Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Similar documents
Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Functional Safety: the Next Edition of IEC 61511

New Developments in the IEC61511 Edition 2

PPA Michaël GROSSI - FSCE PR electronics

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

Changes in IEC Ed 2

Is your current safety system compliant to today's safety standard?

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

INTERNATIONAL STANDARD

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

This document is a preview generated by EVS

INTERNATIONAL STANDARD

PRIMATECH WHITE PAPER CHANGES IN THE SECOND EDITION OF IEC 61511: A PROCESS SAFETY PERSPECTIVE

ADIPEC 2013 Technical Conference Manuscript

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

Digital EPIC 2 Safety manual

2015 Functional Safety Training & Workshops

Value Paper Authors: Stuart Nunns CEng, BSc, FIET, FInstMC. Compliance to IEC means more than just Pfd!

100 & 120 Series Pressure and Temperature Switches Safety Manual

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

Measurement of Safety Integrity of E/E/PES according to IEC61508

United Electric Controls One Series Safety Transmitter Safety Manual

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Integrated but separate

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Session Ten Achieving Compliance in Hardware Fault Tolerance

New requirements for IEC best practice compliance

IEC Functional Safety Assessment

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express

Certification Report of the ST3000 Pressure Transmitter

INTERNATIONAL STANDARD

Failure Modes, Effects and Diagnostic Analysis

InstrumentationTools.com

SIL DETERMINATION AND PROBLEMS WITH THE APPLICATION OF LOPA

IEC61511 Standard Overview

This document is a preview generated by EVS

This is a preview - click here to buy the full publication

Failure Modes, Effects and Diagnostic Analysis

Options for Developing a Compliant PLC-based BMS

Where Process Safety meets Machine Safety

FUNCTIONAL SAFETY CERTIFICATE

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit

Design & Use of Ground Based Pumps Guidance Document

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Failure Modes, Effects and Diagnostic Analysis

Topic MYTH FUNCTIONAL SAFETY IMPLIES HAVING A SIL RATED COMPONENT. Presented by : Arunkumar A

INTERNATIONAL STANDARD

Addressing Challenges in HIPPS Design and Implementation

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

Failure Modes, Effects and Diagnostic Analysis

Safety in the process industry

IEC Functional Safety Assessment

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Session Ten: The importance of a clear Safety Requirements Specification as part of the overall Safety Lifecycle

Failure Modes, Effects and Diagnostic Analysis

INTERNATIONAL STANDARD

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Safety Instrumented Systems

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Failure Modes, Effects and Diagnostic Analysis

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

Safety Instrumented Systems Overview and Awareness. Workbook and Study Guide

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Why AC800M High Integrity is used in Burner Management System Applications?

Fire and Gas Detection and Mitigation Systems

Siemens Process Automation End-user Summit- 2011

NEW CENELEC STANDARDS & CSM-RA NEW CENELEC STANDARDS & CSM-RA 2017

Applying Buncefield Recommendations and IEC61508 and IEC Standards to Fuel Storage Sites


The Use of an Operator as a SIL 1 component in a Tank Overfill Protection System

Technical Report Proven In Use SITRANS P500

Failure Modes, Effects and Diagnostic Analysis

FINAL DRAFT INTERNATIONAL STANDARD

Functional Safety Solutions

Soliphant M with electronic insert FEM52

Failure Modes, Effects and Diagnostic Analysis

Process Safety Workshop. Avoiding Major Accident Hazards the Key to Profitable Operations

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

Practical Methods for Process Safety Management

SAFETY RELAY APPLICATION

This document is a preview generated by EVS

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

INTERNATIONAL STANDARD

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service

Transcription:

Technical Paper Functional Safety Update IEC 61511 Edition 2 Standards Update

Functional Safety Update Table of Contents 1.0 Introduction 2.0 IEC 61511-1 changes 3.0 IEC 61511-2 changes 4.0 IEC 61511-3 changes 5.0 IEC 61511 Edition 2 and impact on FSMS - summary 6.0 References 2 Functional Safety Update - IEC 61511 Edition 2 Standards Update I ABB Technical Paper

IEC 61511 Edition 2 Standards Update 1.0 Introduction Purpose The purpose of this standards update is to provide a notification from ABB s Safety Lead Competency Centre (SLCC) in order to highlight the changes that have been agreed to be made to IEC 61511 Edition 1 as an Edition 2 version. It is a summary of what is considered by the ABB SLCC to be the most significant changes. Note that not all changes have been included and some changes, which are deemed significant for the SLCC, might not be considered as important as other updates in the revised standard. Status of the standard As on the date of this notification, IEC 61511 Edition 2 Part 1 has been published in February 2016. The IEC 61511 maintenance committee have also completed Parts 2 and 3. These two parts have now been published as of July 2016. General Changes have resulted from comments provided by National Committees and User Groups. The Edition 2 standard also clarifies the relationship with IEC 61508 Edition 2. IEC 61511 Edition 2 Part 1 contains normative requirements only. Part 2 provides guidelines for the application of Part 1. Part 3 provides guidance for the determination of the required safety integrity level (SIL). Note that this document focuses mainly on Part 1. ABB Technical Paper l Functional Safety Update - IEC 61511 Edition 2 Standards Update 3

Functional Safety Update 2.0 IEC 61511-1 changes Management of functional safety The second edition requires a formal procedure to be in place to manage the competence of all those involved within the safety instrumented system (SIS) lifecycle. Such competency assessment process shall be documented. Additionally, periodic assessments shall be carried out to document the competence of individuals. It should be noted that if a supplier makes any functional safety claims for a product or service, then they shall have a compliant functional safety management system (FSMS) in place. End users should therefore seek assurances that this is the case for any safety related products or solutions being provided by the supply chain. Also note that in support of FSMS, there are defined requirements to undertake a periodic functional safety assessment (FSA) which shall be performed during the operations and maintenance lifecycle phase. The SIS software, hardware and procedures used to develop and execute the application program shall be subject to configuration management and shall be maintained under revision control. Process Hazard & Risk Assessment A security risk assessment on the SIS and associated equipment is now required. It shall result in a description of the devices covered by this risk assessment and provide a description of the potential threats to security during the different phases of the design, operation and maintenance lifecycles, together with potential consequences resulting from such security events (including likelihood). Part of this assessment process is to identify requirements for additional risk reduction together with the measures to be taken to reduce or remove the potential threats. Allocation of safety functions The results of the allocation process shall be recorded. The safety instrumented functions (SIF) of the process shall be described, e.g., the actions to be taken, set points, reaction times, activation delays, fault treatment, valve closure requirements. This description shall be in an unambiguous logical form and shall be referred to as the process requirements specification or the safety description. The process requirements specification is used as input information for the safety requirements specification (SRS) and shall be sufficiently detailed to ensure adequate specification of the SIS and its devices. If it is intended not to qualify the basic control system (BPCS) to the IEC 61511 standard, then two BPCS functions may be given credit (RRF=<10) for the same hazardous event. They could be: a single BPCS protection function in the case of a demand caused by a BPCS control function or two BPCS protection functions in the case of a demand caused by a non BPCS element e.g. alarm function and control function. It shall be noted that BPCS functions designed to be separate and independent (sensors, input cards, processor, output cards and final element). SIS safety requirements specification Note that there are a number of additional requirements added to the list of requirements (now 29 topic areas) in the SRS content; and in particular: a list of the plant input and output devices related to each SIF which is clearly identified by the plant means of equipment identification (e.g., field tag list); requirements relating to proof test implementation There is also a modified bullet point from Edition 1 regarding bypass functionality and is as follows: the SRS shall also include requirements for which procedure (written procedure) is to be applied during the bypassed state Application program safety requirements Section 10.3.5 identifies a number of modified Edition 1 clause 12.2.2 content and grouped with additional requirements for application program as indicated below: acceptable real time performance in the presence of faults, program sequencing and time delays if applicable; the requirements for communication interfaces, including measures to limit their use and the validity of data and commands both received and transmitted; process dangerous states (for example closure of two valves at the same time that could lead to a dangerous state) generated by the application program that shall be identified and avoided; definitions of process variable validation criteria for each SIF. 4 Functional Safety Update - IEC 61511 Edition 2 Standards Update I ABB Technical Paper

IEC 61511 Edition 2 Standards Update SIS design & engineering In terms of hardware fault tolerance (HFT) requirements, the revised requirements are now based only on the type of device (A or B type) and the target SIL. The safe failure fraction (SFF) concept has been abandoned in IEC 61511 Edition 2. The new requirements for architectural constraints can be seen in Table 1 below. The route now developed within IEC 61511 has been derived from Route 2H of IEC 61508-2:2010. SIL 1 (Any mode) 0 2 (Low demand) 0 2 (High and continuous demand) 1 3 (Any mode) 1 4 (Any mode) 2 Table 1. Hardware Fault Tolerance IEC 61511 Edition 2 Minimum required HFT Also note that clause 11.9 now improves the clarity on the relationship between random failure and the SIF probability of failure calculation and specifically focuses on both probability of failure on demand (PFD) and architectural constraints as there may have been a misconception that the calculation of SIF probability of failure (dependent only on random failure) was directly related to the calculated failure rate only. In other words, it now clarifies that the quantification of random failure is not just the PFD calculation alone, but architectural constraints and the additional requirements for systematic capability aspects also need to be considered (refer to Clause 11.5.2.1). A systematic capability concept has been included within IEC 61511 Edition 2 and has been further aligned to IEC 61508 Edition 2 requirements. The main intent of the prior use evaluation has also been better expressed i.e. is to gather evidence that the dangerous systematic faults have been reduced to a sufficiently low level compared to the required safety integrity. The previous edition was not clear in this area. A safety manual is required for elements that are proven by prior use. This now means all SIS devices shall have a safety manual. A safety manual shall cover operation, maintenance, fault detection and constraints associated with the SIS, the intended configurations of the devices and the intended operating environment. Quantification of random failure The reliability data used when quantifying the effect of random failures shall be based on field feedback from similar devices used in a similar operating environment. The reliability data uncertainties shall be assessed and taken into account when calculating the failure measure. Additional requirements have been added for what to be considered when calculating the failure measure of a SIF e.g. the requirement for proof test coverage which should be identified with the compliant device safety manual i.e. the assumption of 100% proof test coverage. SIS application program development The term application software has been replaced by application programs (AP). Requirements have been streamlined and made more relevant for LVL and FPL rather than FVL. Many of the AP requirements content has been relocated from clause 12 into those lifecycle clauses that the AP addresses (mainly clause 6 and 10). Many AP requirement clarifications have been added during this process. The application program (AP) shall be designed in such a way as to ensure that once the SIS has placed the process in a safe state, the process remains in the safe state, including under loss of power conditions and on power restoration, until a reset has been initiated unless otherwise directed by the SRS. Factory Acceptance Test (FAT) A dedicated Factory Acceptance Test shall take place. New requirements have been added for FAT planning. A FAT is required to perform: performance tests (to determine if the system meets timing, reliability and availability, integrity, safety targets and constrains) internal checks (Internal data flow checks can be carried out to that the SIS is processing input data and generating output response as specified.) environmental tests (EMC life- and stress-testing) testing for safe reaction in case of power failure (including restart after power restored) There are also additional requirements that sensor and final element configurations shall be checked for appropriateness during this stage of the design & engineering lifecycle (Note Edition 1 referred to the logic solver only.) It is now also required to consider the hazards posed by testing especially dealing with stored energy and to record results and observations whilst the test is being conducted. ABB Technical Paper l Functional Safety Update - IEC 61511 Edition 2 Standards Update 5

Functional Safety Update SIS operation and maintenance Persons responsible for operations and maintenance shall review the hazard and risk analysis, allocation and design to ensure the assumptions made are valid e.g. assumptions on occupancy and corrosion protection. A new requirement is added for those responsible persons (this could be either the duty holder or their nominated supply chain partners) to identify spare parts in order to minimise the bypass duration due to the potential non-availability of the hardware parts of the SIS. A new requirement has been introduced to highlight the need for additional measures or constraints to be applied if a nonfault tolerant subsystem is taken offline during maintenance. This is consistent with the requirements when failures in non-fault tolerant systems are detected. The maximum time the SIS is allowed to be in bypass (for repair or testing), while safe operation of the process is continued, shall be defined. Continued process operation with a SIS device in bypass shall only be permitted if a hazards analysis has determined that compensating measures are in place and that they provide adequate risk reduction. The compensating measures required depend on: SIL, the tolerable risk associated with the hazardous event, the hardware fault tolerance of the SIS, the anticipated mean repair time (MRT) and the availability of any other layers of protection etc. In some cases, it can be adequate for an action to be taken to ensure repair of the dangerous failure within the assumed maximum permitted repair time (MPRT) in the calculation of the PFDavg, but in other cases it can be deemed necessary to provide other measures to compensate for the reduced risk reduction until the SIS is fully restored. In addition, new requirements have been added for suitable management procedures to be applied to review deferrals and prevent significant delay to proof testing Also there is a new clause covering the requirements that an FSA shall also be carried out periodically during the operations and maintenance phase to ensure that maintenance and operation are being carried out according to the assumptions made during design and that the requirements within IEC 61511 for safety management and verification are being met. 3.0 IEC 61511-2 changes Part 2 remains as an informative part of the standard. However, significant additions have been made to a number of content sections. Note that some of the informative text originally found in Part 1 of the standard has been moved into Part 2. This section of the standard also consists of more examples and general explanations and therefore the number of pages have increased from 80 to 190. 4.0 IEC 61511-3 changes A number of new annexes have been added. The content has been reworded to achieve improved clarity. A new clause (4.6) has been added to explain the commonly used terms in general use within Part 3. A figure below is intended to illustrate the difference between the terms by showing the progression from hazard to abnormal situation on loss of control through hazardous event after protection measures failed to hazardous situation if a person is in the hazardous zone and to the occurrence of harmful event if a person is unable to escape consequences. Loss of Control or triggering causes Protection Measure(s) failed Person in the Hazard Zone Person unable to escape consequences Modification A new requirement has been added. Modification activities shall not begin until a functional safety assessment is completed in accordance with clause 5. The FSA (Stage 5) shall be done by an independent person. It should be noted that every change to the SIS (covering the subsystem and/ or components, hardware and software (application program) is a modification unless a like for like replacement in kind is performed. Hazard Potential source of harm Abnormal Situation Figure 1. Harmful event progression Hazardous Event Hazardous Situation Person exposed to Hazard Harmful event Person suffers harm 6 Functional Safety Update - IEC 61511 Edition 2 Standards Update I ABB Technical Paper

IEC 61511 Edition 2 Standards Update 5.0 IEC 61511 Edition 2 and impact on FSMS - summary In the SLCC s opinion many significant changes have been agreed for the issue of IEC 61511 Edition 2. The changes are primarily aimed at improving the quality of all lifecycle activities. In doing so, the wording of numerous clauses within the standard has been changed to achieve additional clarity and many of the previous contents comprising should have now been changed to shall within this new edition. 6.0 References 1. IEC 61511-1 Edition 2.0 2016-02 Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and application programming requirements 2. IEC 61511-1 First edition 2003-01 Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and software requirements ABB SLCC July 2016. Rafal Selega ABB, SLCC Functional Safety Consultant The second edition also puts more emphasis on the competency of persons and introduces additional clarity for the systematic capability concept. Hardware fault tolerance requirements have been simplified and the safe failure fraction concept has been abandoned. The requirements for hardware reliability calculations are now more robust in terms of the quality of input data which is required and as such, aims at a more conservative approach of the failure rate calculation methods to be utilised. It is also recognised that a functional safety cyber security lifecycle process must also be implemented for SIS. The revised standard also requires the persons responsible for operations and maintenance to review all design assumptions and to ensure they are valid. This is in addition to implementing an FSA by an independent person (to be performed periodically) during the operation lifecycle phase and before each SIS modification is actually implemented. It is envisaged that the changes make the standard simpler in interpretation, but more exacting in requirements. ABB Technical Paper l Functional Safety Update - IEC 61511 Edition 2 Standards Update 7

Contact us ABB Limited Howard Road, Eaton Socon St Neots Cambridgeshire PE19 8EU Phone: +44 (0)1480 475321 E-Mail: oilandgas@gb.abb.com www.abb.com Notes: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB. Copyright 2016 ABB All rights reserved Printed in UK (10.2016) Functional Safety Update - IEC 61511 Edition 2 Standards Update. Technical Paper/October 2016