodic inspection and testing of fire dampers is a results of a task group that was assembled after the First Draft meeting to continue the work of addressing current industry issues related to the this issue. The frequencies for inspection have not changed, but additional clarification has been provided related to the test method for both dampers operated by a fusible link and those that to not use a fusible link to operate. The new text will provide necessary clarification as to what steps need to be taken during the inspection and testing; guidance that was not provided in earlier editions of NFPA 80. Response Message: Public Comment No. 9-NFPA 80-2014 [Section No. 19.5.3] Public Comment No. 10-NFPA 80-2014 [Section No. 19.5.3.1] Public Comment No. 11-NFPA 80-2014 [Section No. 19.5.3.1] Page 21 of 43

A.19.5.2.2.3 Care should be taken to ensure that there are no obstructions, including hands, in the path of the damper blades before the fusible link is removed. A.19.5.2.3.1 Where static dampers are used and the system is designed to shut down upon detection, the fans should be permitted to be shut down during testing. Page 22 of 43

19.5* Periodic Testing. 19.5.1 Testing Frequency. 19.5.1.1 Each damper shall be tested and inspected 1 year after acceptance testing. 19.5.1.2 The test and inspection frequency shall then be every 4 years, except in buildings containing a hospital, where the frequency shall be every 6 years. 19.5.2 Test Method. 19.5.2.1 All tests shall be completed in a safe manner by personnel wearing personal protective equipment. 19.5.2.2 Periodic Testing for Fusible Link Operated Dampers. 19.5.2.2.1 Fusible links or other moveable parts shall not be painted or coated, unless listed by the testing agency. 19.5.2.2.2 The fan shall be permitted to be shut off during testing. 19.5.2.2.3* The fusible link shall be removed or activated with the damper in the fully-open position. 19.5.2.2.4 With the fusible link removed or activated, the damper shall close completely without assistance. 19.5.2.2.5 Where the damper is designed with a latch to hold the damper in the fully-closed position, the operation of the latch shall be confirmed. 19.5.2.2.65 At the completion of the test, the damper shall be returned to the fully - open position, and the fusible link shall be reinstalled or replaced. 19.5.2.2.76 If the link appears damaged, it shall be replaced with a functionally equivalent link. 19.5.2.2.87 At the completion of the test, it shall be verified that the damper is unobstructed and in a fully operational mode. 19.5.2.3 Periodic Testing for Dampers that do Not Use a Fusible Link to Operate. 19.5.2.3.1* General. Fans shall not be permitted to be shut down during the test. 19.5.2.3.2 Dampers with Motorized Actuators. Testing of dampers with actuators shall comply with the following procedure: (1) Visually confirm that the damper is in the fully -open position. Page 23 of 43

(2) Verify that all obstructions, including hands, are out of the path of the damper blades and then remove electrical power or air pressure from the actuator to allow the actuator s spring return feature to close the damper. (3) Visually confirm that the damper closes completely. (4) Reapply electrical power or air pressure to reopen the damper. (5) Visually confirm that the damper is in the fully -open position. 19.5.3 Documentation. 19.5.3.1 All inspections and testing shall be documented, indicating the location of the damper, date of inspection, name of inspector, and deficiencies discovered. The documentation shall have a space to indicate when and how the deficiencies were corrected. 19.5.3.2 All documentation shall be maintained for at least three test cycles and made available for review by the AHJ. 19.5.3.3 Periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105. Page 24 of 43

Page 17 of 31 Second Revision No. 9-NFPA 80-2014 [ New Section after 20.9.5.2 ] Chapter 21 Fire Protective Curtain Assemblies 21.1 General. 21.1.1* This chapter shall cover the installation, inspection, testing, and maintenance of fire protective curtain assemblies installed to protect vertical openings. 21.1.2* Fire protective curtain assemblies shall be fire tested in accordance with UL 10D, Fire Tests for Fire Protective Curtain Assemblies. 21.1.3 Fire protective curtain assemblies shall be identified by a label attached to the bottom bar of the curtain. See 3.2.3. 21.2 Mounting of Fire Protective Curtain Assemblies. 21.2.1 Fire protective curtain assemblies shall be mounted to supporting construction in accordance with their listing and with the manufacturer s installation instructions. 21.2.2 Items that are not a part of a fire protective curtain assembly shall not be field attached to any component of a fire protective curtain assembly. 21.2.3 Access to and clearances between surrounding construction and a fire protective curtain assembly shall allow for required testing and maintenance. 21.3 Assembly Components. 21.3.1 Fire protective curtain assemblies shall be either self-closing or automatic-closing. 21.3.1.1 Fire protective curtain assemblies shall not have a delay in the initiation of closing of more than 10 seconds. 21.3.1.2 Fire protective curtain assemblies shall have an average closing speed of not less than 6 in./sec (152 mm/sec) or more than 24 in./sec (610 mm/sec). 21.3.2* Curtains shall be permitted to be sewn by qualified persons in accordance with the manufacturer s instructions. 21.4 Power Operators. Power operators shall be provided with a standby or emergency power source to close the curtain upon activation or shall be capable of closing the curtain without power. 21.5 Installation. Fire protective curtain assemblies shall be installed in accordance with their listing and with the manufacturer's installation instructions. 21.6 Inspection, Testing, and Maintenance. 21.6.1 Following completion of installation, fire protective curtains shall be inspected and tested in accordance with Section 21.7. 21.6.2 A record of all inspections and testing shall be signed by the inspector and kept for inspection by the AHJ. Page 25 of 43

Page 18 of 31 21.6.2.1 Records of acceptance testing following completion of installation shall be retained for the life of the assembly. 21.6.2.2 Records of periodic inspections and testing shall be retained for a period of at least 3years. 21.6.2.3 The records shall be on a medium that will survive the retention period. Paper or electronic media shall be permitted. [72:14.6.2.3] 21.6.2.4 A record of all inspections and testing shall be provided that includes, but is not limited to, the following information: (1) Date of inspection (2) Name of facility (3) Address of facility (4) Name of person(s) performing inspections and testing (5) Company name and address of inspecting company (6) Signature of inspector of record (7) Individual record of each inspected and tested fire protective curtain assembly (8) Opening identifier and location of each inspected and tested fire protective curtain (9) Type and description of each inspected and tested fire protective curtain (10) Verification of visual inspection and functional operation (11) Listing of any deficiencies 21.6.2.5 Upon completion of maintenance work, fire protective curtain assemblies shall be inspected and tested in accordance with Section 21.7. 21.7 Acceptance Testing. 21.7.1 Acceptance testing of fire protective curtains assemblies shall be performed by a qualified person with knowledge and understanding of the operating components of the type of assembly being subject to testing. 21.7.2 Before testing, a visual inspection shall be performed to identify any damaged or missing parts that can create a hazard during testing or affect operation or resetting. 21.7.3 Acceptance testing shall include the closing of the fire protective curtain assembly by all means of activation. 21.7.4 A record of these inspections and testing shall be made in accordance with Section 21.6. 21.7.5 The following items shall be verified: (1) Labels are clearly visible and legible. (2) No open holes or breaks exist in surfaces of the curtain or in the stitching of the curtain. (3) Curtain, guides, and coil are aligned, level, plumb, and true. Page 26 of 43

Page 19 of 31 (4) Mounting and assembly bolts are intact and secured. (5) Attachments to jambs are with bolts, expansion anchors, or as otherwise required by the listing. (6) Smoke detectors, if equipped, are installed, operational, and in accordance with NFPA 72. (7) No parts are missing or broken. (8) Auxiliary hardware items that interfere or prohibit operation are not installed on the curtain or frame. (9) No field modifications to the fire protective curtain assembly have been performed that void the label. (10) Fire protective curtain assemblies have an average closing speed of not less than 6 in./sec (152 mm/sec) or more than 24 in./sec (610 mm/sec). 21.7.6 Fire protective curtain assemblies shall be drop-tested twice. 21.7.6.1 The first test shall be to check for proper operation and full closure. 21.7.6.2 A second test shall be done to verify that the automatic-closing device has been reset correctly. 21.7.7 Fusible links, release devices, and other moveable parts shall not be painted or coated with other materials that could interfere with the operation of the assembly. 21.8 Closing Devices. 21.8.1 Fire protective curtain assemblies shall be inspected and tested to check for proper operation and full closure. 21.8.2 Resetting of the automatic-closing device shall be performed in accordance with the manufacturer s instructions. 21.9 Periodic Inspection and Testing. 21.9.1 Periodic inspections and testing of fire protective curtain assemblies shall be performed not less than annually. 21.9.2 As a minimum, the provisions of Section 21.7 shall be included in the periodic inspection and testing procedure. 21.10 Maintenance. 21.10.1 Repairs shall be made, and defects that could interfere with operation shall be corrected without delay. 21.10.2 Any breaks in the face covering of curtains shall be repaired in accordance with manufacturer s requirements without delay. 21.10.3 Where a fire protective curtain assembly or any part of its appurtenances is damaged to the extent that it could impair the assembly s proper emergency function, the following actions shall be performed: (1) The fire protective curtain assembly or any part of its appurtenances shall be repaired with labeled parts or parts obtained from the original manufacturer. (2) The fire protective curtain assembly shall be tested to ensure emergency operation and closing upon completion of the repairs. Page 27 of 43

Page 20 of 31 21.10.4 If repairs cannot be made with labeled components or parts obtained from the original manufacturer, the fire protective curtain assembly or appurtenances shall be replaced. Supplemental Information File Name Chapter_21_FINAL.docx 80_SR_9_Annex_A.docx Description Word document of new Chapter 21, if needed. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 12:21:50 EDT 2014 Committee Statement: Fire protective curtain assemblies are being used in the field to protect openings in fire rated assemblies, thus, NFPA 80 should address these opening protectives to provide guidance and ensure proper protection of the openings. New Chapter 21 represents the work of a task group that was established during the First Draft meeting to further explore and evaluate the necessary requirements for fire and smoke curtains. The language is an expansion of the work completed at the First Draft meeting and is in response to the developed committee inputs. The task group worked together to develop requirements that address the installation, inspection, and testing of these fire and smoke curtain products. An associated definition, and Annex material were also developed to clarify the application of the new chapter. Response Message: Public Comment No. 42-NFPA 80-2014 [New Section after 20.9.5.2] Page 28 of 43

Chapter 21 Fire Protective Curtain Assemblies 21.1 General 21.1.1* This chapter shall cover the installation, inspection, testing, and maintenance of fire protective curtain assemblies installed to protect vertical openings. 21.1.2* Fire protective curtain assemblies shall be fire tested in accordance with UL 10D, Fire Tests for Fire Protective Curtain Assemblies. 21.1.3 Fire protective curtain assemblies shall be identified by a label attached to the bottom bar of the curtain. See 3.23 21.2 Mounting of Fire Protective Curtain Assemblies 21.2.1 Fire protective curtain assemblies shall be mounted to supporting construction in accordance with their listing and with the manufacturer s installation instructions. 21.2.2 Items that are not a part of a fire protective curtain assembly shall not be field attached to any component of a fire protective curtain assembly. 21.2.3 Access to, and clearances between, surrounding construction and a fire protective curtain assembly shall allow for required testing and maintenance. 21.3 Assembly Components 21.3.1 Fire protective curtain assemblies shall be either self-closing or automatic-closing. 21.3.1.1 Fire protective curtain assemblies shall not have a delay in the initiation of closing of more than 10 seconds. 21.3.1.2 Fire protective curtain assemblies shall have an average closing speed of not less than 6 in/sec (152 mm/sec) or more than 24 in/sec (610mm/sec). 21.3.2* Curtains shall be permitted to be sewn by qualified persons in accordance with the manufacturer s instructions. 21.4 Power Operators Power operators shall be provided with standby or emergency power source to close the curtain upon activation, or shall be capable of closing the curtain without power. 21.5 Installation Fire protective curtain assemblies shall be installed in accordance with their listing and with the manufacturer's installation instructions. 21.6 Inspection, Testing, and Maintenance 21.6.1 Following completion of installation, fire protective curtains shall be inspected and tested in accordance with 21.7. 21.6.2 A record of all inspections and testing shall be signed by the inspector and kept for inspection by the AHJ. 21.6.2.1 Records of acceptance testing following completion of installation shall be retained for the life of the assembly. 21.6.2.2 Records of periodic inspections and testing shall be retained for a period of at least 3 years. 21.6.2.3 The records shall be on a medium that will survive the retention period. Paper or electronic media shall be permitted. [72:14.6.2.3] 21.6.2.4 A record of all inspections and testing shall be provided that includes, but is not limited to, the following information: (1) Date of inspection (2) Name of facility (3) Address of facility (4) Name of person(s) performing inspections and testing (5) Company name and address of inspecting company (6) Signature of inspector of record (7) Individual record of each inspected and tested fire protective curtain assembly (8) Opening identifier and location of each inspected and tested fire protective curtain (9) Type and description of each inspected and tested fire protective curtain (10) Verification of visual inspection and functional operation (11) Listing of any deficiencies 21.6.2.5 Upon completion of maintenance work, fire protective curtain assemblies shall be inspected and tested in accordance with 21.7. 21.7 Acceptance Testing 21.7.1 Acceptance testing of fire protective curtains assemblies shall be performed by a qualified person with knowledge and understanding of the operating components of the type of assembly being subject to testing. 21.7.2 Before testing, a visual inspection shall be performed to identify any damaged or missing parts that can create a hazard during testing or affect operation or resetting. 21.7.3 Acceptance testing shall include the closing of the fire protective curtain assembly by all means of activation. 21.7.4 A record of these inspections and testing shall be made in accordance with 21.6. 21.7.5 The following items shall be verified: (1) Labels are clearly visible and legible. Page 29 of 43

(2) No open holes or breaks exist in surfaces of the curtain, or in the stitching of the curtain. (3) Curtain, guides, and coil are aligned, level, plumb, and true. (4) Mounting and assembly bolts are intact and secured. (5) Attachments to jambs are with bolts, expansion anchors, or as otherwise required by the listing. (6) Smoke detectors, if equipped, are installed, operational and in accordance with NFPA 72, National Fire Alarm and Signaling Code. (7) No parts are missing or broken. (8) Auxiliary hardware items that interfere or prohibit operation are not installed on the curtain or frame. (9) No field modifications to the fire protective curtain assembly have been performed that void the label. (10) Fire protective curtain assemblies have an average closing speed of not less than 6 in./ sec (152 mm/sec) or more than 24 in./sec (610 mm/sec). 21.7.6 Fire protective curtain assemblies shall be drop-tested twice. 21.7.6.1 The first test shall be to check for proper operation and full closure 21.7.6.2 A second test shall be done to verify that the automatic-closing device has been reset correctly. 21.7.7 Fusible links, release devices, and other moveable parts shall not be painted or coated with other materials that could interfere with the operation of the assembly. 21.8 Closing Devices 21.8.1 Fire protective curtain assemblies shall be inspected and tested to check for proper operation and full closure. 21.8.2 Resetting of the automatic-closing device shall be performed in accordance with the manufacturer s instructions. 21.9 Periodic Inspection and Testing. 21.9.1 Periodic inspections and testing of fire protective curtain assemblies shall be performed not less than annually. 21.9.2 As a minimum, the provisions of 21.7 shall be included in the periodic inspection and testing procedure. 21.10 Maintenance. 21.10.1 Repairs shall be made, and defects that could interfere with operation shall be corrected without delay. 21.10.2 Any breaks in the face covering of curtains shall be repaired in accordance with manufacturer s requirements without delay. 21.10.3 Where a fire protective curtain assembly or any part of its appurtenances is damaged to the extent that it could impair the assembly s proper emergency function, the following actions shall be performed: (1) The fire protective curtain assembly or any part of its appurtenances shall be repaired with labeled parts or parts obtained from the original manufacturer. (2) The fire protective curtain assembly shall be tested to ensure emergency operation and closing upon completion of the repairs. 21.10.4 If repairs cannot be made with labeled components or parts obtained from the original manufacturer, the fire protective curtain assembly or appurtenances shall be replaced. Page 30 of 43

A.21.1.1 Fire protective curtain assemblies are not to be confused with fabric fire safety curtain assemblies that are intended for use specifically on proscenium openings. A.21.1.2 UL 10D, Fire Tests for Fire Protective Curtain Assemblies, covers the evaluation of fire protective curtain assemblies intended to provide supplemental, passive fire protection as part of an engineered fire protection system. Fire protective curtain assemblies provide nonstructural separation only and are not intended to be substituted for structural hourly rated partitions or opening protectives that have been tested for fire endurance and hose stream performance. While products tested to UL 10D are exposed to a standard temperature time curve and the test is a positive pressure test, the test does not include a hose stream test nor does it provide criteria regarding temperature rise on the unexposed surface. Some curtain products might have been tested in accordance with UL 10B, Fire Tests of Door Assemblies, UL 10C, Positive Pressure Fire Tests of Door Assemblies, or NFPA 252. The AHJ should be consulted regarding their suitability for the application in which they are installed. When those products are fire rated for 20 minutes, they might not have been subjected to a hose stream test. A.21.3.2 Sections of a fire protective curtain can be sewn together when such joints are included in the assembly that was tested in accordance with UL 10D. Page 31 of 43

Page 21 of 31 Second Revision No. 23-NFPA 80-2014 [ New Section after A.4.1.2 ] A.4.1.3.2 Depending on the internal construction of wood and composite doors, the bottom edge of the door leaves are permitted to be undercut (trimmed) to create minimal operating clearance between the bottom of the door and the floor. Undercutting the doors in the field might compromise the structural integrity of the doors by removing most or all of the internal bottom rails, voiding the label on the doors. Before undercutting wood or composite doors in the field, installers should verify that the internal construction of the doors will not be compromised. Due to the design of some wood and composite doors, the bottom edges of the doors are not permitted to be trimmed; labels and warranties might be voided by such work. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:22:21 EDT 2014 Committee Statement: Response Message: A committee input was developed during the First Draft meeting regarding clearances under fire doors. At this time, the committee is not prepared to modify the tolerances for clearances in the mandatory portion of the standard until testing or research can confirm the issue. This new annex language provides necessary clarification on the process of undercutting a door, which is done often in the field, and can lead to a void label or degradation of the fire door assembly. Page 32 of 43

Page 22 of 31 Second Revision No. 19-NFPA 80-2014 [ Section No. A.4.8.4.1 ] A.4.8.4.1 The maximum clearance of 3 4 in. (19 mm.) under fire doors as permitted by this standard is the accepted practice in the industry. NFPA 252 is a test standard, not an installation standard, and prescribes clearances and tolerances for swinging doors installed in the test wall opening. The test procedures as specified in NFPA 252 represent a worst-case condition for the fire test. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:04:28 EDT 2014 Committee Statement: Response Message: The last sentence of the section was incorrect and should be removed for clarification. Page 33 of 43

Page 23 of 31 Second Revision No. 17-NFPA 80-2014 [ Section No. A.5.1.4.1 ] A.5.1.4.1 Field modifications beyond the scope of the prescriptive allowances permitted by 4.1.3.2 through 4.1.3.2.5 typically result in voiding the fire rating of the assembly. Paragraph 4.1.4.2.1 5.1.4.1 provides an alternative method whereby proposed modifications can be documented and presented to the labeling agency prior to work commencing. Where the proposed modification(s) are within the parameters of the manufacturer s procedures and will not degrade the fire resistance of the assembly, the labeling agency is permitted to authorize such modifications without a requirement for a subsequent field inspection. Generally, the replacement of hardware components on swinging doors (hinges, pivots, door closers, etc.) is not considered to be a field modification, provided the replacement hardware does not require additional cutting, mortising, or boring into the doors and frames and the hardware meets the criteria specified elsewhere in the standard. Likewise, the installation of surface-mounted items like protection plates is not considered to be field modifications. Cutting doors for vision panels, enlarging existing cutouts for vision panels, and trimming doors in height or width are examples of field modifications. Similarly, installing hardware components that require additional cutting and mortising of the doors or frames are examples of field modifications. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:00:09 EDT 2014 : Change corrects an error in the referenced section. Response Message: Page 34 of 43

Page 24 of 31 Second Revision No. 22-NFPA 80-2014 [ New Section after A.5.2.3.2 ] A.5.2.3.5.2(11) Aftermarket devices that are intended to alter the function and operation of door hardware could violate the listing and degrade the fire protection performance of the doorway. For example, magnetic strips that are marketed to apply over strike plates for quick school lockdowns directly defeat the purpose of the latching to hold the door in the closed position. Manufacturers and listing agencies should be consulted prior making any modifications or adding any devices to fire doors. Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:17:17 EDT 2014 Committee Statement: Response Message: New text clarifies a common issue in the field where aftermarket products may void the listing or degrade the fire protection rating of the door. Text further clarifies additional changes that were made to the standard regarding field modifications during the First Draft stage and last cycle. Page 35 of 43

Page 25 of 31 Second Revision No. 24-NFPA 80-2014 [ Section No. A.6.3.1.1 ] A.6.3.1.1 Door frames might carry a label stating the hourly rating. The rating of the installed assembly should carry the rating of the door or the door frame, whichever is less. Door frames are constructed of hollow metal, pressed steel, channel iron, aluminum, wood, and composite metals. (See Figure A.6.3.1.1.) Figure A.6.3.1.1 Pressed Steel Door Frame with Snap-On Casing/Trim. Supplemental Information File Name A.6.3.1.1.png Description Figure A.6.3.1.1 (please add caption as follows: Pressed Steel Door Frame with Snap-On Casing/Trim) Submitter Full Name: Kristin Bigda Organization: National Fire Protection Assoc Submittal Date: Mon Oct 06 15:27:17 EDT 2014 : Text provides advisory language on the materials of door frames. Response Message: Page 36 of 43