Super. Digital Inverter. Inverter Air Conditioning for Light Commercial Use

Similar documents
for Light Commercial Use

MiNi-SMMS WHEN COMMERCIAL MEETS RESIDENTIAL

Light commercial range. Passion at work

LIGHT COMMERCIAL RANGE Inverter heat pumps suitable for both homes and commercial premises

Inverter Air Conditioning for Light Commercial Use

Blending Commercial and Residential. MiNi VRF

Inventor of the Inverter Digital Inverter System

Light commercial range. Passion at work. Light commer

Technology that works fast. Inverter Ducted Systems

Technology that works fast. Inverter Ducted Systems

Technology that works fast. Inverter Ducted Systems

Index. Toshiba Solutions. Absolute comfort

INVERTER DUCTED SYSTEMS

Product Launch SHRMi

TOSHIBA AIR CONDITIONING

Business. The business range. The most advanced solutions for larger buildings.

Simultaneous. Heating and Cooling Solution for Large Buildings. Air Conditioning for large buildings

MiNi-SMMS Design Manual HFC R-410A. Indoor unit. Outdoor unit

AIR-CONDITIONER SPLIT TYPE

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

Compact 4-way Cassette ( ) Type

excellence in seasonal efficiency BUSINESS SOLUTIONS

Inverter Ducted Air Conditioners

Energy-saving operation

Air Conditioning For Large Buildings

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

Inverter Wall Mounted Series

Single Fan MiNi VRF Apartment Ready

Midea Ducted and Cassette Split Systems. Maximum versatility, maximum value.

Technical Guide. Multizone: Multi-Split Type Heat Pump Systems

Air to water Heat Pump System

DC Inverter Smart VRF Products(R410A)

MRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design

DESIGN MANUAL R410A. Indoor Unit. Outdoor Unit FILE NO. A Cooling Only Model <Inverter Unit> Heat Pump Model <Inverter Unit>

Commercial Air Conditioners. VRF 60Hz V4+S/V4+R/V4+W/Mini VRF

Midea Ducted and Cassette Split Systems. Year round comfort, all around the house.

Commercial Air Conditioners 2017/2018. VRF 50/60Hz. V5 X Series

Super Modular Multi Design Manual HFC R-410A. Indoor unit. Outdoor unit

Engineering Data Book

Come home to a warm welcome

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A OUTDOOR UNIT

Miraco MISR REFRIGERATION & AIR CONDITIONING MFG. CO.

Variable Refrigerant Flow

SMC DUCTED. High Performance AIR CONDITIONING SYSTEMS

Inverter Ducted Air Conditioners

we care about Better Air

Whole of Home ULTRASLIM. Ducted comfort, for when space is at a premium. That s better. That s Actron.

Whole of Home ULTRASLIM. Ducted comfort, for when space is at a premium. That s better. That s Actron.

P-SERIES PRODUCT CATALOGUE AIR CONDITIONER & HEAT PUMP

Ductless Systems. Right product for the right application

Owner s Manual VN-M150HE VN-M250HE VN-M350HE VN-M500HE VN-M650HE VN-M800HE VN-M1000HE VN-M1500HE VN-M2000HE. Air to Air Heat Exchanger

Comfort. Health Clean. Saving. The new era in air conditioning. Multi-Split Systems

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

RC-0219-A. Single-Split Non Inverter Series

(Non-Inverter & Inverter) R410A

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)-

Ducted Air Conditioning

Air to water Heat Pump System

-20 C 11 HSPF 23 SEER WALL-MOUNTED HEAT PUMPS. 10 years* *See details on the back SINGLE ZONE MULTI-ZONE (UP TO 5 ZONES) descair.

Whole of Home ULTRASLIM. Ducted comfort, for when space is at a premium. That s better. That s Actron.

Ducted Air Conditioning

Ultimate VRF System R410A, 50Hz

Comfort. Health Clean. Saving. The new era in air conditioning. Multi-Split Systems

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

DC inverter Outdoor-air Processing unit (GC )

DESIGN MANUAL R410A. Outdoor Unit. FS unit FILE NO. A RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE

PRODUCT LINEUP VRF. For LIGHT COMMERCIAL & RESIDENTIAL, COMMERCIAL

TOSHIBA Carrier (UK) Ltd. LC DX Interface Installation manual ENGLISH. For commercial use. Model name:

turn to the experts R 410A DC INVERTER LIGHT COMMERCIAL SERIES

MRVIII-S. 007 Features & Benefits 017 MRVIII-S Outdoor

Toshiba solutions 3 At Toshiba, we believe that Evolu on is leading the path to a be er future. Through the decades, we have been constantly crea ng i

Leading edge reverse cycle air conditioning. Ducted and ceiling cassette

Inverter console UFV system. Compact design and personalised air flow selection

DAIKIN Modular Inverter Air Cooled Chiller

Split Type Air Conditioners FTNE-M Series Cooling Only [50 Hz]

2 &3-4 Head Multi System

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

ELECTRICAL QUANTITY WEIGHT (LB)

Technical HandBook. Version

Hi - Wall Split Systems 12K - 18K - 24K

Inventor of the Inverter

Slim Line Ceiling Concealed Ducted Split Systems. Medium Static Pressure. Ducted Split System Heat Pump

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

360 round flow, ensuring uniform airflow distribution across the room. Independent louvre control allows each louvre to be set at the desired angle

Compact design & easy maintenance

SKYAIR SERIES SINGLE ZONE HEATING & COOLING SYSTEMS. Up to 20 SEER / Up to 12.0 HSPF / 14.5 EER INVERTER, VARIABLE-SPEED COMPRESSOR

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Daikin MXS SERIES MULTI-ZONE HEATING & COOLING SYSTEMS

Compact Design For Light Commercial Buildings. Benefit Points SMALL OFFICES HOTELS NEW SHOPS, RESTAURANTS. 1. Compact & Quiet design

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

. Creating Maximum Comfort

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

FUJITSU VRF 2016/17 PRODUCT CATALOGUE VRF MULTI SPLIT VRF VENTILATION

DAIKIN FHQ SERIES HEAT PUMP & COOLING ONLY SYSTEMS. CEILING-SUSPENDED CASSETTE Up to 18.0 SEER / Up to 10.0 HSPF Up to 14.0 EER

A GUIDE TO COMFORT EXCLUSIVELY DISTRIBUTED BY TEMPERZONE AUSTRALIA

Carrier. Ductless Systems. Taking Comfort, And Your Business, Further. The Right Solution. Right Now.

Transcription:

Super Digital Inverter Inverter Air Conditioning for Light Commercial Use

Super Digital Inverter Toshiba Super Digital Inverter series air conditioners combine economy and ecology in a compact body. They feature state-of-the-art technology, flexible control, and easy installation to bring natural comfort and convenience to any business environment. A complete range of indoor units: Cassette, Ducted, Ceiling and High wall units. Superior EER Very efficient energy consumption, Keeps down operating costs. EER of 4.52* and COP of 4.79* achieved by Toshiba s unrivalled Super Digital Inverter technologies and newly developed components. 4-way cassette / Cooling (EER) 6.0 5.56 5.56 5.0 3.82 4.0 3.61 3.0 2.0 4.52 6.49 3.96 5.67 4-way cassette / Heating (COP) 5.96 6.0 5.56 5.0 4.63 4.19 4.0 3.0 2.0 4.79 5.38 4.36 4.90 *4HP outdoor unit 1.0 2 HP 3 HP 4 HP 5 HP 1.0 2 HP 3 HP 4 HP 5 HP Rated 50% load The industry's first magnetic-action control Current model New model Magnetic action Magnetic center The new structure allows a huge reduction in energy loss. The balanced magnetic-action force to rise and the rotor s weight minimized the friction laid on the axis provides excellent operation efficiency. Stator Rotor Rotor s weight Friction loss Reducing friction loss ECO-driving DC twin rotary Vector-controlled inverter Vector IPDU control changes the motor current wave to a smooth sine pattern so that noise emitted from the drive units is greatly reduced. High efficiency heat-transfer (flat fin) Heat-transfer tube with improved heat-transfer coefficient. R410A refrigerant An ozone layer depletion coefficient of zero has become absolutely essential for an advanced air conditioning system. A low minimum speed of 10 rps has been achieved. This has further improved the operating efficiency when the load is low (the minimum in Series 2 was 15 rps). High power motor DC fan motor Highly Efficient DC Motor. Bat wing fan New development for high-pressure low-volume fan. Wide-flow grille Optimizing ventilation performance, Bringing out the full effect of fan and motor. DC twin rotary compressor A low minimum speed of 10 rps has been achieved. Large-area magnet Rotor with slit Newly designed compression path More precise components The structure and shape of each compressor component has been optimised. The area of the rotor magnet has been increased and a slit introduced to the design. These improvements have further enhanced efficiency and reduced noise. 2 Note: Actual component may vary considerably from specifications depending on product model.

Operating temperature range Heater operation is possible starting from an outdoor temperature of -20 C creates a comfortable space even during cold winters, while cooling operation is possible at -15 C outdoor temperature. This enables wider applications and use of the system in colder regions. Heating operation range SDl (2-6HP) SDl (1.5-1.7HP) -20 C -15 C 0 C 15 C Heating: C WB Self-Clean operation-continuing high performance for energy saving This enables indoor unit type and Ceiling type to maintain energy efficiency at the time of purchase for a long time. The mechanism of the wash-off 1. The aqua resin coating prevents dirt from sticking to the fins. 2. The condensation water flows and washes away dirt. Water 3. After washing, a drying operation suppresses the Oil/ Dirt propagation of mold. Quiet operation Aqua resin coating Low-noise design. If the outdoor temperature is 30 C or less, operates at under 45dB(A). It s possible to automatically operate the quiet operation mode below 35 C air temperature. Frost protection 8 C operation for frost protection is possible for the combination with Super Digital Inverter. (4-Way and Slim Duct series 4) Sub cool path Improve reliability for smooth drainage. The outdoor unit of Super Digital Inverter is equipped with Sub cool path preventing freeze under a heat exchanger. (Only 3HP to 6HP) Annual operation (h) 300 240 180 120 60 0 Operation below air temperature 30 ( C) 22 23 24 25 26 27 28 29 30 31 32 33 34 35 Air temperaure ( C) Rear side 50 45 40 35 Operation sound db(a) Piping panel taken out in 4 directions Height Difference Super Digital Inverter leads the industry with support for height differences of up to 30 meters on a single system. That is enough height to cover an 8-story building. Height between indoor units 30m 8F 7F 6F 5F 4F 3F 2F 1F Single system Sub cool path Front Compatible with pipes up to 75 meters long Enable the outdoor unit to be installed out of sight increases installation flexibility. (Only 4HP to 6HP) Under Farthest equivalent length 75m Rear Lateral 3

Super Digital Inverter Combinations 1-phase model Equivalent (HP) 1.5HP 1.7HP 2HP 3HP 4HP 5HP 6HP Standard RAV-SP404ATP-E RAV-SP454ATP-E RAV-SP564ATP-E RAV-SP804ATP-E RAV-SP1104AT-E RAV-SP1404AT-E - Light Anti-Corrosion protection - - - - RAV-SP1104ATZ-E RAV-SP1404ATZ-E - Heavy Anti-Corrosion protection - - RAV-SP564ATJP-E RAV-SP804ATJP-E RAV-SP1104ATZG-E RAV-SP1404ATZG-E - 3-phase model 50Hz 60Hz Standard RAV-SP1104AT8-E RAV-SP1404AT8-E RAV-SP1604AT8-E Light Anti-Corrosion protection RAV-SP1104AT8Z-E RAV-SP1404AT8Z-E RAV-SP1604AT8Z-E Heavy Anti-Corrosion protection RAV-SP1104AT8ZG-E RAV-SP1404AT8ZG-E RAV-SP1604AT8ZG-E Standard RAV-SP1104AT7 RAV-SP1404AT7 RAV-SP1604AT7 Light Anti-Corrosion protection RAV-SP1104AT7Z RAV-SP1404AT7Z RAV-SP1604AT7Z Heavy Anti-Corrosion protection RAV-SP1104AT7ZG RAV-SP1404AT7ZG RAV-SP104AT7ZG Compact 4-way cassette type Single RAV-SM404MUT-E RAV-SM454MUT-E RAV-SM564MUT-E N/A N/A N/A N/A Twin (x 2) N/A N/A N/A RAV-SM404MUT-E RAV-SM564MUT-E N/A N/A Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564MUT-E 4-way cassette type Single N/A N/A RAV-SM564UTP-E RAV-SM804UTP-E RAV-SM1104UTP-E RAV-SM1404UTP-E RAV-SM1604UTP-E Twin (x 2) N/A N/A N/A N/A RAV-SM564UTP-E RAV-SM804UTP-E RAV-SM804UTP-E Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564UTP-E Slim duct type Single RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E N/A N/A N/A N/A Twin (x 2) N/A N/A N/A RAV-SM404SDT-E RAV-SM564SDT-E N/A N/A Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM564SDT-E Standard duct type Single RAV-SM406BTP-E RAV-SM456BTP-E RAV-SM566BTP-E RAV-SM806BTP-E RAV-SM1106BTP-E RAV-SM1406BTP-E RAV-SM1606BTP-E Twin (x 2) N/A N/A N/A RAV-SM406BTP-E RAV-SM566BTP-E RAV-SM806BTP-E RAV-SM806BTP-E Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM566BTP-E Ceiling type Single N/A N/A RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM1107CTP-E RAV-SM1407CTP-E RAV-SM1607CTP-E Twin (x 2) N/A N/A N/A N/A RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM807CTP-E Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM567CTP-E High wall type Single N/A N/A RAV-SM566KRT-E RAV-SM806KRT-E N/A N/A N/A Twin (x 2) N/A N/A N/A N/A RAV-SM566KRT-E RAV-SM806KRT-E RAV-SM806KRT-E Triple (x 3) N/A N/A N/A N/A N/A N/A RAV-SM566KRT-E 4

Available Indoor Units 5

Compact 4-way cassette type Perfectly fit for 600 x 600 grid system ceiling Perfect for grid system ceiling This compact unit (575 x 575 mm) fits perfectly into ceilings and matches standard architectural modules, without the need to cut ceiling tiles. Panel Designed for simple & easy installation and maintenance The slim flat stylish panel design is only 268 mm in height even when an electrical box is located inside the unit. Easy access to electrical box is achieved by simply removing the suction grill. Easy installation is also possible using the panel adjust pocket. Use the adjust pocket function for fine adjustments after installation. The drain up height is 850 mm. Available for ceilings up to 3.5 m in height. 3.5m RBC-UM11PG(W)-E Maximum height (RAV-) SM404MUT-E SM454MUT-E SM564MUT-E Outdoor unit Power supply Cooling* 1 Heating* 1 Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E Light Anti-Corrosion protection (RAV-) - - - Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E 1-phase 50Hz 230V (220 240V) Capacity kw 3.6 4.0 5.0 Range, min-max kw 1.5-4.0 1.5-4.5 1.2-5.6 Power consumption kw 1.00 1.19 1.56 EER (Energy Efficiency Ratio) Capacity 100% 3.60 3.36 3.21 Capacity 80% 3.95 3.94 3.45 Capacity 50% 4.47 4.82 4.03 Capacity kw 4.0 4.5 5.6 Range, min-max kw 1.5-5.0 1.5-5.6 0.9-7.4 Power consumption kw 0.97 1.16 1.54 COP (Coefficient of Performance) Capacity 100% 4.12 3.88 3.64 Capacity 80% 4.27 4.04 3.93 Capacity 50% 4.44 4.33 4.52 Standard air flow (H/M/L) m 3 /h 660/552/468 660/552/468 798/672/546 Sound pressure level (H/M/L) db(a) 40/36/31 40/36/31 43/39/34 Sound power level (H/M/L) db(a) 55/51/46 55/51/46 58/54/49 Main unit dimensions (H/W/D) mm 268/575/575 268/575/575 268/575/575 Weight kg 17 17 17 Panel dimensions (H/W/D) mm 27/700/700 27/700/700 27/700/700 Panel weight kg 3 3 3 Outdoor unit Compressor type DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø12.7 / ø6.4 ø12.7 / ø6.4 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 5 Max. pipe total length m 30 30 50 Maximum height difference m 30 30 30 Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290 Weight kg 40 40 44 Standard air flow (Fan unit) m 3 /h 2400 2400 2400 Sound pressure level, Cooling/Heating* 2 db(a) 45/47 45/47 47/48 Sound power level, Cooling/Heating db(a) 62/64 62/64 63/64 Operating range, Cooling/Heating C -15~43 / -15~15-15~43 / -20~15 Options Auxiliary fresh air flange TCB-FF101URE2 Panel RBC-UM11PG(W)E 6 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber

4-way cassette type The wide air flow in all direction Multi-louver individual control Individual louver control enables airflow to be chosen according to user preferences. The angles of each louver can be set individually in 3 different choices of swing patterns; Standard swing, Diagonally opposite swing and Turn-around swing (1) Standard swing (2) Diagonally opposite swing New Long-life pre-filter A new long-life pre-filter has a surface 1.5 times of current filters to improve Dustcollection performance. Easy installation Light weight unit (24kg at 5HP) Easy panel installation, The panel is attached using the bolt that is already installed on the indoor unit. (3) Turn-around swing Built-in condensate drain pump 300mm or less 850mm or less 210mm (RAV-) SM564UTP-E SM804UTP-E SM1104UTP-E SM1404UTP-E SM1104UTP-E SM1404UTP-E SM1604UTP-E Outdoor unit Standard (RAV-) SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E Light Anti-Corrosion protection (RAV-) - - SP1104ATZ-E SP1404ATZ-E Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8-E, SP1104AT7 SP1104AT8Z-E, SP1104AT7Z SP1104AT8ZG-E, SP1104AT7ZG SP1404AT8-E, SP1404AT7 SP1404AT8Z-E, SP1404AT7Z SP1404AT8ZG-E, SP1404AT7ZG SP1604AT8-E, SP1604AT7 SP1604AT8Z-E, SP1604AT7Z SP1604AT8ZG-E, SP1604AT7ZG Power supply 1-phase 50Hz 230V (220 240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V Cooling* 1 Heating* 1 Capacity kw 5.3 7.1 10.0 12.5 10.0 12.5 14.0 Range, min-max kw 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0 Power consumption kw 1.47 1.86 2.21 3.16 2.37 3.46 4.49 EER (Energy Efficiency Ratio) Capacity 100% 3.61 3.82 4.52 3.96 4.22 3.61 3.12 Capacity 80% 4.25 4.40 5.31 4.64 4.79 4.10 3.53 Capacity 50% 5.56 5.56 6.49 5.67 5.88 5.43 5.07 Capacity kw 5.6 8.0 11.2 14.0 11.2 14.0 16.0 Range, min-max kw 0.9-8.1 1.3-11.3 2.4-13.0 2.4-16.5 2.4-15.6 2.4-18.0 2.4-19.0 Power consumption kw 1.21 1.91 2.34 3.21 2.42 3.42 4.30 COP (Coefficient of Performance) Capacity 100% 4.63 4.19 4.79 4.36 4.63 4.09 3.72 Capacity 80% 5.15 4.71 5.01 4.57 5.09 4.50 4.09 Capacity 50% 5.96 5.56 5.38 4.90 6.09 5.47 5.33 Standard air flow (H/M/L) m 3 /h 1050/870/780 1230/960/810 2010/1440/1170 2100/1440/1230 2010/1440/1170 2100/1440/1230 2130/1500/1260 Sound pressure level (H/M/L) db(a) 32/29/28 35/31/28 43/38/33 44/38/34 43/38/33 44/38/34 45/40/36 Sound power level (H/M/L) db(a) 47/44/43 50/46/43 58/53/48 59/53/49 58/53/48 59/53/49 60/55/51 Main unit dimensions (H/W/D) mm 256/840/840 256/840/840 319/840/840 319/840/840 319/840/840 319/840/840 319/840/840 Weight kg 20 20 24 24 24 24 24 Panel dimensions (H/W/D) mm 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950 30/950/950 Panel weight kg 4.2 4.2 4.2 4.2 4.2 4.2 4.2 Outdoor unit Compressor type DC twin rotary DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 Max. pipe total length m 50 50 75 75 75 75 75 Maximum height difference m 30 30 30 30 30 30 30 Outer dimensions (H/W/D) mm 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 Weight kg 44 66 93 93 95 95 95 Standard air flow (Fan unit) m 3 /h 2400 3000 6060 6180 6060 6180 6180 Sound pressure level, Cooling/Heating* 2 db(a) 47/48 48/49 49/50 51/52 49/50 51/52 51/53 Sound power level, Cooling/Heating db(a) 63/64 64/65 66/67 68/69 66/67 68/69 68/70 Operating range, Cooling/Heating C -15~43 / -20~15-15~46 / -20~15 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber 7 RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V

Slim duct type Slim design for greater application flexibility Functional design Only 210 mm in height for greater application flexibility. 4-step static pressure setup. Concealed installation within a ceiling void. Auxiliary fresh air intake available. Slim & quiet Quiet, powerful operation. Perfect comfort throughout the room and can be used with any style of air diffuser. 210mm 210mm (RAV-) SM404SDT-E SM454SDT-E SM564SDT-E Outdoor unit Power supply Cooling* 1 Heating* 1 Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E Light Anti-Corrosion protection (RAV-) - - - Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E 1-phase 50Hz 230V (220 240V) Capacity kw 3.6 4.0 5.0 Range, min-max kw 1.5-4.0 1.5-4.5 1.2-5.6 Power consumption kw 1.03 1.20 1.56 EER (Energy Efficiency Ratio) Capacity 100% 3.50 3.33 3.21 Capacity 80% 3.83 3.91 3.45 Capacity 50% 4.34 4.77 4.03 Capacity kw 4.0 4.5 5.6 Range, min-max kw 1.5-5.0 1.5-5.6 0.9-7.4 Power consumption kw 1.00 1.15 1.44 COP (Coefficient of Performance) Capacity 100% 4.00 3.91 3.89 Capacity 80% 4.10 4.09 4.11 Capacity 50% 4.35 4.41 4.52 Standard air flow (H/M/L) m 3 /h 690/600/522 690/600/522 780/678/582 External static pressure-standard (Upper-Lower) Pa 5-15-30-45 5-15-30-45 4-14-29-44 Sound pressure level-under air inlet db(a) 39/36/33 39/36/33 45/40/36 Sound pressure level-back air inlet db(a) 30/28/26 30/28/26 33/31/28 Sound power level (H/M/L) db(a) 54/51/48 54/51/48 60/55/54 Dimensions (H/W/D) mm 210/845/645 210/845/645 210/845/645 Weight kg 22 22 22 Outdoor unit Compressor type DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø12.7 / ø6.4 ø12.7 / ø6.4 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 5 Max. pipe total length m 30 30 50 Maximum height difference m 30 30 30 Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290 Weight kg 40 40 44 Standard air flow (Fan unit) m 3 /h 2400 2400 2400 Sound pressure level, Cooling/Heating* 2 db(a) 45/47 45/47 47/48 Sound power level, Cooling/Heating db(a) 62/64 62/64 63/64 Operating range, Cooling/Heating C -15~43 / -15~15-15~43 / -20~15 Options Auxiliary fresh air flange TCB-FF101URE2 8 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber

Standard duct type Wide range of application opportunities Compact sizing Compact size especially in height (275 mm), new slimmer chassis offers wide range of installation opportunities to customer. Built-in High-lift drain pump The flexible piping layout is made possible by an optionally available drain-pump kit that raises the drain piping up to 850 cm from the drain port. High static pressure External static pressure can be raised as high as 120 Pa, so that all areas of the room can be reached for even temperature distribution, no matter how complex the layout. Flexible duct is accessible, Allows complete design flexibility New spigot shaped flange as new accessories New spigot shaped flange has higher static pressure with optimized design, the static pressure drops only 20Pa from rectangle flange states. Maximum Static pressure will be 100Pa* with all models. (*static pressure with filter which included in, and intake from back ward) (RAV-) SM406BTP-E SM456BTP-E SM566BTP-E SM806BTP-E SM1106BTP-E SM1406BTP-E SM1106BTP-E SM1406BTP-E SM1606BTP-E Outdoor unit Standard (RAV-) SP404ATP-E SP454ATP-E SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E Light Anti-Corrosion protection (RAV-) - - - - SP1104ATZ-E SP1404ATZ-E Heavy Anti-Corrosion protection (RAV-) - - SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8-E, SP1104AT7 SP1104AT8Z-E, SP1104AT7Z SP1104AT8ZG-E, SP1104AT7ZG SP1404AT8-E, SP1404AT7 SP1404AT8Z-E, SP1404AT7Z SP1404AT8ZG-E, SP1404AT7ZG SP1604AT8-E, SP1604AT7 SP1604AT8Z-E, SP1604AT7Z SP1604AT8ZG-E, SP1604AT7ZG Power supply 1-phase 50Hz 230V (220 240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V Cooling* 1 Heating* 1 Capacity kw 3.6 4.0 5.0 7.1 10.0 12.5 10.0 12.5 14.0 Range, min-max kw 1.5-4.0 1.5-4.5 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0 Power consumption kw 1.07 1.23 1.56 2.06 2.64 3.83 2.64 3.86 4.65 EER (Energy Efficiency Ratio) Capacity 100% 3.38 3.24 3.21 3.45 3.79 3.26 3.79 3.24 3.01 Capacity 80% 3.69 3.81 3.23 3.89 4.44 3.83 4.30 3.68 3.41 Capacity 50% 4.19 4.65 3.47 4.93 5.43 4.66 5.71 4.88 4.90 Capacity kw 4.0 4.5 5.6 8.0 11.2 14.0 11.2 14.0 16.0 Range, min-max kw 1.5-5.0 1.5-5.6 0.9-7.4 1.3-10.6 2.4-13.0 2.4-16.5 2.4-15.6 2.4-18.0 2.4-19.0 Power consumption kw 1.04 1.24 1.55 2.21 2.77 3.67 2.77 3.67 4.60 COP (Coefficient of Performance) Capacity 100% 3.84 3.63 3.61 3.62 4.04 3.81 4.04 3.81 3.48 Capacity 80% 3.95 3.79 3.80 3.79 4.25 4.00 4.44 4.18 3.82 Capacity 50% 4.17 4.09 4.12 4.08 4.55 4.29 5.33 5.09 4.98 Standard air flow (H/M/L) m 3 /h 798/630/480 798/630/480 798/630/480 1200/930/720 2100/1650/1260 2100/1650/1260 2100/1650/1260 2100/1650/1260 2100/1650/1260 External static pressure (factory setting) Pa 30 30 30 30 50 50 50 50 50 External static pressure-standard (Upper-Lower) Pa 30(120-30) 30(120-30) 50(120-30) 30-40-50-65-80-100-120 (7 steps) Sound pressure level (H/M/L) db(a) 33/29/25 33/29/25 33/29/25 34/30/26 40/36/33 40/36/33 40/36/33 40/36/33 40/36/33 Sound power level (H/M/L) db(a) 48/44/40 48/44/40 48/44/40 49/45/41 55/51/48 55/51/48 55/51/48 55/51/48 55/51/48 Dimensions (H/W/D) mm 275/700/750 275/700/750 275/700/750 275/1000/750275/1400/750 275/1400/750 275/1400/750 275/1400/750 275/1400/750 Weight kg 23 23 23 30 40 40 40 40 40 Outdoor unit Polygonal rooms Narrow rooms Rooms with fixtures and obstacles Compressor type DC twin rotary DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 Max. pipe total length m 30 30 50 50 75 75 75 75 75 Maximum height difference m 30 30 30 30 30 30 30 30 30 Outer dimensions (H/W/D) mm 550/780/290 550/780/290 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 Weight kg 40 44 66 93 95 95 95 Standard air flow (Fan unit) m 3 /h 2400 3000 6060 6180 6060 6180 6180 Sound pressure level, Cooling/Heating* 2 db(a) 45/47 45/47 47/48 48/49 49/50 51/52 49/50 51/52 51/53 Sound power level, Cooling/Heating db(a) 62/64 62/64 63/64 64/65 66/67 68/69 66/67 68/69 68/70 Operating range, Cooling/Heating C -15~43 / -15~15-15~43 / -20~15-15~46 / -20~15 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber 9 RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V

Ceiling type Smooth curve design & Low noise level Smooth Curve for pliant Shape Flap control New Designed Wide Flap All-new chassis and new rounded design, This new models have been developed in response to customers needs for ceiling units that better match their room interiors. Comfortable ambience The airflow angle is automatically set to the most suitable setting according to your cooling or heating needs, and an automatic swing mode enables airflow to reach all areas of the room to create a comfortable ambience. New fan has adopted the turbulence prevention rib to optimize the ventilating way. Air volume has increased and noise level also has decreased compared with previous model. Winds of new ceiling type of 4HP to 6HP can be reached up to 4.3 metre. Temperature measuring section Center 8m The new air outlet has realized both High noise reduction and large air volume. 8m Previous model New model 30% Extension 3m Previous model New model New Drain pump kit available as an option 8m 8m The Drain pump kit makes draining easier. Glass built into Drain Pump Kit helps reduce mould formation. 3m 0.5m above the floor Temperature (deg.c) 10 16 22 28 34 (C) (RAV-) SM567CTP-E SM807CTP-E SM1107CTP-E SM1407CTP-E SM1107CTP-E SM1407CTP-E SM1607CTP-E Outdoor unit Standard (RAV-) SP564ATP-E SP804ATP-E SP1104AT-E SP1404AT-E Light Anti-Corrosion protection (RAV-) - - SP1104ATZ-E SP1404ATZ-E Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E SP1104ATZG-E SP1404ATZG-E SP1104AT8-E, SP1104AT7 SP1104AT8Z-E, SP1104AT7Z SP1104AT8ZG-E, SP1104AT7ZG SP1404AT8-E, SP1404AT7 SP1404AT8Z-E, SP1404AT7Z SP1404AT8ZG-E, SP1404AT7ZG SP1604AT8-E, SP1604AT7 SP1604AT8Z-E, SP1604AT7Z SP1604AT8ZG-E, SP1604AT7ZG Power supply 1-phase 50Hz 230V (220 240V) / 1-phase 60Hz 220V 3-phase 50Hz 400V (380-415V) / 3-phase 60Hz 380V Cooling* 1 Heating* 1 Capacity kw 5.0 7.1 10.0 12.5 10.0 12.5 14.0 Range, min-max kw 1.2-5.6 1.9-8.0 2.6-12.0 2.6-14.0 2.6-12.0 2.6-14.0 2.6-16.0 Power consumption kw 1.37 1.86 2.45 3.90 2.37 3.72 4.50 EER (Energy Efficiency Ratio) Capacity 100% 3.65 3.82 4.08 3.21 4.22 3.36 3.11 Capacity 80% 4.00 4.37 4.79 3.76 4.62 3.82 3.53 Capacity 50% 4.72 5.63 5.81 4.60 5.21 5.08 5.07 Capacity kw 5.6 8.0 11.2 14.0 11.2 14.0 16.0 Range, min-max kw 0.9-7.4 1.3-10.6 2.4-13.0 2.4-16.5 2.4-14.0 2.4-18.0 2.4-19.0 Power consumption kw 1.28 1.92 2.39 3.62 2.53 3.56 4.31 COP (Coefficient of Performance) Capacity 100% 4.38 4.17 4.69 3.87 4.43 3.93 3.71 Capacity 80% 4.87 4.71 4.92 4.06 4.57 4.31 4.08 Capacity 50% 5.71 5.71 5.23 4.35 4.79 5.22 5.33 Standard air flow (H/M/L) m 3 /h 900/720/540 1410/1002/750 1860/1350/1020 2040/1530/1200 1860/1350/1020 2040/1530/1200 2040/1530/1260 Sound pressure level (H/M/L) db(a) 37/35/28 41/36/29 44/38/32 46/41/35 44/38/32 46/41/35 46/42/36 Sound power level (H/M/L) db(a) 52/50/43 56/51/44 59/53/47 61/56/50 59/53/47 61/56/50 61/57/51 Dimensions (H/W/D) mm 235/950/690 235/1270/690 235/1586/690 235/1586/690 235/1586/690 235/1586/690 235/1586/690 Weight kg 23 29 35 35 35 35 35 Outdoor unit Compressor type DC twin rotary DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 ø15.9 / ø9.5 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 7.5 / 3 Max. pipe total length m 50 50 75 75 75 75 75 Maximum height difference m 30 30 30 30 30 30 30 Outer dimensions (H/W/D) mm 550/780/290 890/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 1340/900/320 Weight kg 44 66 93 93 95 95 95 Standard air flow (Fan unit) m 3 /h 2400 3000 6060 6180 6060 6180 6180 Sound pressure level, Cooling/Heating* 2 db(a) 47/48 48/49 49/50 51/52 49/50 51/52 51/53 Sound power level, Cooling/Heating db(a) 63/64 64/65 66/67 68/69 66/67 68/69 68/70 Operating range, Cooling/Heating C -15~43 / -20~15-15~46 / -20~15 10 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber RAV-SPxx04AT8(Z),(ZG)-E: 3-phase 50Hz 400V (380-415V), RAV-SPxx04AT7(Z),(ZG): 3-phase 60Hz 380V

High wall type Elegant and slim Slim-line design With is attractive, slim-line design, the unit can easily blend in with any room interior. The filtration system further the indoor air quality benefits of this high-wall unit. Self cleaning function Toshiba s self-cleaning function is designed to reduce the humidity that causes mold to form inside an air-conditioning unit 20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils. Optimum air distribution 70 directional Auto-swing louver mode allows optimum air distribution throughout the room. Total comfort is granted, thanks also to Automatic air volume control and Automatic cooling/heating. Cooling mode Heating mode Cooling Normal Operation Moisture stays trapped inside Self-cleaning Function 20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils. SWING (RAV-) SM566KRT-E SM806KRT-E Outdoor unit Power supply Cooling* 1 Heating* 1 Standard (RAV-) SP564ATP-E SP804ATP-E Light Anti-Corrosion protection (RAV-) - - Heavy Anti-Corrosion protection (RAV-) SP564ATJP-E SP804ATJP-E 1-phase 50Hz 230V (220 240V) / 1-phase 60Hz 220V Capacity kw 5.0 7.1 Range, min-max kw 1.2-5.6 1.9-8.0 Power consumption kw 1.44 2.21 EER (Energy Efficiency Ratio) Capacity 100% 3.47 3.21 Capacity 80% 3.81 3.76 Capacity 50% 4.31 4.61 Capacity kw 5.6 8.0 Range, min-max kw 0.9-7.3 1.3-10.6 Power consumption kw 1.50 2.34 COP (Coefficient of Performance) Capacity 100% 3.73 3.42 Capacity 80% 3.86 3.58 Capacity 50% 4.06 3.85 Standard air flow (H/M/L) m 3 /h 840/750/660 1020/750/660 Sound pressure level (H/M/L) db(a) 42/39/36 47/41/36 Sound power level (H/M/L) db(a) 57/54/51 62/56/51 Dimensions (H/W/D) mm 320/1050/228 320/1050/228 Weight kg 12 12 Outdoor unit Compressor type DC twin rotary Connecting pipe dia., Gas/Liquid side mm ø12.7 / ø6.4 ø15.9 / ø9.5 Standard / Min. pipe length m 7.5 / 5 7.5 / 5 Max. pipe total length m 50 50 Maximum height difference m 30 30 Outer dimensions (H/W/D) mm 550/780/290 890/900/320 Weight kg 44 66 Standard air flow (Fan unit) m 3 /h 2400 3000 Sound pressure level, Cooling/Heating* 2 db(a) 47/48 48/49 Sound power level, Cooling/Heating db(a) 63/64 64/65 Operating range, Cooling/Heating C -15~43 / -20~15 *1 Rated conditions Cooling : Indoor air temperature 27 o C DB / 19 o C WB, Outdoor air temperature 35 o C DB Heating : Indoor air temperature 20 o C DB, Outdoor air temperature 7 o C DB / 6 o C WB *2 Sound pressure levels measured in an anechoic chamber 11

Twin and Triple system Twin system: Super Digital Inverter 1-phase Twin system: Super Digital Inverter 3-phase type Compact 4-way cassette 4-way cassette Slim duct Standard duct Ceiling High wall Compact 4-way cassette 4-way cassette Slim duct Standard duct Ceiling High wall Outdoor unit (RAV-) (RAV-) HP Rated Cooling Capacity EER Heating Capacity COP min-max Power consumption 100% 80% 50% Rated min-max Power consumption 100% 80% 50% SP804AT(J)P-E SM404MUT-E 3 7.1 1.9-8.0 2.21 3.21 3.69 4.77 8.0 1.3-10.6 2.16 3.70 4.18 5.06 SP1104AT(Z)(ZG)-E SM564MUT-E 4 10.0 2.6-12.0 2.67 3.75 4.23 5.17 11.2 2.4-13.0 2.67 4.19 4.39 4.71 SP1104AT(Z)(ZG)-E SM564UTP-E 4 10.0 2.6-12.0 2.21 4.52 5.31 6.49 11.2 2.4-13.0 2.34 4.79 5.01 5.38 SP1404AT(Z)(ZG)-E SM804UTP-E 5 12.5 2.6-14.0 3.16 3.96 4.64 5.67 14.0 2.4-16.5 3.21 4.36 4.57 4.90 SP804AT(J)P-E SM404SDT-E 3 7.1 1.9-8.0 2.21 3.21 3.69 4.77 8.0 1.3-10.6 2.16 3.70 4.18 5.06 SP1104AT(Z)(ZG)-E SM564SDT-E 4 10.0 2.6-12.0 2.77 3.61 4.39 5.36 11.2 2.4-13.0 2.67 4.19 4.39 4.71 SP804AT(J)P-E SM406BTP-E 3 7.1 1.9-8.0 2.06 3.45 3.89 4.92 8.0 1.3-10.6 2.21 3.62 3.79 4.08 SP1104AT(Z)(ZG)-E SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.44 5.43 11.2 2.4-13.0 2.77 4.04 4.25 4.55 SP1404AT(Z)(ZG)-E SM806BTP-E 5 12.5 2.6-14.0 3.83 3.26 3.83 4.66 14.0 2.4-16.5 3.67 3.81 4.00 4.29 SP1104AT(Z)(ZG)-E SM567CTP-E 4 10.0 2.6-12.0 2.45 4.08 4.79 5.81 11.2 2.4-13.0 2.39 4.69 4.92 5.23 SP1404AT(Z)(ZG)-E SM807CTP-E 5 12.5 2.6-14.0 3.90 3.21 3.76 4.60 14.0 2.4-16.5 3.62 3.87 4.06 4.35 SP1104AT(Z)(ZG)-E SM566KRT-E 4 10.0 2.6-12.0 2.77 3.61 4.24 5.17 11.2 2.4-13.0 2.80 4.00 4.19 4.48 SP1404AT(Z)(ZG)-E SM806KRT-E 5 12.3 2.6-13.5 3.88 3.17 3.72 4.54 14.0 2.4-16.5 3.83 3.66 3.84 4.12 SP1104AT8(Z)(ZG)-E SM564MUT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54 SP1104AT7(Z)(ZG) SM564MUT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54 SP1104AT8(Z)(ZG)-E SM564UTP-E 4 10.0 2.6-12.0 2.37 4.22 4.79 5.88 11.2 2.4-15.6 2.42 4.63 5.09 6.09 SP1104AT7(Z)(ZG) SM564UTP-E 4 10.0 2.6-12.0 2.37 4.22 4.79 5.88 11.2 2.4-15.6 2.42 4.63 5.09 6.09 SP1404AT8(Z)(ZG)-E SM804UTP-E 5 12.5 2.6-14.0 3.46 3.61 4.46 5.43 14.0 2.4-18.0 3.42 4.09 4.50 5.47 SP1404AT7(Z)(ZG) SM804UTP-E 5 12.5 2.6-14.0 3.46 3.61 4.46 5.43 14.0 2.4-18.0 3.42 4.09 4.50 5.47 SP1604AT8(Z)(ZG)-E SM804UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33 SP1604AT7(Z)(ZG) SM804UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33 SP1104AT8(Z)(ZG)-E SM564SDT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54 SP1104AT7(Z)(ZG) SM564SDT-E 4 10.0 2.6-12.0 2.79 3.58 4.06 5.00 11.2 2.4-14.0 2.67 4.19 4.59 5.54 SP1104AT8(Z)(ZG)-E SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.30 5.71 11.2 2.4-15.6 2.77 4.04 4.44 5.33 SP1104AT7(Z)(ZG) SM566BTP-E 4 10.0 2.6-12.0 2.64 3.79 4.30 5.71 11.2 2.4-15.6 2.77 4.04 4.44 5.33 SP1404AT8(Z)(ZG)-E SM806BTP-E 5 12.5 2.6-14.0 3.86 3.24 3.68 4.88 14.0 2.4-18.0 3.67 3.81 4.18 5.09 SP1404AT7(Z)(ZG) SM806BTP-E 5 12.5 2.6-14.0 3.86 3.24 3.68 4.88 14.0 2.4-18.0 3.67 3.81 4.18 5.09 SP1604AT8(Z)(ZG)-E SM806BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98 SP1604AT7(Z)(ZG) SM806BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98 SP1104AT8(Z)(ZG)-E SM567CTP-E 4 10.0 2.6-12.0 2.37 4.22 4.62 5.21 11.2 2.4-14.0 2.53 4.43 4.57 4.79 SP1104AT7(Z)(ZG) SM567CTP-E 4 10.0 2.6-12.0 2.37 4.22 4.62 5.21 11.2 2.4-14.0 2.53 4.43 4.57 4.79 SP1404AT8(Z)(ZG)-E SM807CTP-E 5 12.5 2.6-14.0 3.72 3.36 3.82 5.08 14.0 2.4-18.0 3.56 3.93 4.31 5.22 SP1404AT7(Z)(ZG) SM807CTP-E 5 12.5 2.6-14.0 3.72 3.36 3.82 5.08 14.0 2.4-18.0 3.56 3.93 4.31 5.22 SP1604AT8(Z)(ZG)-E SM807CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33 SP1604AT7(Z)(ZG) SM807CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33 SP1104AT8(Z)(ZG)-E SM566KRT-E 4 10.0 2.6-12.0 2.92 3.42 4.02 4.91 11.2 2.4-14.0 2.85 3.93 4.13 4.41 SP1104AT7(Z)(ZG) SM566KRT-E 4 10.0 2.6-12.0 2.92 3.42 4.02 4.91 11.2 2.4-14.0 2.85 3.93 4.13 4.41 SP1404AT8(Z)(ZG)-E SM806KRT-E 5 12.3 2.6-13.5 4.00 3.08 3.61 4.41 14.0 2.4-18.0 3.88 3.61 3.97 4.24 SP1404AT7(Z)(ZG) SM806KRT-E 5 12.3 2.6-13.5 4.00 3.08 3.61 4.41 14.0 2.4-18.0 3.88 3.61 3.97 4.24 SP1604AT8(Z)(ZG)-E SM806KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86 SP1604AT7(Z)(ZG) SM806KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86 Triple system: Super Digital Inverter 3-phase type Compact 4-way cassette 4-way cassette Slim duct Standard duct Ceiling High wall Outdoor unit (RAV-) (RAV-) HP Rated Cooling Capacity EER Heating Capacity COP min-max Power consumption 100% 80% 50% Rated min-max Power consumption 100% 80% 50% SP1604AT8(Z)(ZG)-E SM564MUT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 4.58 16.0 2.4-19.0 4.60 3.48 3.82 5.00 SP1604AT7(Z)(ZG) SM564MUT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 4.58 16.0 2.4-19.0 4.60 3.48 3.82 5.00 SP1604AT8(Z)(ZG)-E SM564UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33 SP1604AT7(Z)(ZG) SM564UTP-E 6 14.0 2.6-16.0 4.49 3.12 3.53 5.07 16.0 2.4-19.0 4.30 3.72 4.09 5.33 SP1604AT8(Z)(ZG)-E SM564SDT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 5.00 16.0 2.4-19.0 4.60 3.48 3.18 5.00 SP1604AT7(Z)(ZG) SM564SDT-E 6 14.0 2.6-16.0 4.99 2.81 3.18 5.00 16.0 2.4-19.0 4.60 3.48 3.18 5.00 SP1604AT8(Z)(ZG)-E SM566BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98 SP1604AT7(Z)(ZG) SM566BTP-E 6 14.0 2.6-16.0 4.65 3.01 3.41 4.90 16.0 2.4-19.0 4.60 3.48 3.82 4.98 SP1604AT8(Z)(ZG)-E SM567CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33 SP1604AT7(Z)(ZG) SM567CTP-E 6 14.0 2.6-16.0 4.50 3.11 3.53 5.07 16.0 2.4-19.0 4.31 3.71 4.08 5.33 SP1604AT8(Z)(ZG)-E SM566KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86 SP1604AT7(Z)(ZG) SM566KRT-E 6 14.0 2.6-16.0 5.10 2.75 3.22 3.93 16.0 2.4-19.0 4.88 3.28 3.60 3.86 12

Options TCB-FF101URE2 TCB-GFC1602UE 4-way cassette type Spacer for height adjustment Fresh air inlet box TCB-GB1602UE Air discharge direction kit TCB-BC1602UE RBC-U31PGP(W)-E RBC-U31PGP(WS)-E Spacer for height adjustment TCB-SP1602UE Panel RBC-U31PGP(W)-E RBC-U31PGP(WS)-E Air inlet grille Air discharge parts A Packing A Air discharge parts B Packing B Refrigerant piping side Drain piping side Air discharge parts C Packing B Standard duct type 694 TCB-SF56C6BPE TCB-SF80C6BPE TCB-SF160C6BPE 994 1394 Model TCB-SF56C6BPE TCB-SF80C6BPE TCB-SF160C6BPE Compatible (RAV-) SM406BTP-E, SM456BTP-E, SM566BTP-E SM806BTP-E SM1106BTP-E, SM1406BTP-E (Unit:mm) TCB-KP13CE, TCB-KP23CE Elbow piping Ceiling type RBC-AX33CE Wireless remote controller TCB-DP31CE Drain pump kit TCB-PCUC1E Optional connecting kit 13

Controllers & Accessories Parts Name Model Name Applied Model Remarks RBC-AMT32E Wired remote controller RBC-AMS41E RBC-AMS51E-ES/-EN Simple wired remote controller RBC-AS41E Controllers RBC-AX32U(W)/(WS)-E 4-way cassette Wireless remote controller kits RBC-AX33CE Ceiling TCB-AX32E2 TCB-EXS21TLE - Use with wired remote controller TCB-CC163TLE2 - Use with wired remote controller Remote controller kits TCB-SC642TLE2 BMS-CM1280TLE TCC-Link TCB-PCNT30TLE2 except High-wall Fresh air inlet box TCB-GB1602UE Use with TCB-GFC1602UE 4-way cassette Fresh air filter chamber TCB-GFC1602UE Auxiliary fresh air flange TCB-FF101URE2 4-way cassette, compact 4-way cassette and Slim duct Branch kit Accessories Application control Spacer for height adjustment TCB-SP1602UE 4-way cassette Air discharge direction kit TCB-BC1602UE 4-way cassette Drain pump kit TCB-DP31CE Ceiling Use with TCB-KP13CE, TCB-KP23CE TCB-KP13CE Ceiling Elbow piping kit TCB-KP23CE Ceiling Optional connecting kit TCB-PCUC1E Ceiling RBC-TWP30E2 Super Digital Inverter 1-phase, 3-phase model RBC-TWP50E2 RBC-TRP100E "1:3" Triple system of Super Digital Inverter 3-phase model TCB-PCOS1E2 Super Digital Inverter 1-phase model TCB-KBOS2E Features Inverter Features Allows step-less regulation of the air-conditioner s power,which reduces energy consumption and improves comfort. Applied Model Individual Louver control Enables airflows to be chosen according to user preferences. 4-way cassette Auto-turn Louver Air outlet grilles move automatically to fill every corner of the room with warm or cool air. except Slim duct and Standard duct Comfort Automatic Air Volume control Depending on the difference between the room temperature and the set temperature, switches automatically between High, Low and Very Low. Long-life Filter Built-in long-life filter makes maintenance easier. except High wall Hot Start When using the heater for preheating or defrosting, stops the indoor fan to prevent cold air from being blown into the room. Dry Gradually dehumidifies the room to create even greater comfort. Filter Sign Automatic displays on the remote controller say when to perform maintenance for the indoor unit filter. except High wall Operativity Limit Timer On/Off Timer Uses a 168-hour timer with three modes - ON timer, OFF timer and Repeat OFF timer. The operation start and stop times can be set with a digital clock. except High wall High wall 20 minutes of fan operation after shut down 20 minutes of fan operation after shut down dries the moist air and helps reduce mold formation on heat exchanger coils. High wall Installation Cooler Compatible with an Outdoor Temperature of -15 C Built-in Drain Pump Stable cooler operation is possible when the outdoor temperature is as low as -15 C. The built-in drain pump makes draining easier. (In the ceiling cassette type, it is built in to the main unit.) except High wall 14

Remote controllers Lite-Vision plus Remote Controller RBC-AMS51E-ES RBC-AMS51E-EN Wired remote controller with a built in 7-day timer-featuring a new multi-language, LCD display with backlight, energy saving options and a return back function. Possibility to set and display the room name to easily set-up and monitor the working parameter. New modern and desirable controller design with menu driven display. Save mode by schedule timer to optimise energy consumption. Room temperature display always available. Two Hot Keys (F1, F2) for easy operation of air conditioner functions. Easy to read layout including display of indoor unit model name and serial number. Built-in backup power. Settings are kept in memory up to 72 hours in case of power failure. Remote TA sensor available in controller. Can be connected to a single indoor unit or a group of up to 8 indoor units. RBC-AMT32E Standard Remote controller Standard wired remote controller can be connected to a single indoor unit or a group of up to 8 indoor units. Power save operation limits the greatest current value. The remote controller allows error to be displayed while the protective device works or a error occurs. RBC-AMS41E Remote controller with weekly timer (7-day timer function) Wired remote controller with clock display and a built in 7-day timer function, possible to program 8 functions for each day of the week. *The following items can be set in program: operation time, operation start/stop, operation mode, temperature setting, restriction on button operation TCB-SC642TLE2 Central remote controller Individual control for max. 64 indoor units divided into 1 to 4 zone (Up to 16 indoor units for each zone) Up to 16 outdoor header units are connectable 4 types of central control settings to inhibit individual operation by remote controller can be selected Usable with other central control devices (Max. 10 devices in one control circuit) Two control mode selectivity (Central controller mode ) Remote controller mode Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer. BMS-CM1280TLE Central remote controller Operation Individual operation of 128 indoor units available Return Back Operation Weekly Schedule Operation* (ON/OFF) * Schedule timer necessary Monitoring Zone setting (64 zones x 2) Individual unit operation mode operation restriction Alarm display Control input Status output RBC-AS41E Simple wired remote controller Simple wired remote controller can be connected to a single indoor unit or a group of up to 8 indoor units. Start/Stop Temperature setting Air flow changing Check code display TCB-EXS21TLE Schedule timer Schedule timer mode 6 programmings per day Enabling 8 groups to be programmed A maximum of 64 indoor units can be controlled A maximum of 100 hours back-up power supply Weekly timer mode 7 types of weekly schedule and 3 programmings per day TCB-CC163TLE2 ON-OFF controller Individual control of up to 16 indoor units. Setting of simultaneous ON/OFF 3 times per day combined with the weekly timer. Wireless remote controller kit Start/Stop Changing mode Temperature setting Air flow changing Timer function Either ON time or OFF time or CYCLIC can be set how many 30 min. later ON or OFF is operated. Control by 2 remote controllers is available. Two wireless remote controllers can operate one indoor unit. The indoor unit can then be operated separately from the two different locations. Check code display RBC-AX32U(W)/(WS)-E Integral receiver (For 4-way cassette) RBC-AX33CE Integral receiver (For ceiling) TCB-AX32E2 Sensor unit; Stand alone receiver (For 4-way cassette, Compact 4-way cassette (600 x 600), Ceiling, Duct type, High wall) 15

Installation and the use of refrigerants not specified by Toshiba Carrier Corporation Toshiba refrigeration and air-conditioning units are designed and manufactured on the assumption that the product is used with a specific refrigerant suitable for each unit. We have recently seen some cases where the type of refrigerant used is different from the one originally installed in the product. Such actions may cause mechanical defects, malfunctions, failures and in some cases result in a serious safety issue. Therefore do not install any refrigerant other than the one specified by Toshiba Carrier Corporation for its respective products. The type of the refrigerant used for each of our products is shown in the accompanying owners manual, or on the product label attached on the product itself. Toshiba Carrier Corporation shall not assume any liability for failures, malfunctions or safety in its products if the refrigerant used is different from the one specified. SAFETY PRECAUTIONS For operation: Before use, read through the operating instructions to ensure proper use. Concerning the purpose for which the air conditioners are to be used The air conditioners presented in this catalogue are air conditioning/heating units to be used solely by general consumers. Do not use these air conditioners for special applications such as for the storage of food items, animals, plants, precision machines or works of art. Doing so may degrade the quality of the items. Do not use these air conditioners for air-conditioning applications in vehicles or ships. Doing so may cause water and/or power leakages. Precautions for using air conditioners Concerning the automatic defrosting unit When the outdoor air temperature drops, frost may form on the heat exchanger of the outdoor unit. In such cases, the automatic defrosting unit will be activated, and it will take 5 to 8 minutes for the heating operation to be restored. Concerning the air conditioner's operating conditions and their selection (1) Avoid using the air conditioner in the following locations. Locations with acidic or alkaline atmospheres (locations at which highly acidic or alkaline air is directly drawn in, such as in hot springs areas from which sulfur gases are given off, or where chemicals, vinegar, exhaust air from burners, etc., are given off) The heat exchangers and other parts may become corroded. Locations with atmospheres filled with coolant or other machine oil or steam exhaust (such as at food preparation factories or machine plants). The heat exchangers may corrode; frost may form as a result of heat exchanger malfunction; air conditioner operating performance may be compromised or condensation may form as a result of clogged filters; plastic parts may incur damage; heat-insulation materials may become separated, etc. (2) Before using an air conditioner in any of the following locations, consult with your dealer or a qualified contractor. Locations where vapors from edible oils are given off (such as in bakeries or kitchens and restaurants that use edible oils)...the air conditioner's operating performance may be compromised or condensation may form as a result of clogged filters, and the plastic parts may incur damage. In line with the prevailing conditions, take countermeasures such as tailoring the installation conditions in accordance with the conditions, using air conditioners designed for kitchens or oil guard filters, etc. Locations with disinfectant-induced chlorine atmospheres (water tanks, etc.) The metal parts in the heat exchangers, motors, etc., may become corroded. Locations with high salinity (coastal areas, etc.) Corrosion may occur so use outdoor units specifically designed to withstand exposure to salt. Locations where power is supplied from independent power generators. The power line frequency and/or voltage may fluctuate, possibly causing the air conditioner to malfunction. Locations where high frequencies or electrical noise is generated (from high-frequency welders used for vinyl welding and processing, high-frequency therapeutic devices used for thermotherapy, etc.) The electronic components may be adversely affected, possibly causing the air conditioner to malfunction. Locations where electronic equipment is installed. Electrical noise may adversely affect the operation of the electronic equipment. (3) Concerning use in locations with high ceilings In locations with high ceilings, use of circulators for improving the temperature distribution during heating is recommended. (4) Concerning use in high-humidity environments When the ceiling-recessed type of indoor unit is installed in a location, such as those described below, and it is very hot and humid inside the ceiling, condensation may form on the external surfaces of the indoor unit and drip down. In such cases, add external heat-insulating materials. Locations such as food preparation sites in which the areas above the ceilings are hot and humid Locations in which outside air is drawn in and routed above the ceiling Above ceilings with a slate roof or tiled roof overhead (5) Even when an air conditioner is shut down, it will still consume a small amount of power to protect the unit. If the air conditioner will not be used for a prolonged period, turn OFF the main switch (ground fault circuit breaker). However, before the unit is to be used again, turn ON the main switch (ground fault circuit breaker) for at least 12 hours in order to prevent trouble. Notice: - Products listed in this leaflet use HFC refrigerant R410A with a GWP of 2,088*. - Toshiba is committed to continuously improving its products to ensure the highest quality and reliability standards, and to meet local regulations and market requirements. All features and specifications are subject to change without prior notice. *The GWP value is calculated based on information provided in the EU F-gas Regulation and IPCC Fourth Assessment Report. T201511-LC-SDI