VeriFlame CE Burner Monitoring System

Similar documents
UV Scanner. Model Specification. Introduction. 854 Instruction Manual

Eclipse 90 UV Scanner Model A Version 1

FIREYE FLAME SAFEGUARD CONTROLS DESCRIPTION

Instruction Manual 826 7/22/2009. Eclipse Bi-Flame Dual Burner Monitoring System Model 6500 Version 1

Eclipse Self-Check UV Scanner

MBCE-110/230FR Flame Sensor Module

MBCE-110/230UV Flame Sensor Module

MBCE-110/230FR Flame Sensor Module

Design Guide 111 9/25/2008. Eclipse Winnox Burners WX Series Version 1

Design Guide No /01. RatioMatic Burners. RM Series Version 3.10

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

Design Guide /12/2008. Eclipse RatioAir Burners RA Series Version 1

Eclipse AirHeat Burner

BGH Series Hot Surface Ignition Control

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

Eclipse AirHeat Burners

Eclipse ER Indirect Air Heater

Eclipse RatioMatic Burners

Flame Rod Manual. Publication Rev A

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Distributed By: M&M Control Service, INC

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Interrupted Ignition Series Oil Primary Control

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

LAE10 LFE10. Use. Series 02

Installation, Operation & Service Manual

Flame Safeguards LFE10. Building Technologies HVAC Products

Model Universal Oil Primary Control

Model 60200FR Gas Primary Control Data Sheet

Power Flame Incorporated

Flame Safeguards LFE10. Building Technologies HVAC Products

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

SAFETY INFORMATION AND WARNINGS

7800 SERIES Relay Modules

BURNER MANAGEMENT CONTROLS

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

LFL Series Burner Flame Safeguard Control

FIREYE C9707A ALL FUEL SCANNER

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Flame Safeguard Fault Code Diagnostics

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Power Flame Incorporated

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

Operator: Save these instructions for future use!

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

UV Flame Supervision System

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

EUROBOX SERIES TYPES CM... SM... MM...

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded

IFT-RC150 IntelliFire Touch Remote Control Installation Instructions

CA5000 Liquid CO 2 Freezer Backup System

50A Integrated Furnace Control

Duct and Rough Service Carbon Monoxide Sensor

Model 3300 Technical Support and Installation Manual

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Fireye FLAME SCANNERS

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

Eclipse AirHeat Burners AH Series version 2.00 (Patent Pending)

Hot Surface Ignition (HSI) System Booklet

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

50A Integrated Furnace Control

B-40/B-41 Modulating Temperature Controller

Q - Series Boiler. Troubleshooting Manual

24 VAC Intermittent Pilot Gas Ignition Control

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

FIREYE YZ300 and YZ320 INTERLOCK ANNUNCIATOR For use with the Fireye BurnerLogix Control

ECLIPSE INFORMATION GUIDE

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

OPERATING AND MAINTENANCE MANUAL

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

SECTION GAS-FIRED RADIANT HEATERS

Operator: Save these instructions for future use!

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

Static Pressure Control

Indirect gas-fired air heater

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LC3000 Level Controller Installation and Maintenance Instructions

FIREYE FLAME SCANNERS

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER)

BasicTroubleshooting Information and Guidelines

Transcription:

Instruction Manual No. 818-2 9/02 VeriFlame CE Burner Monitoring System Model VF56 Version 2.0

COPYRIGHT DISCLAIMER NOTICE Copyright 2002 by Eclipse Combustion. All rights reserved worldwide. This publication is protected by federal regulation and shall not be copied, distributed, transmitted, transcribed or translated into any human or computer language, in any form or by any means, to any third parties, without the express written consent of Eclipse Combustion. In accordance with the manufacture s policy of continual product improvement, the product presented in this brochure is subject to change without notice or obligation. The material in this manual is believed adequate for the intended use of the product. If the product is used for purposes other than those specified herein, confirmation of validity and suitability must be obtained. Eclipse Combustion warrants that the product itself does not infringe upon any United States patents. Not further warranty is expressed or implied. We have made every effort to make this manual as accurate and complete as possible. Should you find errors or omissions, please bring them to our attention so that we may correct them. In this way we hope to improve our product documentation for the benefit of our customers. Please send your corrections and comments to our Marketing Communications Manager. LIABILITY AND WARRANTY It must be understood that Eclipse Combustion s liability for its product, whether due to breach of warranty, negligence, strict liability, or otherwise is limited to the furnishing of replacement parts and Eclipse Combustion will not be liable for any other injury, loss, damage or expenses, whether direct or consequential, including but not limited to loss of use, income, or damage to material arising in connection with the sale, installation, use of, inability to use, or the repair or replacement of Eclipse Combustion s products. 2 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

About this manual AUDIENCE SCOPE This manual has been written for the people who select and install the product and the technicians who work on it. They are expected to have previous experience, training, and knowledge with this kind of equipment. This manual contains essential information for the proper installation and operation of the Eclipse VeriFlame Single Burner Monitoring System. Following the instructions in this manual should assure trouble free installation and operation. Read this manual carefully. Make sure that you understand its structure and contents. Obey all the safety instructions. Do not deviate from any instructions or application limits in this manual without written consent from Eclipse Combustion. If you do not understand any part of the information in this manual, do not continue. Contact your Eclipse sales office or Eclipse Combustion, Rockford, Illinois. HOW TO GET HELP If you need help, you can contact your local Eclipse Combustion sales office. You can reach Power Equipment Company at: 12011 Williamsburg Road Richmond, Virginia 23231 U.S.A. Phone: 804-236-3800 Fax: 804-236-3882 www.peconet.com Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 3

DOCUMENT CONVENTIONS There are several special symbols in this document. You must know their meaning and importance. The explanation of these symbols follows. Please read it thoroughly. Danger: Indicates hazards or unsafe practices that WILL result in severe personal injury or even death. Only qualified and well-trained personnel are allowed to carry out these instructions or procedures. Act with great care and follow the instructions. Warning: Indicates hazards or unsafe practices that could result in severe personal injury or damage. Act with great care and follow the instructions. Caution: Indicates hazards or unsafe practices that could result in damage to the machine or minor personal injury. Act carefully. Note: Indicates an important part of the text. Read the text thoroughly. 4 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

Table of contents Copyright... 2 Disclaimer Notice... 2 Liability and Warranty... 2 Audience... 3 Scope... 3 How To Get Help... 3 Document Conventions... 4 1 Introduction... 7 Product Description... 7 Control Unit... 7 Wiring Base... 7 Sensor... 7 CE Conformity... 8 2 Specifications... 10 Power Supply... 10 Output Ratings... 10 Dimensions... 11 3 Function Summary... 13 Introduction... 13 Standard Features... 13 Optional Features... 15 System Errors and Lockout Conditions... 16 Status Lights & Push-button... 17 Figure 3 1 Typical Sequence for NO-PURGE Models... 18 Figure 3 2 Typical Sequence for PURGE Models... 19 Figure 3 3 Typical Sequence for Modulation Models... 19 4 System Installation... 20 Introduction... 20 Figure 4 1 Wiring for No-Purge Models... 23 Figure 4 2 Wiring for Purge Models... 23 Figure 4 3 Wiring for Direct Spark of Main Flame, No-&Purge Models... 24 Figure 4 4 Wiring for Modulation Models... 24 Figure 4 5 Wiring for Direct Spark of Main Flame, Modulation Models... 24 Figure 4 6 Wiring for Models 5600-90, -91, -91N4 UV Scanners... 25 Figure 4 7 Wiring for Flame Rod... 25 Figure 4 8 Wiring for Models 5602-91 Self-Check UV Scanner... 25 Figure 4 9 Wiring for Model 5602DB, 24VDC Remote Display... 25 Figure 4 10 Wiring for Model 5602DBP, 120VAC Remote Display... 25 Figure 4 11 Base Layout for NO-PURGE and PURGE Models... 26 Figure 4 12 Base Layout for MODULATION Models... 26 5 Sensor Installation... 27 Introduction... 27 Sensor Wiring... 27 Flame Rods... 28 Figure 5 1 Flame Rod Position... 28 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 5

Scanners... 29 Figure 5 2 Scanner Sighting... 29 6 Test Procedures... 30 Introduction... 30 Flame Signal Strength... 30 Minimum Pilot Test... 30 Pilot Flame Failure Test... 31 Main Flame Failure Test... 31 Spark Sighting Test... 31 Limits and Interlocks Test... 31 7 Maintenance and Troubleshooting... 32 Introduction... 32 Maintenance... 32 Monthly Check List... 33 Yearly Check List... 33 Troubleshooting... 34 LED Status... 36 Figure 7 1 NoPurge Model... 37 Figure 7 2 Purge Model... 37 Figure 7 3 Modulation Model... 37 8 Remote Display Messages... 38 Introduction... 38 Elapsed Time Indicator... 38 Flame Signal Strength Readout... 38 Keypad Operation Remote Reset... 38 Figure 8 1 Startup... 39 Figure 8 2 Purge, TFI, and Main... 40 Figure 8 3 Main Firing... 41 Figure 8 4 Shutdown... 42 Remote Display Message Listing... 43 9 Appendix... 46 Product Model Number Guide... 46 Illustrated Parts List... 47 6 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

Introduction 1 PRODUCT DESCRIPTION The Eclipse Combustion VeriFlame CE Single Burner Monitoring System consists of a microprocessor based control unit, a wiring base, and a flame sensor. CONTROL UNIT WIRING BASE SENSOR The control unit includes all the necessary digital logic and analog measuring circuitry to control the sequence and monitor the flame of single gas, oil or combination gas/oil burners. Three available control sequences are no-purge, purge, and modulation (air damper control). The part number specifies the various features such as the flame sensor type, sequences, and timings; thus the designer has control and protection against field tampering of critical sequences. The wiring base provides a convenient means for connecting field wiring from the burner and valve system to the control unit. There are three styles of bases: an internal terminal base that provides a guarded wiring compartment; an external terminal base for use within a protective control panel; and an expanded external terminal base for use with the modulation sequence control units. Sensors that may be used with the VeriFlame include flame rod (rectified ionization), ultra-violet (UV) scanners, and self-checking UV scanners. Four types of UV scanners meet the demands of various environmental conditions. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 7

CE CONFORMITY This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC Directive, and 90/396/EEC the Gas Appliance Directive based on examination to EN298 Automatic gas burner control systems for gas burners and gas burning appliances with or without fans. Conformity of this product with any other CE Mark Directive(s) shall not be assumed. Product Classification: Class I: Permanently connected, panel-mounted Industrial Control Equipment with protective earthing (grounding) on metal bases. (EN61010-1). Enclosure Rating: panel-mounted equipment rated IP00, when used with the external terminal wiring bases (the terminals must be enclosed within the panel.) IP30 when used with internal terminal bases. (IEC 529). Installation Category (Overvoltage Category): Category II: Energy-consuming equipment supplied from the fixed installation, local level appliances, and Industrial Control Equipment. (EN61010-1) Pollution Degree: Pollution Degree 2: Normally nonconductive pollution with occasional conductivity caused by condensation. (Ref. IEC 664-1) EMC Classification: Group 1, Class A, ISM Equipment (EN55011, emissions), Industrial Equipment (EN50082-2, immunity) Method of EMC Assessment: Technical File (TF) Declaration of Conformity: EC-87/02/57/a EC Product Identification Number: 87BN57 Deviation from the installation conditions specified in this manual may invalidate this product s conformity with the Low Voltage, EMC, and Gas Appliance Directives. 8 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

CE CERTIFICATE Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 9

Specifications 2 POWER SUPPLY 102-132 VAC, 50/60 Hz 204-264 VAC, 50/60 Hz 12 VA internal consumption, excludes externally connected loads Unit Model No. Temperature Range Weight VeriFlame VF56-40 to +60 C -40 to 140 F 1.09 kg 90-degree UV Scanner 5600-90A -20 to +60 C -4 to 140 F.25 kg Straight UV Scanner 5600-91 -20 to +125 C -4 to 257 F.30 kg Straight UV - Sealed 5600-91N4-20 to +125 C -4 to 257 F.20 kg Self-Check UV Scanner 5602-91 -20 to +60 C -4 to 140 F 1.20 kg 24VDC Remote Display 5602DB 0 to +50 C 32 to 122 F.36 kg 120VAC Remote Display 5602DBP 0 to +50 C 32 to 122 F.50 kg OUTPUT RATINGS Function Terminal Inductive Load The maximum total connected load must not exceed 15 amps. Gas Valves 3, 5 175VA Ignition Transformer 4 375VA Motor or Contactor 8 470VA Control A, 10, 11, 12, 13 175VA 10 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

DIMENSIONS VeriFlame Control Unit, all models VeriFlame Bases, NO-PURGE and PURGE sequence models VeriFlame MODULATION sequence model, Base Model Number 5602-40 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 11

Remote Display Model Number 5602-DB p.n. 20317: 24VDC Power Supply for Remote Display 5602-DB Remote Display Model Number 5602-DBP 12 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

Function Summary 3 INTRODUCTION This section describes the features of the VeriFlame CE. It is presented in three categories: Standard Features, Optional Features, System Errors and Lockout Conditions, and the LED Indicator Lights. STANDARD FEATURES Interlocks and Limit Switch Input (Terminal 7) Combustion Air Switch Input (Terminal 6) The following functions are standard features on the VeriFlame models as noted. This input is considered the normal operation control or run input to the VeriFlame system. Interlocks are generally pressure or temperature switches that when activated will start the burner. Limit switches are generally pressure, temperature, and other switches that when activated will stop the burner. The interlocks and limit switches are wired in series. A break in this circuit will shut the burner down, but will not produce an alarm or lockout condition. For PURGE and MODULATION sequence models: This input is for monitoring the combustion air switch separately from other interlocks and limits. The VeriFlame checks the air flow switch input is open before start-up, closed during operation, and open again at burner shutdown, thus preventing operation with an air switch that is defective, maladjusted or bypassed. This input has about a 1 second delay to filter out and ignore a momentary interruption. If the input is improperly powered before the fan output is energized, the system error light will blink. The input must de-energize within 30 seconds or the VeriFlame will alarm and lockout. After the fan output has energized, the air switch input must be made within 10 seconds. If not proven, then the system will lockout and the alarm output and the air failure light will come on. However, if the unit has the air switch input hold feature, the sequence is held indefinitely without causing a lockout. Then when the air switch input is made, the sequence continues. If the air switch opens during the main firing cycle, the Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 13

Pre-Purge system will lockout and the alarm output and the air failure light will come on. However, if the unit has the recycle option and the main output has been operating for at least 35 seconds, the VeriFlame will shut-down and restart. For PURGE sequence models: The VeriFlame delays the sequence after the air switch is proven by the specified purge time. Once completed, the sequence continues to the trial for ignition. For MODULATION sequence models: The purge time is doubled into two sequences. The first is a high fire purge for the specified time. The second is a low fire purge allowing the air butterfly valve time to achieve starting position. Sequence Step Internal Contacts Function Main Fuel Valve Closed Switch (Terminal V) Main Fuel Valve Closed / High Fire Purge Check (Terminal D) Low Fire Start (Terminal 3 - impedance) Pilot Test Mode Power Off 10 to 11 AUTO Power On, Limits Open 10 to 12 LOW Purge to High Fire 10 to 13 HIGH Purge to Low Fire 10 to 12 LOW Automatic Modulation 10 to 11 AUTO Alarm and Lockout 10 to 12 LOW For NO-PURGE and PURGE sequence models: The VeriFlame can be interlocked with the main valve closed position switch. This feature checks the switch position before start-up and after shutdown to insure proper valve operation when the jumper on the base is cut. For MODULATION sequence models: This feature is enabled when the jumper on the base is cut. The system checks that the high fire purge position switch and the main valve closed switch are both made at the end of the high fire purge. For MODULATION sequence models: When wired, the system checks for the low fire start position prior to light-off. In the pilot test mode, the VeriFlame will hold the sequence once the pilot flame is established and prevents energizing the main valve (terminal 5). Depressing the TEST/RESET button on the front cover enters this mode. When in the pilot test mode, the green INTERLOCKS CLOSED light blinks. To exit the pilot test mode, simply push the TEST/RESET button again. 14 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

Interrupted or Intermittent Pilot Spark, Pilot Flame & Main Flame Separation Post Purge An interrupted pilot shuts off at the time specified by the part number after the main valve is energized. An intermittent pilot (specified as 00 time) continues during the entire main flame firing cycle. During the trial for ignition period (TFI), the pilot and ignition outputs remain energized. At the end of the TFI, the pilot output remains on and the ignition output is de-energized. After a five second delay to prove the pilot or start flame, the main gas valve is energized. For PURGE and MODULATION sequence models: Post purge maintains the combustion air fan output for the time specified after the interlocks and limit switch input have opened. OPTIONAL FEATURES Recycle Mode Air Switch Input Hold Manual Reset on Power Outage Remote Display The following functions are optional features that must be specified when ordering. With R specified, the VeriFlame will restart the sequence after flame or air failure. The recycle mode allows the system to re-initiate the start-up sequence automatically only if the main burner has been operating for at least 35 seconds. If the pilot or start flame fails to light during recycling, the system will alarm and lockout. If the recycle is successful and the main burner is once again operational for at least 35 seconds, the system is enabled for another recycle. At no time will the system recycle in the event of a pilot or starting flame failure. For PURGE and MODULATION sequence models: With H specified, the VeriFlame holds the sequence indefinitely until the air switch input is made. Once made, normal functional sequence continues. With B specified, the TEST/RESET button must be pressed twice (in and out) to start the sequence. The system error light blinks rapidly (about 4 times per second) and a remote display will show PUSH RESET TO START. Two models of remote display are available. The model 5602DB operates on 24VDC and has no keypad. The model 5602DBP operates on 120VAC and has a keypad for reset function. The display is mounted through the panel-door and features a liquid crystal display in a ¼ DIN housing. The unit connects to the VeriFlame by a cable to the flame signal test jack, and receives a serial communication on each sequence state change. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 15

The display incorporates the following functions: 1) Provides status messages for the Veri-Flame sequence, see Section 8 Remote Display Messages on page 38. 2) Indicates lockout conditions when they occur, as well as the amount of time into the sequence when the lockout occurred. 3) Provides continuous monitoring of the burner s flame signal strength and run time during main burner operation. SYSTEM ERRORS AND LOCKOUT CONDITIONS A system error (illuminated by the red System Error LED on the front cover) prevents gas ignition. The unit will continue its sequence after the error is cleared. A lockout condition energizes the alarm output and deenergizes the gas valve and ignition outputs. The unit must be reset to clear the alarm and start the sequence. To reset, the button must be pressed twice so that the button is in the out position. The following system errors result in immediate lockout conditions: 1) Wiring error that puts external voltage on the output terminals. 2) Welded internal contacts or other malfunctions in the VeriFlame. 3) Main fuel valve closed position switch is open after cycle shutdown or before start-up. The system error light blinks twice and then remains on. The fan output terminal 8 will energize. 4) Low fire fail (for modulation model) the low fire switch is open prior to trial for ignition. 5) High fire fail (for modulating model) the high fire switch is not closed at the end of high fire purge. The following situations will result in a lockout condition: 6) Air failure (for purge and modulation models) loss of combustion air anytime during the operational cycle. The Air Failure LED will be on for this condition. (See Recycle Mode ). 7) Pilot flame fail loss of flame during the trial for pilot ignition period. The Flame Failure LED will be on for this condition. 16 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

8) Main flame fail loss of flame during the main burner trial for ignition or run period (recycling not selected). The Flame Failure LED will be on for this condition. System Errors and Lockout Conditions (Continued) The following result in lockout conditions after 30 seconds, the system error light blinks about 14 times and then remains on: 9) If a flame is detected out of sequence, which may be caused by: a) a faulty scanner; b) electrical interference on the sensor wiring; c) a flame exists in the burner or in the line of sight of a scanner, due to a gas leak, product fire or other condition. 10) Air flow switch closed before start-up (for purge and modulation models). STATUS LIGHTS & PUSH-BUTTON Interlocks Closed Air Failure System Error Flame Failure All of the status lights and the TEST/RESET push-button are located on the front cover of the Veri-Flame. This section describes their respective functions. This green LED illuminates when the operation limits are made. The limits are wired in series to terminal 7. This input becomes energized to begin the burner sequence. When in the test mode, this LED blinks (see Pilot Test Mode ). For purge and modulation models: this red LED illuminates whenever combustion air is lost during the operational cycle of the Veri-Flame. This red LED illuminates when a system error is detected (see System Errors & Lockout Conditions ). This red LED illuminates when a pilot or main flame fails. Low Fire High Fire For modulation models: this yellow LED illuminates during the low fire period of the purge cycle. For modulation models: this red LED illuminates during the high fire period of the purge cycle. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 17

Auto Test/Reset Flame Signal For modulation models: this green LED illuminates during the automatic period which occurs 20 seconds after the main valve is energized. This push-button is used to activate the pilot test mode or to reset the Veri-Flame unit. This red LED is located behind the signal test port and illuminates when a flame signal is present. FIGURE 3 1 TYPICAL SEQUENCE FOR NO-PURGE MODELS 18 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 3 2 TYPICAL SEQUENCE FOR PURGE MODELS FIGURE 3 3 TYPICAL SEQUENCE FOR MODULATION MODELS Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 19

System Installation 4 INTRODUCTION In this section, the necessary procedures are detailed to integrate a VeriFlame into a burner system. Specific wiring directions are given for the various functions described in the previous section. Note: Shut off the power supply before the VeriFlame is removed or replaced from the base. Caution: Installation and maintenance must conform with the national and local codes and authorities having jurisdiction. Only qualified technicians with knowledge or training of combustion equipment and safety systems must install and commission flame monitoring systems. Interlocks and Limit Switch Input (Terminal 7) Wire external interlock, control, and limit switches in series to this input. Guard against induced voltage levels to wiring connected to this input. In some extreme wiring runs, reduction of induced voltages may require a load (relay or light) connected to terminal 7 to avoid system error lockouts. This input is the power source for the valve and ignition output terminals. Be sure all switches wired to this input can handle the current required by the total of all loads connected to terminals 3, 4,and 5. Combustion Air Switch Input (Terminal 6) For purge and modulation models: Wire any switches and contacts in series to this terminal for proving airflow function and relating to the air failure light. Power must not be immediately present at terminal 6 when power is first applied to terminals 1 or 7. If the combustion air blower is controlled outside of the VeriFlame system, then a three-way solenoid valve must be connected between the air switch port and the blower sensing port. The valve de-energized state should vent the switch to ambient pressure. The energized state then connects the air switch to the blower 20 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

sensing port. Power the valve from the blower output terminal 8. An alternate method if accepted by local codes: the air switch could be wired between the combustion blower output and the air switch input. Connecting the air switch in this manner will satisfy the open contact (air short) check during startup. If this terminal is not used and the air switch requirement is satisfied by an alternate method accepted by the authority having jurisdiction, then place a jumper between the combustion blower output (terminal 8) and the air switch input (terminal 6) to satisfy the controller function. Ignition Wiring (Terminal 4) The output terminal normally powers a high voltage transformer. Route the high voltage ignition wiring a sufficient distance from all sensors and other low voltage wiring to avoid electrical interference, which may cause erratic operation of the VeriFlame system. Keep the high voltage wire as short as possible. The best condition is to mount the ignition transformer close to the burner and keep a low impedance path from the burner ground to the ground of the transformer. Make sure the high voltage lead and ground return paths do not create a loop antenna around the VeriFlame and sensor wiring. Low Fire Start Switch (Terminal 3 resistance through valve coil) Main Valve Closed Switch Input (Terminal V or D) For modulation sequence models: It is possible to wire the system for checking low fire start position prior to pilot ignition. To use this feature, the low fire start switch must be connected between terminal 3 and the pilot valve. On direct spark burners, a by-pass contact must be wired around the low fire switch. The system can be wired to check for the main valve closed switch on the main gas valve prior to start-up and after the end of the burner cycle. For purge and no purge models: The main valve closed switch must be connected to Terminal V and the jumper in the base must be cut. For modulation models: The main valve closed switch must be wired in series between the airflow switch and the high purge damper switch. To use this feature, the jumper in the base must be cut. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 21

High Purge Switch Input (Terminal D) For modulation models: the system can be wired to check for high purge position for the high fire purge portion of the sequence. To use this feature, the red jumper in the base must be cut and the high purge position switch must be connected from terminal 6 to D. If this feature is not used, the jumper in the base remains intact or a jumper must be installed between terminals 1 and D. (The yellow jumper on the base has no effect whether cut or intact.) Remote Reset (Terminal 1) This feature permits remote mounting of a switch to reset the VeriFlame. To use this feature, a normally closed remote reset switch must be wired so that power is interrupted to terminal 1. When it is pressed or actuated, the connection to terminal 1 is momentarily interrupted and resets the VeriFlame. Remote Display Identify the model of remote display (see page 12) and wire according to Figure 4 9 or Figure 4 10. Mount through a ¼ DIN cutout using the two supplied brackets in either the top and bottom or the side slots. Locate the display and wiring to minimize electrical interference. Applying and disconnecting the display power supply should coincide with power to terminal 1 of the VeriFlame. Use the appropriate cable (Eclipse part #20318) to connect to the test jack and to the S2 terminal of the VeriFlame wiring base. Do not attempt to parallel the test jack signal to other devices when using a remote display. The LCD display contrast can be adjusted on the back with a small blade screwdriver. Note: 1. Control circuit wires must meet 90 C (194 F) specification minimum and must be 1.5mm 2 (No. 16 AWG) or larger and in accordance with all applicable codes. 2. Flame sensor wires must be individually run in their own separate conduit; multiple unshielded flame sensor wires CANNOT be run together in a common conduit or wire way (See Sensor Installation Section). 3. The neutral wire to terminal 2 must be at ground potential (bonded at the supply source). Ground, shielding, and conduit must not be connected to terminal S2, which is internally referenced to terminal 2. Warning: Install a modulation sequence model into the modulation style base only; never plug into purge or no-purge bases. 22 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 4 1 WIRING FOR NO- PURGE MODELS FIGURE 4 2 WIRING FOR PURGE MODELS Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 23

FIGURE 4 3 WIRING FOR DIRECT SPARK OF MAIN FLAME, NO- &PURGE MODELS Unit must be intermittent pilot, not interrupted. FIGURE 4 4 WIRING FOR MODULATION MODELS See the Function Summary Section for the sequence of these Internal Contacts. FIGURE 4 5 WIRING FOR DIRECT SPARK OF MAIN FLAME, MODULATION MODELS Unit must be intermittent pilot, not interrupted. CR is a control relay used to bypass the low fire switch after the burner is lit. 24 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 4 6 WIRING FOR MODELS 5600-90, -91, -91N4 UV SCANNERS Scanner FIGURE 4 7 WIRING FOR FLAME ROD FIGURE 4 8 WIRING FOR MODELS 5602-91 SELF-CHECK UV SCANNER 5602-91-7 cable 4-pin connector FIGURE 4 9 WIRING FOR MODEL 5602DB, 24VDC REMOTE DISPLAY FIGURE 4 10 WIRING FOR MODEL 5602DBP, 120VAC REMOTE DISPLAY Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 25

FIGURE 4 11 BASE LAYOUT FOR NO-PURGE AND PURGE MODELS FIGURE 4 12 BASE LAYOUT FOR MODULATION MODELS 26 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

Sensor Installation 5 INTRODUCTION This section describes the proper wiring, installation and sighting considerations for the sensors used with a VeriFlame. Warning: Incorrect sensor installation may cause the sensor to generate a false flame signal, possibly resulting in the collection of unburned fuel in the combustion chamber. This unburned fuel creates the potential for explosions which can result in injuries, death, and property damage. Be certain that the flame sensor detects acceptable pilot and main flames only. SENSOR WIRING Route sensor wiring a sufficient distance from ignition and other high voltage or high current wiring to avoid electrical interference. Interference from ground currents, nearby conductors, radio-frequency emitters (wireless devices), and inverter drives (VFD) can induce false flame signals. Shielded cables can help reduce interference with the shield connected to ground at the control end only. Please note that a grounded shield may also decrease the signal due to the cable s internal capacitance. Cable capacitance (picofarads or microfarads) is determined by the wire type and construction. Multiple U.V. tube-type sensor-leads run together without shielding may interfere or cross talk, so the shield or flexible armor must be grounded to prevent this situation. For flame rod sensor runs approximately 30 meters (100 feet) or greater, use Eclipse part number 21741 coax cable. To achieve the maximum wiring distance, the shield should not be grounded (keep in mind that an ungrounded shield provides less protection against electrical interference). Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 27

Note: Unshielded sensor wiring must not be run in common with other wires; it must be run in separate conduit. Use 1mm 2 to 2mm 2 (#14 to #18 AWG) wire suitable for 90 C (194 F) and 600 volt insulation. Multiple unshielded flame sensor wiring must not be run together in a common conduit or wire way. Multiple shielded flame sensor cables can be run in a common conduit. FLAME RODS Flame rods should be used only on gas burners. They accumulate soot on oil burners, causing nuisance shutdowns and unsafe operating conditions. See the burner manufacturer s literature for flame rod mounting location. When installing flame rods, please consider the following: 1) Keep the flame rod as short as possible for reliable detection and at least 13 mm (1/2") away from any refractory. 2) Position the rod into the intersection of both the pilot and main flames, preferably at a descending angle to minimize drooping of the flame rod against burner parts. The flame rod position must detect only a pilot flame that is adequate to light the main flame for all normal burner draft conditions. Extend the rod 13 mm (1/2") into non-luminous flames, such as blue flames from premix and nozzle-mix air/gas burners. For partially luminous flames, such as atmospheric air/gas mixtures, place the rod at the edge of the flame. FIGURE 5 1 FLAME ROD POSITION 3) Provide a burner flame grounding area that is at least four times greater than the flame rod area contacting the flame. The flame rod to burner ground ratio and position of the rod in the flame may need adjustment to yield maximum flame signal strength. 4) Ignition interference from the spark plug may increase or decrease the flame signal strength. Reversing the ignition transformer primary leads may reduce this effect. Changing the spark gap or adding grounding 28 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

area between the flame rod and spark plug may eliminate the interference. SCANNERS Warning: Use only Eclipse scanner models as listed for operation with the VeriFlame. When installing scanners, please consider the following: 1) Position the scanner within 450 mm (18") of the flame. Consult factory for longer distances. 2) Bushing threads are ½-inch F.N.P.T. for all scanner models except 5602-91, which has 1-inch F.N.P.T. bushing threads. 3) The ambient temperature limits of each scanner vary; check the literature for the specific scanner model. For higher temperatures, use Eclipse heat block seal 23HBS for ½ N.P.T. scanners and if necessary, add cooling purge air. 4) An optional magnifying lens may also be used to increase the flame signal strength and narrow the field of view in difficult sighting situations. FIGURE 5 2 SCANNER SIGHTING 5) Aim scanners at the third of the flame closest to the burner nozzle (oil flames typically have less UV radiation in the outer flame). The scanner should view the intersection of the pilot and main flames. 6) Sight the scanner away from the ignition spark. If necessary, use a scanner orifice to reduce spark pickup. 7) Do not allow the scanner to detect a pilot flame that is too small to ignite the main burner. 8) Perform a minimum pilot test when installing or adjusting any pilot or main burner system; see Minimum Pilot Test on page 30. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 29

Test Procedures INTRODUCTION FLAME SIGNAL STRENGTH MINIMUM PILOT TEST This section describes the test procedures that must be performed after installation to insure that the VeriFlame is operating properly; these procedures are mandatory. Insert the positive probe of a 0-15 VDC, digital voltmeter into the test point on the front cover of the VeriFlame; connect the negative probe to S2 or alternately to ground. Good flame signal strength will read between 6 and 11 VDC; anything below 4 VDC is inadequate. Also, the red LED inside the test point illuminates when a flame signal is indicated. Run the following test procedures to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame: 1) Manually shut off the fuel supply to the main burner, but not to the pilot. 2) Start the system normally. 3) To enter the pilot test mode, depress the test/reset button located in the lower right corner on the front cover, see Pilot Test Mode on page 14. 4) The control will hold the operating sequence at the pilot flame step. Measure the flame signal strength. 5) Reduce the pilot flame until the flame signal drops towards 4VDC. Increase pilot flame until the flame signal is steady and greater than 4 VDC. This is the minimum pilot. If you don t think this flame will be able to safely light the main burner then realign the sensor so that it requires a larger pilot flame and repeat these steps. 6) Push the test/reset button so that it is in the out position to exit the test mode (reset) and begin the normal startup sequence again. 7) When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the burner. If the main burner does not light within five seconds, immediately shut off the burner supply to shut down the system. Realign the sensor so that it requires a larger 6 30 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

pilot flame. Repeat steps 1 through 6 until the main burner lights off smoothly and reliably. PILOT FLAME FAILURE TEST MAIN FLAME FAILURE TEST SPARK SIGHTING TEST LIMITS AND INTERLOCKS TEST 1) Manually shut off the fuel supply to the pilot and the main burner. 2) Press the test/reset button in for the Pilot Test Mode, see page 14. 3) Start the system normally. The controller should go to a lockout condition. If it doesn t, then the controller is detecting a false flame signal, see Section 5. Find the problem and correct it before resuming normal operation. This test is for a VeriFlame specified with interrupted pilot. 1) Manually shut off the fuel supply to the main burner but not to the pilot. 2) Start the system normally. The pilot should ignite and then after pilot interruption, the controller should go to a lockout condition. If not, the controller is detecting a false flame signal, see Section 5. Find the problem and correct it before resuming normal operation. 1) Manually shut off the fuel supply to the pilot and the main burner. 2) Start the system normally. 3) Measure the flame signal as described in Flame Signal Strength in this section. 4) If a flame signal greater than 4 VDC is measured for more than three seconds during the trial for ignition, then the sensor is picking up a signal from the spark plug; see Sensor Wiring on page 27. Periodically check all interlock and limit switches by manually tripping them during burner operation to make sure they cause the system to shut down. Warning: Never operate a system that is improperly adjusted or has faulty interlocks or limit switches. Always replace faulty equipment with new equipment before resuming operation. Operating a system with defective safety equipment can cause explosions, injuries, and property damage. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 31

Maintenance and Troubleshooting INTRODUCTION MAINTENANCE This section is divided into two parts. The first part describes the maintenance procedures. The second part describes troubleshooting procedures and includes identifying problems and interpreting the operating conditions by the lit LEDs on the front cover. Preventative maintenance is the key to a reliable, safe and efficient system. The core of any preventive maintenance program is a list of periodic tasks. In the paragraphs that follow are suggestions for a monthly list and a yearly list. 7 Note: The monthly list and the yearly list are an average interval. If your environment is harsh or dirty, then the intervals may need to be shorter. Caution: Turn off power before disconnecting or installing sensors, wiring bases, displays, or control units. Warning: Individuals working on this equipment should be trained in the design, operation, and maintenance of the complete system. They should recognize when a system is operating outside of its design parameters and be able to safely shut down the system. 32 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

MONTHLY CHECK LIST YEARLY CHECK LIST 1) Inspect flame-sensing devices for good condition and cleanliness. Keep scanner lenses clean with a soft, damp cloth, since small amounts of dust will measurably reduce the flame signal strength. Wash the flame rod electrode and insulator with soap and water, then rinse and dry thoroughly. 2) Test all the alarm systems for proper signals. 3) Check ignition spark electrodes and check proper gap. 4) Test interlock sequence of all safety equipment as described in Test Procedures on page 30: manually make each interlock fail, noting what related equipment closes or stops as specified by the manufacturer. 5) Test flame sensor lockout operation by manually shutting off the gas to the burner. 1) Test (leak test) safety shut-off valves for tightness of closure. 2) Check valve piping for leaks. 3) Test pressure switch settings by checking switch movements against the pressure setting and comparing with actual impulse pressure. 4) Visually check ignition cable and connectors. 5) Make sure that the following components are not damaged or distorted: a. burner nozzle b. spark plug c. flame sensor d. flame tube or combustion block of the burner Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 33

TROUBLESHOOTING PROBLEM POSSIBLE CAUSE REMEDY Cannot initiate start sequence Cannot complete purge sequence No power to control unit. Unit is in lockout condition. High or low gas pressure switches are open; INTERLOCKS CLOSED light is off. No power to terminal 7; INTERLOCKS CLOSED light is off. INTERLOCKS CLOSED light is off; power is present at terminal 7. Improper field wiring Air pressure switch is open or shorted. Improper field wiring Check for incoming power to terminals 1-2. Push the reset button twice, first in and then to out position. Measure gas pressure; if out of range correct cause (regulator, filter, obstruction). Check for damaged or incorrectly adjusted switch. Check wiring to terminal 7. Check all series connected switches feeding 7. Replace with new control unit. Replace wiring base. Check for interference and induced flame signals, look for flame on light in the test jack and for SYSTEM ERROR light. Check grounding system. Install surge suppressors, separate wiring by voltages and follow guidelines for sensor wiring in Section 5. Measure air pressure; if out of range then correct cause (filter, blower rotation, obstruction). Check for damaged or incorrectly adjusted switch. Check wiring to terminal 6; voltage to 6 must not make before output on terminal 8. See improper field wiring above 34 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

PROBLEM POSSIBLE CAUSE REMEDY Cannot initiate full trial for ignition Cannot establish pilot flame Main Valve never opens Does not lockout with a main valve switch open test Will not recycle Flame Signal Voltage reading greater than 12VDC Low fire, high fire, or main valve closed switches are not making. Ignition circuit interference FLAME FAILURE Unit in pilot test mode. FLAME FAILURE Jumper in wiring base is not cut. Improper model Main flame was not established for 35 seconds. Improper grounding Check for improperly adjusted or defective position switches and loose wiring. Separate and isolate high voltage spark wire. Swap ignition transformer primary lead polarity. Install surge suppressors, separate wiring by voltages and follow guidelines for sensor wiring in Section 5. Relocate ignition transformer; change the ground return path. Correct reversed sensor wiring or replace defective flame sensor. Adjust burner settings. Repair defective ignition circuit. Press the reset button to the out position. See FLAME FAILURE above. Check wiring for direct ignition burners (no pilot). Cut the 1 to V or the 8 to D jumper in the base. Check part number. See FLAME FAILURE above. Check grounding of neutral at control power transformer. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 35

LED STATUS LED(S) ON INTERLOCKS CLOSED SYSTEM ERROR FLAME FAILURE AIR FAILURE AUTO HIGH FIRE LOW FIRE This section describes the status of operating conditions based on the LED or combination of LEDs that are lit on the front cover of the VeriFlame. Some of the listed causes may apply only to a specific model sequence: No-Purge, Purge, or Modulation. POSSIBLE CAUSES The interlocks, limits, and contacts wired to terminal 7 are closed to allow operating the burner. 1) The flame signal light is on - flame detected is out of sequence; the scanner is defective; inductance is detected on sensor wires. 2) Voltage is back-wired into output terminals 3, 4 or 5. 3) Internal relay contacts are welded or other internal controller failure. 4) Airflow switch is closed before start-up. 5) Main fuel valve switch opens after shutdown or before start-up; no power to terminal V. 6) High purge damper switch and/or main fuel valve switch opens during start-up; no power to terminal D. 7) Low fire switch not made before TFI. 1) Pilot flame is not established within the trial for ignition period (TFI). 2) Main flame is not established within the TFI. 3) Flame failed during operation in non-recycle mode, or the main flame fails within 35 seconds of TFI. 4) Flame failed 35 seconds after TFI and was not established during the subsequent TFI in recycle mode. 1) Airflow switch not closed within ten seconds of start-up. 2) Airflow switch opens during timing cycle. 3) Airflow switch opens during firing cycle. Burner in run mode, firing rate determined by automatic controller. Purge high sequence. Purge low sequence or interlocks open. 36 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 7 1 NOPURGE MODEL FIGURE 7 2 PURGE MODEL FIGURE 7 3 MODULATION MODEL Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 37

Remote Display Messages INTRODUCTION ELAPSED TIME INDICATOR FLAME SIGNAL STRENGTH READOUT KEYPAD OPERATION REMOTE RESET This section covers how the optional remote display shows messages that relate to the sequences of the Veri-Flame. The remote display provides LCD messages which monitor the status of the VeriFlame s functions as well as any lockout conditions, see Remote Display on page 15. See Figure 4 9 and Figure 4 10 on page 25 for wiring information. This section is divided into two parts: The first part describes the start-up and shutdown monitoring sequences of the Veri-Flame and how the progress (or halting) of the sequence can be monitored by the messages on the remote display. The second part alphabetically lists and explains the diagnostic messages which can appear on the remote display. The remote display provides running time while the burner is firing. This time is zeroed from the start of the interlocks input. When in a lockout condition, the display alternately shows the current elapsed time and the time when the lockout took place. The remote display shows the flame signal strength during the pilot trial for ignition and during the main firing cycle. It is displayed as a voltage reading from 0 to about 12V, corresponding to the output voltage from the test jack. Currently only the RESET button of the model 5602-DBP display functions at this time. Pressing this button opens the internal normally closed contact on terminals R1 and R2, see Figure 4 10 on page 25, and also resets the internal microprocessor. 8 38 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 8 1 STARTUP Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 39

FIGURE 8 2 PURGE, TFI, AND MAIN 40 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

FIGURE 8 3 MAIN FIRING Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 41

FIGURE 8 4 SHUTDOWN 42 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

REMOTE DISPLAY MESSAGE LISTING EXPLANATION AIR FAILURE XX:XX:XX LOCKOUT AIR FAILURE RECYCLING AIR NOT PROVEN XX:XX:XX LOCKOUT AIR PROVEN AUTOMATIC MODULATION BURNER ON XX.XV TIME=XXXX:XX:XX CLOCK FAIL XX:XX:XX LOCKOUT FAN ENERGIZED FLAME FAILURE XX:XX:XX LOCKOUT HI DAMPER FAIL XX:XX:XX LOCKOUT INTERNAL FAULT XX:XX:XX LOCKOUT K-INTERNAL FAULT XX:XX:XX LOCKOUT LIMITS OPEN TIME=XXXX:XX:XX L-INTERNAL FAULT XX:XX:XX LOCKOUT LKOUT= XX:XX:XX LOW FIRE FAIL XX:XX:XX LOCKOUT MAIN FLAME FAIL XX:XX:XX LOCKOUT The airflow switch input has opened for two or more seconds after the initial proving period, resulting in a lockout. The airflow switch input has opened after running over 35 seconds in main flame. The burner has shut down and the unit is recycling to the start-up sequence. The airflow switch input to terminal 6 has not made within ten seconds of the fan output on terminal 8, resulting in lockout. The airflow switch to terminal 6 has made. The unit no longer controls the damper or modulating motor and enables automatic control by an external controller. The main flame is on and the flame signal is displayed along with the elapsed time in hours:minutes:seconds. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Unit has energized terminal 8 just before the purge delay. The flame signal was lost resulting in a lockout condition. The high purge position switch or main valve closed switch input to terminal D was not made during the high purge sequence resulting in a lockout condition. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. The control has completed its internal safe start check and is standing by for the interlocks to close. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Unit is in a lockout condition, shown with the time of lockout. The low fire switch was not made before trial for ignition, resulting in a lockout condition. The main flame signal was lost during the main flame proving period. MAIN FLAME FAIL The main flame signal was lost after the required 35 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 43

RECYCLING MAIN ON MAIN ON PILOT OFF MAIN VALVE FAIL XX:XX:XX LOCKOUT MISSING HZ XX:XX:XX LOCKOUT PILOT TEST POST PURGE PURGE IN PROGRESS PURGE TO HIGH FIRE PURGE TO LOW FIRE PUSH RESET TO START RAM FAIL LOCKOUT XX:XX:XX RELAY FAIL XX:XX:XX LOCKOUT ROM FAIL XX:XX:XX LOCKOUT SAFE START OK v2.0 CS= S-FAILURE-COMMS XX:XX:XX LOCKOUT S-FAILURE-HDWARE S-FAILURE-IGNIT XX:XX:XX LOCKOUT S-FAILURE-MAIN XX:XX:XX LOCKOUT S-FAILURE-PILOT XX:XX:XX LOCKOUT seconds, and will recycle back to the start-up sequence. The main output has energized and the flame proven. The pilot output has de-energized (interrupted) and the main output is on. The main valve closed switch was open before start-up or after shut-down. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Control is in the Pilot Test Mode. The fan output remains energized after burner shutdown for this timed sequence. The fan output is energized and the purge sequence is timing. The modulation model s first purge sequence has started to drive the damper to the high position for full airflow. The modulation s second purge sequence has started to drive the damper to the low position before trial for ignition. Unit has the manual start option that requires pushing the test/reset button in/out to start after a power interruption. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Control has performed and passed internal safe start check. The version and software check-sum are displayed. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. 44 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

S-FAILURE-PURGE XX:XX:XX LOCKOUT TEST TFI FLAME FAIL XX:XX:XX LOCKOUT TIME= TRIAL FOR IGNITION UNSAFE AIR SHORT UNSAFE AIR SHORT XX:XX:XX LOCKOUT UNSAFE FLAME ON UNSAFE FLAME ON XX:XX:XX LOCKOUT Internal component may have failed; remove power and retry. If message repeats, then replace controller. Control is in the Pilot Test Mode. Flame was not detected by the end of the trial for ignition, resulting in a lockout condition. Shows the elapsed time since interlocks have completed. Control is starting the trial for ignition sequence. The combustion air switch input is made before the fan output on start-up or after the fan output turns off on shutdown. If the switch opens within 30 seconds the control restores normal operation. The unit will go to a lockout condition if the condition lasts over 30 seconds. The above inappropriate combustion air switch input did not open within 30 seconds, resulting in a lockout condition. Unit has detected an inappropriate flame signal (actual, induced, or faulty scanner) before start-up or after shutdown. The fan output will energize and will go to a lockout condition if the condition lasts over 30 seconds. If the cause is corrected within 30 seconds, the control turns off the fan and restores normal operation. An inappropriate flame signal lasted longer than 30 seconds, resulting in a lockout condition. UNSAFE-FLM-PURGE Unit has detected an inappropriate flame signal (actual, induced, or faulty scanner) during the purge sequence. If the cause is corrected within 30 seconds, the unit will continue sequence; otherwise it will go to a lockout condition. VALVE ON IGNITION OFF VALVE ON IGNITION ON VERIFLAME 2.0 REVISION # V-INTERNAL FAULT XX:XX:XX LOCKOUT WATCHDOG FAIL XX:XX:XX LOCKOUT Control has completed trial for ignition time and is currently in the flame proving sequence. Control is in the trial for ignition sequence. Normal display of the version and revision screen. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Internal component may have failed; remove power and retry. If message repeats, then replace controller. Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 45

Appendix PRODUCT MODEL NUMBER GUIDE Make one selection each from Tables I through VIII Model I II III IV V VI VII VIII VF56 9 TABLE DESCRIPTION SELECTION TABLE I POWER SUPPLY TABLE II SEQUENCE TABLE III FLAME FAIL RESPONSE TABLE IV PURGE TIME TABLE V IGNITION TRIAL TABLE VI PILOT TIME TABLE VII POST-PURGE TABLE VIII RECYCLE AIR SWITCH RESET 102-132VAC, 50/60Hz 204-264VAC, 50/60Hz No-Purge * Purge Modulation ** UV Scanner with 1 second FFRT Flame-rod with 1 second FFRT UV Scanner with 3 second FFRT Flame-rod with 3 second FFRT Enter TIME in seconds, 0 999 * For No-Purge Sequence selection N, enter 00; ** For Modulation Sequence M, the time is applied to both the high and low cycles, effectively doubling the specified time. Enter TIME in seconds, 1 15 Enter INTERRUPTED TIME in seconds, 0 99 To specify INTERMITTENT pilot, enter 00. Enter TIME in seconds, 0 99 For no post-purge, enter 00. Standard no Recycle Recycle Standard, alarm if switch not made in 10s. Sequence hold until switch makes Standard automatic reset on power up Manual push button to start on power up 1 2 N P M 1 U 1 F 3 U 3 F _ 0 R _ 0 _ H 0 B 46 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02

ILLUSTRATED PARTS LIST CATEGORY FIG DESCRIPTION MODEL NUMBER PART NUMBER Sensors 1 Straight UV Scanner 5600-91 49600-91 2 90 Degree UV Scanner 5600-90A 49600-90 4 Self-Check UV Scanner 5602-91 49602-91 - 10-foot Cable for Self-Check UV Scanner 5602-91-7 49602-91-7 5 Sealed Straight UV Scanner 5600-91N4 20898 6 Scanner Support Lens Assembly, used with 5600-90A and 5600-91N4 5600-90A-SSH 20722 7 Magnifying Lens Assembly 5600-98 49600-98 - Lens, Magnifying, used with 5600-98 and 5602-91 49600-99 49600-99 - Lens, Non-magnifying 18165 18165 8 Insulated Coupling 5600-99 49099 - Cable, coax, RG62A/U for flame rod 21741 21741 Bases 9 Internal Terminal Base, Metal 5602-10 49602-10 9 Internal Terminal Base, Plastic 5602-10 P 22194 10 External Terminal Base, Metal 5602-10-1 49602-10-1 11 Modulation Base, Metal 5602-40 49602-40 - Screw, Mount Control Unit to Plastic Base - Screw, Mount Control Unit to Metal Base 22110 22110 22385 22385 Tester - Tester for VeriFlame 5602 49602 - Relay Module, plugs into above tester for use with modulation models 5602-40-4 49240-2 Display 12 Remote Display, 24VDC 5602-DB 20316 - Remote Display, 120VAC with Keypad - Power Supply, 24VDC, used with 5602-DB 5602-DBP 20896 20317 20317 - Cable for Remote Display 20318 20318 Eclipse VeriFlame CE Instruction Manual 818-2, 09/02 47

Offered By: Power Equipment Company 2011 Williamsburg Road Richmond, Virginia 23231 Phone (804) 236-3800 Fax (804) 236-3882 www.peconet.com