Performance Assessment of Water Cooled Condenser Refrigeration System

Similar documents
(ME-225) HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Scientific Journal Impact Factor: (ISRA), Impact Factor: Methodology. [Yadav, 3(9): September, 2014] ISSN:

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Fabrication of Hot and Cold Water Dispenser

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

II. OBJECTIVE OF RESEARCH

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Presentation on HVAC: Heating Ventilation Air Conditioning

Refrigeration and Air Conditioning

Enhancement of COP in Vapour Compression Refrigeration System

Design & Fabrication of Hybrid Cooler

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Performance of an Improved Household Refrigerator/Freezer

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Design and Fabrication of Water Refrigeration System by Creating Vacuum

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

Modified Air Cooler with Split Cooling Unit

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

EXPERIMENTAL INVESTIGATION ON RECOVERY OF WASTE HEAT FROM WINDOW AIR CONDITIONER

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Performance Evolution of Domestic Refrigerator Using LPG Cylinder

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Chapter 11 REFRIGERATION CYCLES

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

CHAPTER 1 INTRODUCTION

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Sarthak Thakar, 2 R.P.Prajapati 1

Chapter 11 REFRIGERATION CYCLES

Thermodynamics II Chapter 5 Refrigeration

Waghmare Tushar Ramrao, D.S.Nakate

Performance Analysis of a Domestic Refrigerator in Malaysia using Experimental Method

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Pressure Enthalpy Charts

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Performance investigation of Air-conditioning system using ejector as expansion device

Reheating Refrigeration System

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

HVAC Fundamentals & Refrigeration Cycle

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Numerical Simulation of Window Air Conditioner

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Fabrication and analysis of instantaneous water cooler by using isobutane as refrigerant

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Evaluation of COP in Refrigeration System by using Different Refrigerants

Design of LPG Refrigeration System

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Cost-Effective COP Enhancement of a Domestic Air Cooled Refrigerator using R-134a Refrigerant

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Performance Optimization of the Evaporative Condenser Design

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

ISSN: [Farooque* et al., 6(5): May, 2017] Impact Factor: 4.116

Air Conditioning Inspections for Buildings Condensers

Adsorption refrigeration system using waste heat

SBS5311 HVACR II Experiment 2: Analysis of the Combined Rankine and Vapour Compression Cycle

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

1.1. SCOPE OF THE WORK:

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

CHAPTER 1 INTRODUCTION

UNIT - 3 Refrigeration and Air - Conditioning

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Transcritical CO2 Bottle Cooler Development

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Transcription:

Energy and Power 2017, 7(3): 70-74 DOI: 10.5923/j.ep.20170703.03 Performance Assessment of Water Cooled Condenser Refrigeration System Sheetal Narayan Shetty *, Prashanth Kamath Department of Mechanical Engineering, Canara Engineering College, Mangalore, India Abstract A large increase in the requirement of energy is the biggest problem faced by the world at present. This has resulted in usage of more and more energy resources which is not a good sign. So there should be actions taken so as to reduce the energy losses from any system and an attempt should be made to utilize maximum amount of the energy supplied by an energy consuming system. Keeping these things in mind a water cooled condenser refrigerator system is developed. In this paper the COP of the refrigerator by using water as the cooling medium instead of air for condenser system is calculated, which is the cooling medium in conventional refrigeration system otherwise. Here comparison is made between the COP of air and water cooled condenser refrigeration system to find the percentage increase in COP. By this it is possible to utilise more part of the energy supplied to the refrigeration system. Keywords Water cooled condenser, Temperature, COP, System 1. Introduction Refrigerator is a device which extracts heat continuously from the system and dissipate that heat into the surroundings with the help of an external aid like electrically driven compressor which is described in second law of thermodynamics. There are many statements for second law of thermodynamics, but two of them are very important they are, i) Kelvin and Planck Statement- No (heat) engine whose working fluid undergoes a cycle can absorb heat from a single reservoir, deliver an equivalent amount of work, and deliver no other effect. and ii) Clausius Statement- No machine whose working fluid undergoes a cycle can absorb heat from one system, reject heat to another system and produce no other effect. The term Refrigeration is defined as a process of removing heat from a substance and maintaining its temperature well below the atmospheric temperature under controlled conditions [1]. Refrigeration has been adopted from ancient times where they had used method of artificial cooling in ice making; nowadays they are used for preservation of the perishables such as milk, food, drinks, medicines, etc. and indoor air cooling to provide human comfort and cool environment is required in electronic, precision manufacturing and process industries, and also in various other applications like cryogenics, etc. [2]. The application of refrigeration is in plenty of numbers but one of the most important applications of refrigeration has * Corresponding author: shettysheetalnarayan@gmail.com (Sheetal Narayan Shetty) Published online at http://journal.sapub.org/ep Copyright 2017 Scientific & Academic Publishing. All Rights Reserved been the preservation of perishable food products by storing them at lower temperature [3]. In conventional Refrigeration System the condenser is cooled by air which can be free convection or in some cases by forced convection where a forced draught fan forces the air over the condenser [4]. But the COP of such a system is relatively low since heat carrying capacity of air is less [5]. The COP can be increased by using water as a cooling medium because water has more heat carrying capacity than air. In this experiment the air cooled condenser of a domestic refrigerator has been replaced by a water cooled condenser. 2. Methodology As most of the refrigeration system are working on vapour compression system with four basic components they are evaporator, compressor, condenser and expansion device. In a refrigerator, a medium called refrigerant continuously extract the heat from the space within the refrigerator (refrigerated space) which is to be kept cool at temperature less than that of the atmosphere and finally rejects this heat to surrounding air. Some of the fluids like, Ammonia, Freon, Methyl Chloride, Carbon dioxide are the commonly used refrigerants. Here we are using R134a fluid as our refrigerant. As we cannot change or upgrade evaporator, compressor and expansion device easily since it is internally fabricated so we have chosen to increase the efficiency of the refrigerator by increasing the heat transfer rate through the condenser unit. In this experiment the condenser unit is changed from air cooled condenser of 9m length of iron material to water cooled condenser of 3m length of copper material. To cool the condenser coil, the condenser is enclosed in a small tank

Energy and Power 2017, 7(3): 70-74 71 of dimension 0.45m 0.325m 0.025m. Thus the capacity of the tank is approximately 3.6 10-3 m 3 or 3.6 litres. This design is so chosen to enclose the condenser for water cooling. Pipes are provided on the top face and lower face at suitable positions to circulate water to and from the upper tank. The tank of size approximately ten times the lower tank is placed on the top of the refrigerator which serves as a heater box. In order to measure the performance of the refrigerator two pressure gauges have been installed one at the suction and another at the delivery of the compressor. The range of delivery pressure gauge is 500psi and that of suction is 150psi. For measuring temperatures at different points thermocouples have been installed. There are six thermocouples placed at different positions to measure various temperatures. made through which the hot water circulation from the condenser tank passes as shown in the Figure 4 and Figure 5. The upper end of the lower tank is connected to the upper end of the upper tank and the lower end of the lower tank is connected to the water supply tank. The lower end of the upper tank is let out free for the water to exit the system after the circulation as shown in Figure 3. To measure and compare the performance of this refrigerator with the conventional refrigerator, two pressure gauges have been installed in the refrigerator. The remaining components of the refrigerator are not altered. 3. Method The lower temperature refrigerant in the liquid state enters the evaporator and vaporise by absorbing the heat from the evaporation chamber. Then the refrigerant is compressed to a higher temperature and high pressure by a compressor. The vapour refrigerant is then condensed in the water cooled condenser to lower temperature and high pressure. The refrigerant gives away its latent heat in condenser and get condensed. This heat is taken away by the water in the smaller tank surrounding the condenser. The temperature of the water in the condenser tank gets increased and its density decreases. Due to the thermo syphon action, the hot water rises up and reaches the upper tank. Simultaneously cold water enters to the lower tank from the lower side of the upper tank, thus maintaining a moderate temperature in the lower tank. The condensed refrigerant then enters the capillary expansion and expands to a lower temperature and low pressure. Then again the low temperature low pressure refrigerant enters the evaporator and the cycle repeats. In the water cooled condenser the vapours of the refrigerant gives off its latent heat to the water through the copper tubes and consequently condenses into liquid so that it can be recirculated in the refrigeration cycle. The latent heat of the refrigerant that is given off in the condenser comprises mainly of the heat absorbed from the refrigerated space and the heat developed due to compression of the refrigerant. Operation of a water cooled refrigeration is as shown in the Figure 1. In this experiment a domestic refrigerator was purchased and necessary modifications were done to obtain the required outcome. The capacity of the refrigerator is 165 litres and the refrigerant used is R134a. The condenser of reduced length is enclosed in a tank (lower tank) which is as shown in Figure 2 and Figure 3. The tank is filled with water which acts as a cooling medium. In order to circulate the heated water, no separate pump is used, which would require extra power. Hence to facilitate circulation of water, thermo syphon principle is used. For this purpose water from tank placed above the refrigerator is made use of. A heater box is also Figure 1. Refrigeration cycle in water cooled condenser refrigeration system Figure 2. Isometric view of a water cooled domestic refrigerator Figure 3. Line diagram of water cooled refrigerator

72 Sheetal Narayan Shetty et al.: Performance Assessment of Water Cooled Condenser Refrigeration System 4. Calculation Figure 4. Water cooled condenser lower tank Figure 5. Sectional view of heater box The Table 1. shown below gives the amount of heat rejected in air and water cooled condenser and for different lengths. Table 1. Heat rejected in air and water cooled condenser for different lengths of condenser Cooling Method Condenser Material Length of Condenser Pipe (m) Heat Rejected (W) Air Cooled Iron 9 110 Water Cooled Copper 9 1740 Water Cooled Copper 3 600 The Table 2. shows the comparison of time for the evaporator temperature drop between air cooled and water cooled condenser refrigerator. Table 2. Time comparison table for evaporation temperature drop between air cooled and water cooled condenser refrigerator Temperature Range Time for Cooling in the Temperature ( C) Evaporator (Seconds) From To Air Cooled Water Cooled High 20 15 77 56 Medium 5 0 213 125 Low -8-13 673 515 Terms used are as follows: T 1 = temperature before compression ( C) T 2 = temperature after compression ( C) T 3 = temperature after condensation ( C) T 4 = temperature after expansion ( C) T 5 = temperature of water in heater box ( C) T 6 = temperature inside freezer ( C) h 1 = enthalpy before compression (kj/kg) h 2 = enthalpy after compression (kj/kg) h 3 = enthalpy after condensation (kj/kg) h 4 = enthalpy after expansion (kj/kg) P 1 = pressure before compression (MPa) P 2 = pressure after compression (MPa) Calculation of COP for air cooled condenser refrigerator: Observation: Refrigerant R134a Capacity = 165 litres Rating = 230V, 50Hz, 1.1Amps Room temperature = 32 C Enthalpy values for corresponding pressure and temperature from R134a pressure-enthalpy chart are, h 1 (P 1,T 1 ) = (0.055,35.6) = 425kJ/kg h 2 (P 2,T 2 ) = (1.27,70) = 450kJ/kg h 3 (P 3,T 3 ) = (1.27,49) = 270kJ/kg = h 4 COP air (1) COP air COP air = 6.28 Calculation of COP for water cooled condenser refrigerator: Observation: Room temperature = 30 C Enthalpy values for corresponding pressure and temperature from R134a pressure-enthalpy chart are, h 1 (P 1,T 1 ) = (0.033447,46) = 440kJ/kg h 2 (P 2,T 2 ) = (1.0341,55) = 460kJ/kg h 3 (P 3, T 3 ) = (1.0341,45) = 250kJ/kg = h 4 COP water (2) COP water COP water = 9.5 Percentage increase in COP: % increase (3) %increase = %increase = 51.27% 5. Results and Discussions COP of air cooled refrigerator is 6.28 and the COP obtained for water cooled condenser is 9.5. Thus COP is increased by 51.27%. Thermo syphon action has been observed. Time for cooling in the evaporator has been reduced which is shown in Figure 6.

Energy and Power 2017, 7(3): 70-74 73 The condenser outlet temperature is reduced drastically which is shown in Figure 7. 7. Scope for Future Work Appropriate coolant must be used in place of water to prevent corrosion problems. Suitable alterations can be made in the design, so that the system can be easily moved. 8. Conclusions Figure 6. Graph of temperature v/s time of evaporator for air and water cooled refrigerator Figure 7. Graph of time for water and air cooled refrigerator v/s temperature after condensation 6. Advantages and Disadvantages Advantages: Since water cooling is more efficient than air cooling, time required for cooling is less and hence, COP is increased. Length of the condenser pipe is reduced which reduces the compressor work and hence increases its efficiency. Water cooling system does not require any external power. Disadvantages: Use of water as a cooling medium might cause corrosion problem. Presence of water tank makes the system bulky and this might cause problem during domestic use. Use of water as a cooling medium may result in the formation of scales in the supply line. With the incorporation of water cooled Condenser, the Refrigeration Effect increases which in turn increases the COP. Time for cooling in the Freezer is reduced drastically. Hence, time required to reach the required temperature is less and the compressor can shut off quickly saving electrical power. Reduced condenser length results in lesser refrigerant travel distance and hence the pumping power required is less. With the incorporation of water cooled Condenser, the net weight of the system increases. Since the specific heat of water is 4.187kJ/kg/ C which is higher than any other common substance and because air is having its specific heat as 1.005kJ/kg/ C which is lower than water, hence the heat carrying capacity by water is more than air which leads to lower condenser temperature in water cooled condenser than that of air cooled condenser. With the incorporation of water cooled condenser, on an average we can have 14.7 C less condenser temperature than that of air cooled condenser. Since Copper tube (k=386w/mk) is having higher Thermal Conductivity than that of Iron tube (k=72.7w/mk), heat transfer is more in copper tube. The amount of heat transfer rate in copper tube condenser of 3m is 4.5 times more than that of the iron tube condenser of 9m. Since the distance between the centre of upper tank and lower tank is 0.5m which is less than 12m (limit up to which thermo syphon principle for water is applicable), thermo syphon principle is observed. The time taken for water cooled condenser is 27.27% lesser than that of air cooled condenser from 20 C to 15 C, 41.31% lesser from 5 C to 0 C and 23.48% lesser from -8 C to -13 C respectively. REFERENCES [1] Khurmi R.S., and Gupta J.K., Refrigeration and Air Conditioning, S Chand, 2012. [2] Hundy G.F., Trott A.R., and Welch T.C., Refrigeration and Air Conditioning, 4 th Edition, Butterworth-Heinemann, 2008.

74 Sheetal Narayan Shetty et al.: Performance Assessment of Water Cooled Condenser Refrigeration System [3] Admiraal D. M., and Bullard C. W., Heat Transfer in Refrigerator Conditioners and Evaporators, University of Illinois, 1993. [4] Holman J.P., Heat Transfer, Mc Graw Hill, 2003. [5] Domkundwa and Arora, Refrigeration and Air Conditioning, Dhanpat Rai and Sons, 1994. [6] Shan K. W., Handbook of Air Conditioning and Refrigeration, 2nd Edition, Mc Graw Hill, 2003.