Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Similar documents
Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger

Case 13 Food Storage & Processing Center

Case 8 Basic Performance of Screw Compressor

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Partial Load Performance Of Refrigeration System

(2) 325 tpd York Chlorine Liquefier Systems

Chapter 1 Preface & General

Chapter 4 Compressors Overview & System Annual Power Consumption

Energy Use in Refrigeration Systems

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Refrigeration and Boil Off Compression Systems for NGL Export Facilities

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Copy Right By: Thomas T.S. Wan

c o n d e n s e r Glossary of Terms

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

System Design, Commissioning, Operation

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

MaxiCoking Technology Breakthrough Technology for Improved Existing Delayed Coker Performance

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

A Treatise on Liquid Subcooling

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

A STUDY OF TWO STAGE CASCADE REFRIGERATION

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

PACKAGED AIR COOLED Product Data Catalog

Chapter-8 Capacity Control of Refrigeration Systems

Technical Bulletin (TB-0037)

LOW RECIRCULATION RATE EVAPORATORS

Air-Cooling Evaporators

Refrigeration Systems and Accessories

The Refrigeration Cycle

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

TWO- AND THREE-STAGE CASCADE REFRIGERATION SYSTEM By: Paul B. Reed

The Refrigeration Cycle

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

HEAT EXCHANGERS Maximize Thermal Efficiency with LaZerWeld Plate Heat Exchangers. For Industrial Refrigeration

Liebert CSU3000 Chiller

CO2 TRANSCRITICAL BOOSTER SYSTEMS

WHAT IS AN ENERGY BALANCE AND WHY SHOULD I CARE?

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

BASCO TYPE T and TC MOISTURE SEPARATORS and TRAP. ...world leaders in heat transfer technology

BASCO TYPE ES EXTENDED SURFACE PLATE FIN HEAT EXCHANGERS. ...world leaders in heat transfer technology

REFRIGERATION CYCLES

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Sporlan Valve Division Parker Hannifan/CIC Group

Refrigerator and Heat Pump Objectives

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

USING THE P-T CARD AS A SERVICE TOOL

MicroTech Series-200 Flooded Screw Chiller

APPLICATION OF HYDROCARBON REFRIGERANTS IN LOW TEMPERATURE CASCADE SYSTEMS

Form No: MS0454A. Products That Perform...By People Who Care. Screw Compressor Air Cooled Flooded Chillers. HXAC Series. R134a. 60 Hz.

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

YOUR BASIC REFRIGERAION SYSTEM SVASD MAY 26, 2011

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Chapter 9. Refrigeration and Liquefaction

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Application Engineering

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Hydrocarbon Recovery. Chapter 12 Based on presentation by Prof. Art Kidnay

MicroTech Series 200 Centrifugal Chiller

Midwest Industrial Initiative Webinar: Industrial Refrigeration

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

ORGANISATION AFRICAINE DE LA PROPRIETE INTELLECTUELLE N Titre :Liquefied natural gas plant with ethylene independent heavies recovery system.

Rotary Metal Parts Treatment System; Rotary Metal Parts Treater RMPT Effluent Heater MPT Quench Tower Rotary Metal Parts Treater

VAPOUR RECOVERY DURING FUEL LOADING. Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

AFHX Series 60Hz. Air Cooled Screw Flooded Chillers Cooling Capacity: 208 to 557 TR (732 to 1959 kw) R134a. Products that perform...

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Chapter 11 REFRIGERATION CYCLES

KCC Centrifugal Fan Air Cooled Condensers

Evaporators. Direct Expansion Flooded Recirculated Over Feed

Evaporation System: Types and Design Aspects

Water-Cooled Dual Compressor Screw Chiller

Refrigeration Plant Information. We Speak Hockey 365

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 = 90 F. compressor. condenser. 5 evaporator 1. evap

Thermodynamics II Chapter 5 Refrigeration

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Superheat charging curves for technicians

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support


SARAVEL Minichill PACKAGED LIQUID CHILLERS

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

HEAT EXCHANGER FORMULAS & EXAMPLE

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

Technical Paper #2. Refrigeration Piping: A Simplified Guide to a Modern Approach

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Air-Cooled Global Chiller

HVAC Equipments and Systems

Transcription:

Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool the LPG (Liquefied Petroleum Gas) liquid for the purpose of avoiding flash gas during loading and unloading of the LPG liquid. It is the preference of the user to use R-134a refrigerant for the high stage and R-23 refrigerant for the low stage instead of using R-1270 (Propylene) for the high side and R- 1150 (Ethylene) for the low stage as the logical refrigerant selection for cascade systems for most hydrocarbon industries. The system is required to provide fast pull-down during start-up after shut-down, therefore, liquid subcooling and suction gas heat exchanger is not used for the low stage compressor suction. The superheat gas might flash all the liquid in the heat exchanger and might sometimes delaying the pull down process during start-up. Nickel steel is to be used for the low stage evaporator. Cast steel casing is required for the screw compressor for the low stage circuit. Related Technical Data and Information for the Case: The refrigeration system is to cool 237,510 Lbs/Hr of LPG from -50 to -62, 15 Psia. The average specific gravity and the specific heat at the average temperatures for the LPG liquid are: Estimate specific gravity = 0.6 Specific heat = 0.4334 Cooling water is available, 85 in and 95 out. Maximum ambient design temperature: 110 Fouling factor for all heat exchangers: 0.001 Electrical classification for the area is Class I, Group D, Division II.

Power supply: 4,160-3-60 460-3-60 120-1-60 Actually, the evaporative temperature for this case is within the range of one refrigerant using compound system. However, because the user prefers to have positive pressure in the refrigeration system, therefore cascade system with R-23 refrigerant is used for the low stage. R-134a is selected over the R-717 and R-22 for the high stage as suggested by the user. System Design Logic and Approach: The working principal of a cascade system is to use two separate working refrigerants linked together through a cascade condenser as shown in Figure 16-1. Each of the two refrigerants is contained in a separate complete independent refrigerant circuit. The cascade condenser performs as the condenser for the low stage and as the evaporator for the high stage. Figure 16-1 Principal of Cascade Refrigeration system

The refrigerant selected for the low stage is a low temperature refrigerant which is having higher pressure and smaller specific volume at the low temperature. In this case, the refrigerant for the low stage circuit is R-23, the liquid refrigerant absorbs the heat from the evaporator, evaporated and the vapor is compressed by the low stage compressor, the refrigerant vapor is condensed in the tube side of the cascade condenser. The refrigerant for the high stage is R-134a, the R-134a liquid in the evaporator, the shell side of the cascade condenser, absorbs the heat, the evaporated gas is compressed by the high stage compressor and is condensed in the water cooled condenser at the high stage. In accordance with the guide line given by the user, the construction of the shell-and-tube evaporator heat exchanger for the LPG liquid subcooling shall be TEMA-B U-tube design. The leaving LPG shall be -62 the fouling factor is 0.001, the evaporative temperature of -76ºF is assumed for the evaporator. This shall provide a temperature difference of 14ºF between the leaving LPG liquid and the ET for the heat transfer. Therefore: ET = -76 for the low stage LPG cooler. LPG liquid subcooling heat load: Specific Gravity = 0.6 Specific heat = 0.4334 Cooling 237,510 Lbs/Hr. of LPG from -50 to -62 Lbs/Min flow 237,510/60 GPM flow = ------------------------- = ---------------------- = 792 GPM 8.33 x Sp.Gr. 8.33 x 0.6 GPM TR = --------- x S.G. x C p x T 24 792 = -------- x 0.6 x 0.4336 x 12 24 = 103 TR The cooling water is available is 85 in and the design leaving cooling water temperature is 95. The condensing temperature for the high stage is designed at 108

The next step is to fix the CT and ET for the Cascade Condenser. As a general guide for cascade system, it is to design the low stage system for a maximum design working pressure of not more than 300 Psig and the expansion tank is sized to have extra volume for 250 Psig storage pressure at design ambient temperature of 110ºF. If the design condensing temperature for R-23 is to be designed for 15ºF, use 10ºF temperature difference between CT and ET, the evaporative temperature for R-134a high stage system is to be 5ºF. Low Stage Refrigeration Circuit: The P-H diagram for the low stage refrigeration system is shown in Figure 16-2: Figure 16-2 P-H Diagram for the Low Stage Refrigeration System Operating conditions and specifications for the evaporator for LPG subcooling: Heat load: Heat Exchanger design: Material: Construction: Tube Side: Tubes: LPG flow: LPG inlet & outlet: 103 TR Flooded, Full Bundle with surge drum 3-1/2% nickel steel TEMA-B 16 BWG 237,510 Lbs/Hr -50 to -62

Inlet pressure: 15 Psia Average specific gravity: 0.6 Average specific heat: 0.4334 Estimate specific gravity: 0.6 Specific heat: 0.4334 Fouling factor: 0.001 Design working pressure: 150 Psig Shell Side: Refrigerant: R-23 Refrigerant feed: Flooded Evaporative temperature: -76ºF Liquid temperature to shell: 15ºF Design working pressure: 300 Psig The operating conditions for low stage screw compressor unit and computer selection input data: Capacity: 103 TR Refrigerant: R-23 Evaporative Temperature: -76ºF Condensing Temperature: 15ºF Suction pressure drop: 0.5 Psi Suction superheat: 15ºF Discharge pressure drop: 1.0 Psi Compressor speed: 3,550 rpm Oil pump: Recycling Oil cooling: Water cooled Compressor unit selected: Model Number: Power consumption: Oil cooling heat removal: Compressor construction: Casing: Design working pressure: RW-100 354 BHP 20,800 Btu/Hr. cast steel 300 Psig The refrigerant flow diagram for this low stage R-23 system is shown in Figure 16-3. An expansion tank is used for the R-23 low stage system. The expansion tank is connected to the suction side of the low stage compressor; it is to provide additional volume for the low stage refrigerant to expand during shutdown when the system is warmed up to room temperature.

Figure 16-3 Refrigerant Flow Diagram for the R-23 Low Stage System A surge receiver is for the purpose of providing liquid seal; a solenoid valve connecting between the high side and the low side of the R-23 circuit is to equalizing the pressure between the high side and the low side of the system. The design working pressure for the low stage system is 300 Psig. The expansion tank is sized to have enough volume for R-23 stand-by pressure of 250 Psig at 110ºF maximum ambient temperature. High Stage R-134a Refrigeration Circuit: Heat load for the high stage refrigeration Circuit is the total heat rejection from the low stage refrigeration Circuit. Heat rejection from low stage R-23 system = 103 TR + Heat input from low stage

354 x 2545 20,800 = 103 + ------------------------------- 12,000 = 103 + 176.3 = 176.3 TR Heat load for the high stage circuit = 176.3 TR The ET is 5ºF and the CT is 108ºF. The high stage R-134a system is to be equipped with economizer for the lowering of power consumption. The economizer is to be shell-andtube liquid subcooling design. The operating conditions for high stage screw compressor unit and computer selection input data: Capacity: 176.3 TR Refrigerant: R-134a Evaporative Temperature: 5ºF Condensing Temperature: 108ºF Suction pressure drop: 0.5 Psi Suction superheat: 10ºF Discharge pressure drop: 1.0 Psi Compressor speed: 3,550 rpm Oil pump: Recycling Oil cooling: Water cooled Economizer: Shell-and-tube P.D. for economizer: 5 Psi Approach for economizer: 10ºF Compressor unit selected: Model Number: Power consumption: Oil cooling heat removal: Economizer ET: Liquid to evaporator: High stage compressor construction: Casting: Design working pressure: RW-222 Economizing 351 BHP 175,000 Btu/Hr. 53.5ºF 63.5ºF Maker standard 200 Psig The P-H diagram for the high stage R-134a refrigeration circuit is shown in Figure 16-4:

Figure 16-4 P-H Diagram for R-134a High Stage Refrigeration Circuit The design working pressure for the high stage refrigeration system is 200 Psig. The heat rejection to the water cooled condenser: = 176.3 x 12,000 + 351 x 2545 175,000 = 2,833,895 Btu/Hr Cooling water flow for condenser: Btu/Hr GPM = ---------------------------- 499.8 x T 2,833,895 = ------------------------------ 499.8 x (95 85)

= 567 GPM The refrigerant flow diagram for the high stage refrigeration system is shown as in the Figure 16-5: Figure 16-5 Refrigerant Flow Diagram for the R-134a Refrigeration System Operating conditions and specifications for the water cooled condenser for the high stage refrigeration circuit: Heat load: Construction: Tube Side: Tubes: Material: 2,833,895 Btu/Hr TEMA-B 16 BWG Carbon steel

Water flow: 567 GPM Water inlet & outlet temperature: 85 to 95 Design working pressure: 150 Psig Shell Side: Refrigerant: R-134a condensing temperature: 108ºF Design working pressure: 200 Psig The P-H diagram for the cascade system is shown in Figure 16-6 which is combining the Figure 16-2 and Figure 16-4: Figure 16-6 P-H Diagram for the Cascade System The refrigerant flow diagram for the cascade system is shown in Figure 16-7 which is the combination of the Figure 16-3 and Figure 16-5.

Figure 16-7 Refrigerant Flow Diagram for the Cascade System

Operating conditions and specifications for the cascade condenser: Heat load: 176.3 TR Heat Exchanger design: Flooded, Full Bundle with surge drum Construction: TEMA-B Tube Side: Tubes: 14 BWG Material: Carbon steel Gas: R-23 R-23 flow: 320 Lbs/Min Condensing temperature: 15 Leaving R-23 temperature: 15 Inlet pressure: 279 Psia Fouling factor: 0.001 Design working pressure: 300 Psig Shell Side: Refrigerant: R-134a Refrigerant feed: Flooded Liquid to evaporator temperature: 63.5ºF Liquid pressure to evaporator: 156.5 Psia Evaporative temperature: 5ºF Design working pressure: 200 Psig