INSTALLATION MANUAL. R-407C split series outdoor units R25GZ7V11 R35GZ7V11 R45GZ7V11 R45GZ7W11

Similar documents
INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL

INSTALLATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

BCF1080 FORWARD PLATE COMPACTORS PARTS BOOK

MULTI-MAX. A) Application - Operating with wheels Do not work without protection cover

CTC EcoMiniEl. Installation- and Maintenance Manual. External electric boiler. Providing sustainable energy solutions worldwide

IDEAL IDEAL Modular conveyor belt system. Operating Instructions

Operating Instructions for Liquid Level Transducer Model : MM Series

Operating instructions For Vibration level switch. Model NSV

Regulatory Compliance and Safety Information

INSTALLATION MANUAL. Split System air conditioners FCQ35C7VEB FCQ50C7VEB FCQ60C7VEB FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB

INSTALLATION AND OPERATION MANUAL

OPERATING INSTRUCTIONS

INSTALLATION MANUAL. Packaged water-cooled water chillers EWWP014KAW1N EWWP022KAW1N EWWP028KAW1N EWWP035KAW1N EWWP045KAW1N EWWP055KAW1N EWWP065KAW1N

CTC EcoZenith C 530 l 510

INSTALLATION MANUAL. Outdoor unit for air to water heat pump ERHQ006BAV3 ERHQ007BAV3 ERHQ008BAV3 ERLQ006BAV3 ERLQ007BAV3 ERLQ008BAV3

INSTALLATION AND OPERATION MANUAL

INSTALLATION MANUAL. System air conditioner BSV4Q100P7V1

INSTALLATION AND OPERATION MANUAL

Instruction Manual Captive Air Level Control. Model NLP

INSTALLATION AND OPERATION MANUAL

EC DECLARATION OF CONFORMITY

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL

OPERATING INSTRUCTIONS

INSTALLATION MANUAL R410A SPLIT SERIES MODELS FTXN25LV1B FTXN35LV1B RXN25LV1B RXN35LV1B RXN50LV1B RXN60LV1B FTXN50LV1B FTXN60LV1B.

INSTALLATION MANUAL. Unit for air to water heat pump system EKCBX008BBV3 EKCBH008BBV3

INSTALLATION MANUAL. Packaged water-cooled water chillers EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB2MUAW ECB3MUAW

INSTALLATION MANUAL. Condenserless water-cooled water chillers

INSTALLATION MANUAL. Packaged water-cooled water chillers EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N

The CE Marking Access to the European Market

USING AND MAINTENANCE MANUAL FOR SELF-CONTAINED POWER BRUSH MACHINE FOR CARPET AND HARD FLOOR. Elite-Silent. Elite-Silent

DECLARATION OF CONFORMITY KONFORMITÄTSERKLÄRUNG

INSTALLATION MANUAL. Unit for air to water heat pump system EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1

INSTALLATION MANUAL. System air conditioner. BS unit BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B

DECLARATION OF CONFORMITY

INSTALLATION MANUAL. Unit for air to water heat pump system EDHQ011BB6V3 EDHQ014BB6V3 EDHQ016BB6V3 EDHQ011BB6W1 EDHQ014BB6W1 EDHQ016BB6W1

INSTALLATION MANUAL. Split System air conditioners RZQS71D7V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B

ENGLISH INSTRUCTION MANUAL ONE

DECLARATION OF CONFORMITY

technical data air conditioning systems Indoor Units FBQ-C7VEB

INSTALLATION MANUAL. Split System air conditioners FBQ35C7VEB FBQ50C7VEB FBQ60C7VEB FBQ71C7VEB FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB

DAIKIN AIR CONDITIONER

INSTALLATION MANUAL. Split System air conditioners AZQS71B2V1B AZQS100A7V1B AZQS125A7V1B AZQS140A7V1B AZQS100A7W1B AZQS125A7W1B AZQS140A7W1B

SST FOR THE AIR CONDITIONING SYSTEM

INSTALLATION MANUAL. Split system air conditioner RZQ200B8W1B RZQ250B8W1B

Pizza Oven. Instruction manual. Model: CP868

INSTALLATION MANUAL. Split System air conditioners FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB

Air Conditioners. Technical Data FBQ-C

INSTALLATION AND OPERATION MANUAL

BCF2150 FORWARD PLATE COMPACTOR PARTS BOOK

Operating Instructions

INSTALLATION AND OPERATION MANUAL

INSTALLATION MANUAL. R410A Split Series. Models ARX20GV1B ARX25GV1B ARX35GV1B ARX20JV1B ARX25JV1B ARX35JV1B. Installation manual R410A Split series

INSTALLATION MANUAL. System air conditioner. BS unit BS1Q10A7V1B BS1Q16A7V1B BS1Q25A7V1B

MULTISTAGE ELECTRIC PUMPS

Slim Bottle Cooler. Instruction manual. Model: CS586

Waste heat exchanger - CHRP-S

BCF1570 FORWARD PLATE COMPACTORS PARTS BOOK

Induction Cooker Instruction Manual. Model Modèle Modell Modello Modelo Malli : CN203

Operating Manual Ionizer

Hamburger Machine Instruction manual

User Manual. WR10-CP-LED 10 W Art.-No.: WR20-CP-LED 20 W Art.-No.: WR30-CP-LED 30 W Art.-No.

Rev Installation Guide. Sondex Industrial and Marine Pumps

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

INSTALLATION MANUAL. Split System air conditioners RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B

8573 Nocchi Booklet 12 linguil :Pentair Water Italy Srl - Reb

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

VACOOK. Thermocirculator for Sous Vide cooking USE AND MAINTENANCE MANUAL

Installation- and Maintenance Manual CTC EcoAir 520M. Modulating air/water heat pump. Providing sustainable energy solutions worldwide

Service & Operating Manual

INSTALLATION AND OPERATION MANUAL

BIOSTORE HEATING ROLL IN CABINETS SCC 1010, SCC 2320, SCC 1120, SCC 2340 TECHNICAL MANUAL INCLUDING - USER MANUAL - INSTRUCTIONS

TABLE OF CONTENTS ERSQ-AAY1

Installation- and Maintenance Manual CTC EcoAir 500M. Modulating air/water heat pump. Providing sustainable energy solutions worldwide

SERVICE MANUAL FOR MODEL RM-49

INSTALLATION MANUAL. Packaged air-cooled water chillers EWAP110MBYNN EWAP140MBYNN EWAP160MBYNN EWAP200MBYNN EWAP280MBYNN EWAP340MBYNN

Installation Manual. KS Series KS09 KS12 KS18 KS24 KS28. J3387_Kaden_Installer_Manual_ indd 1

NC, NCD. Circolatori flangiati a tre velocità Three speeds circulation pumps with flanges ISTRUZIONI PER L USO OPERATING INSTRUCTIONS

Installation- and Maintenance Manual CTC EcoAir 510M. Modulating air/water heat pump 400V 3N~ Providing sustainable energy solutions worldwide

INSTALLATION MANUAL. Packaged water-cooled water chillers

IU-PSINV-HW12R IU-PSINV-HW16R IU-PSINV-HW18R IU-PSINV-HW25R

Split Air Conditioner

SERVICE MANUAL FOR MODEL RM-10

INSTALLATION MANUAL. R410A Split Series. Models 2MXS40BVMB 2MKS40BVMB 2AMXS40BVMB 2AMKS40BVMB. Installation manual R410A Split series

QBx Sub. Powered Subwoofer Owner s Manual

INSTALLATION MANUAL. Condenserless water-cooled water chillers

EEDEN technical data ERHQ AA. Altherma. Altherma

INSTALLATION MANUAL. System air conditioner RXQ5M9W1B RXQ8M9W1B RXQ10M9W1B RXYQ5M9W1B RXYQ8M9W1B RXYQ10M9W1B RXYQ12M9W1B RXYQ14M9W1B RXYQ16M9W1B

SERVICE MANUAL FOR MODEL RM-26

INSTALLATION MANUAL. Split System air conditioners RZQ71D3V1B RZQ100D9V1B RZQ125D9V1B RZQ140D9V1B RZQ100B9W1B RZQ125B9W1B RZQ140B9W1B

INVERTER SPLIT - TYPE

INSTALLATION MANUAL. Split System air conditioners RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B

INSTALLATION MANUAL. R410A Split Series. Models. Installation manual R410A Split series. Installationsanleitung Split-Baureihe R410A

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL. R410A Split Series. Models. Installation manual R410A Split series. Installationsanleitung Split-Baureihe R410A

Providing sustainable energy solutions worldwide. Installation- and maintenance instruction B 30 A

Inverter Air Conditioner Installation Manual GIN 090/GIN 091 GIN 120/GIN 121 GIN 180/GIN 181 GIN 240/GIN 241

GLASS WASHING MACHINE INSTRUCTION MANUAL

TECHNICAL DATA & SERVICE MANUAL

Transcription:

INSTALLATION MANUAL R-407C split series outdoor units R25GZ7V11 R35GZ7V11 R45GZ7V11 R45GZ7W11

CE - DECLARATION-OF-CONFORMITY CE - CONFORMITEITSVERKLARING CE - H ø H YMMOPºø H CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE CE - KONFORMITÄTSERKLÄRUNG CE - DECLARACION-DE-CONFORMIDAD CE - DECLARAÇÃO-DE-CONFORMIDADE CE - ERKLÆRING OM-SAMSVAR CE - DECLARATION-DE-CONFORMITE CE - DICHIARAZIONE-DI-CONFORMITA' CE - OPFYLDELSESERKLÆRING CE - ILMOITUS-YHDENMUKAISUUDESTA Daikin Europe N.V. declares under its sole responsibility that the air conditioning models to which this declaration relates: erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist: déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration: verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft: declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace referencia la declaración: dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione: ËÏÒÓÂÈ Ì appleôîïâèûùèî ÙË Â ı ÓË fiùè Ù ÌÔÓÙ Ï ÙˆÓ ÎÏÈÌ ÙÈÛÙÈÎÒÓ Û ÛΠÒÓ ÛÙ ÔappleÔ Ó Ê ÚÂÙ È Ë apple ÚÔ Û ÏˆÛË: declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere: erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører: deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att: erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon innebærer at: ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit: R25GZ7V11, R35GZ7V11, R45GZ7V11, R45GZ7W11 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions: der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß unseren Anweisungen eingesetzt werden: sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions: conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze instructies: están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras instrucciones: sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni: Â Ó È Û ÌÊˆÓ Ì ÙÔ( ) ÎfiÏÔ ıô( ) appleúfiù appleô( ) ÏÏÔ ÁÁÚ ÊÔ( ) Î ÓÔÓÈÛÌÒÓ, applefi ÙËÓ appleúô applefiıâûë fiùè ÚËÛÈÌÔappleÔÈÔ ÓÙ È Û ÌÊˆÓ Ì ÙÈ Ô ËÁ Â Ì : estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de acordo com as nossas instruções: overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser: respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att användning sker i överensstämmelse med våra instruktioner : respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i henhold til våre instrukser: vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti: EN60335-2-40, following the provisions of: gemäß den Vorschriften der: conformément aux stipulations des: overeenkomstig de bepalingen van: siguiendo las disposiciones de: secondo le prescrizioni per: Ì ٠ÚËÛË Ùˆv È Ù Íˆv Ùˆv: de acordo com o previsto em: under iagttagelse af bestemmelserne i: enligt villkoren i: gitt i henhold til bestemmelsene i: noudattaen määräyksiä: Low Voltage 73/23/EEC Machinery Safety 89/392/EEC Electromagnetic Compatibility 89/336/EEC * Directives, as amended. Direktiven, gemäß Änderung. Directives, telles que modifiées. Richtlijnen, zoals geamendeerd. Directivas, según lo enmendado. Direttive, come da modifica. ËÁÈÒv, fiappleˆ Ô Ó ÙÚÔappleÔappleÔÈËıÂ. Directivas, conforme alteração em. Direktiver, med senere ændringer. Direktiv, med företagna ändringar. Direktiver, med foretatte endringer. Direktiivejä, sellaisina kuin ne ovat muutettuina. * Note as set out in the Technical Construction File DAIKIN.TCF.001 and judged positively by KEMA according to the Certificate 58242-KRQ/ECM95-4224. Hinweis wie in der Technischen Konstruktionsakte DAIKIN.TCF.001 aufgeführt und von KEMA positiv ausgezeichnet gemäß Zertifikat 58242-KRQ/ECM95-4224. Remarque tel que stipulé dans le Fichier de Construction Technique DAIKIN.TCF.001 et jugé positivement par KEMA conformément au Certificat 58242-KRQ/ECM95-4224. Bemerk zoals vermeld in het Technisch Constructiedossier DAIKIN.TCF.001 en in orde bevonden door KEMA overeenkomstig Certificaat 58242-KRQ/ECM95-4224. Nota tal como se expone en el Archivo de Construcción Técnica DAIKIN.TCF.001 y juzgado positivamente por KEMA según el Certificado 58242-KRQ/ECM95-4224. Nota delineato nel File Tecnico di Costruzione DAIKIN.TCF.001 e giudicato positivamente da KEMA secondo il Certificato 58242-KRQ/ECM95-4224. ËÌ ˆÛË fiappleˆ appleúôû ÈÔÚ ÂÙ È ÛÙÔ Ú Â Ô Â ÓÈÎ Ù ÛΠDAIKIN.TCF.001 Î È ÎÚ ÓÂÙ È ıâùèî applefi ÙÔ KEMA Û ÌÊˆÓ Ì ÙÔ ÈÛÙÔappleÔÈËÙÈÎfi 58242-KRQ/ECM95-4224. Nota tal como estabelecido no Ficheiro Técnico de Construção DAIKIN.TCF.001 e com o parecer positivo de KEMA de acordo com o Certificado 58242-KRQ/ECM95-4224. Bemærk som anført i den Tekniske Konstruktionsfil DAIKIN.TCF.001 og positivt vurderet af KEMA i henhold til Certifikat 58242-KRQ/ECM95-4224. Information utrustningen är utförd i enlighet med den Tekniska Konstruktionsfilen DAIKIN.TCF.001 som positivt intygas av KEMA vilket också framgår av Certifikat 58242-KRQ/ECM95-4224. Merk som det fremkommer i den Tekniske Konstruksjonsfilen DAIKIN.TCF.001 og gjennom positiv bedømmelse av KEMA ifølge Sertifikat 58242-KRQ/ECM95-4224. Huom jotka on esitetty Teknisessä Asiakirjassa DAIKIN.TCF.001 ja jotka KEMA on hyväksynyt Sertifikaatin 58242-KRQ/ECM95-4224 mukaisesti.... Dany Chalmet Director Quality Assurance Ostend, 3rd of April 2000 Zandvoordestraat 300, B-8400 Oostende, Belgium 3PW09147-6A

5 ØA 6 ØB R25GZ7 Ø9.5mm or 3/8" Cut Ø6.4mm or 1/4" Cut R35GZ7 Ø12.7mm or 1/2" Cut Ø6.4mm or 1/4" Cut R45GZ7 Ø15.9mm or 5/8" Cut Ø6.4mm or 1/4" Cut 1 H 1000 A 250 H > 1000 A 500 2 3 R25GZ7 l 15m 17.5m 20.0m 22.5m 25m R35GZ7 R407C +0g +50g +100g +150g +200g R45GZ7 Hmax. 15m H 4 5 6 1 7 9 2 4 5 14 15 6 1 5 2 4 3 A C B A B C 6 12 8 10 3 11 13 7 8

9 (3TW01906-1) 10 (3TW01926-1) 11 (3TW01936-1)

R25GZ7V11 R35GZ7V11 R45GZ7V11 R45GZ7W11 R-407C split series outdoor units READ THIS MANUAL IN COMBINATION WITH THE INSTALLATION MANUAL OF THE CORRESPONDING INDOOR UNIT. IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL. IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION. 1. INSTALLING THE OUTDOOR UNIT 1.1. OUTLOOK DIAGRAM (see figure 1) 1) drain outlet 2) 4 x holes for anchor bolts (M8 or M10) 3) service cover + wiring diagram 4) power intake 5) low pressure gas stop valve ØA 6) liquid stop valve ØB 7) low pressure service port 8) nameplate 1.2. SELECTING THE LOCATION Be sure to install the outdoor unit where: - the foundation is solid enough to bear the weight and vibration of the unit. - the space around the unit is adequate for ventilation. (see figure 2) - the site is not near a concentration of flammable gas. - the site is not exposed to a salty atmosphere or sulphate gas. - the site is efficiently isolated so that the running noise and hot exhaust do not disturb the users or their neighbours. When operating the unit at low outdoor ambient temperature, be sure to follow the instructions described below. - To prevent exposure to wind, install the outdoor unit with its suction side facing the wall. - Never install the outdoor unit at a site where the suction side may be exposed directly to wind. - To prevent exposure to wind, it is recommended to install a baffle plate on the air discharge side of the outdoor unit. - In heavy snowfall areas, select an installation site where the snow will not affect operation of the unit. Since drain comes out of the outdoor unit, do not place anything around the outdoor unit that must be kept free from moisture. Do not install the unit in a place containing moisture. 1.3. INSTALLATION (see figure 3) 1) If drainage is bad, place concrete blocks as bases. 2) Leave sufficient space for piping and electric wiring, or at least enough space for unscrewing and removing the terminal cover. 2. REFRIGERANT PIPING 2.1. FIELD PIPING All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes. 2.2. PIPE CONNECTIONS Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as this would reduce the lifetime of the units. Never use piping which has been used for previous installations. Only use parts which are delivered with the unit. Do never install a drier to this R-407C unit in order to guarantee its lifetime. The drying material may dissolve and damage the system. Piping connections must be made from the right side of the unit. (Refer to figure 1 for the required piping diameters). 2.3. FIRST INSTALLATION (see figures 4~5) - If pipe length ( l ) between indoor and outdoor unit exceeds 15 meters, additional refrigerant R-407C (20g/m) must be charged after vacuum drying of the installation! - Maximum allowable level difference (Hmax) between indoor and outdoor unit is limited up to 15 meters. 3. VACUUM DRYING OF THE INSTALLATION 3.1. FIGURES Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refrigerant in the outdoor unit for air purging! 3.1.1. Gas stop valve (see figure 7) A) connection to fan coil (indoor) unit B) connection to accumulator / compressor C) connection to low pressure gauge manifold 1) blind cover 2) low pressure service port cover 3) low pressure service 4) check valve 5) valve shaft 6) flare nut 3.1.2. Vacuum pump connection drawing (see figure 8) A) air B) refrigerant - gas C) refrigerant - liquid test for leakage 1) fan coil (indoor) unit 2) condensing (outdoor) unit 3) accumulator 4) compressor 5) condenser 6) evaporator 7) gas line 8) liquid line 9) gas stop valve with low pressure service port 10) liquid stop valve 11) high pressure service port 12) flare joint 13) 2-stage vacuum pump 14) low pressure gauge 15) high pressure gauge 3.2. METHOD Installation manual Use a vacuum pump for R-407C exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit. Step 1: Gas stop valve and liquid stop valve remain closed. Step 2: Connect the low pressure service port to the low pressure gauge manifold and the vacuum pump as illustrated in figure 8. Notes: - Use a 2-stage vacuum pump with a built-in contra flow preventive adapter or attach a separate contra flow preventive adapter. - Use a clean gauge manifold and charging hose for R-407C exclusively. Step 3: Open the low pressure valve of the gauge manifold Step 4: Actuate the vacuum pump and make sure that the low pressure gauge indicates -0.1 MPa (-760 mmhg) Evacuation duration: Gas side piping size Piping length 15 m > 15 m ø 9.5 mm 10 minutes 15 minutes ø 12.7 mm 15 minutes 20 minutes ø 15.9 mm 20 minutes

Step 5: - Completely close the low pressure valve first. - Remove the vacuum pump from the gauge manifold, and then turn off the vacuum pump. - Leave the system as it is for 2 minutes and confirm that the low pressure gauge readout does not decrease. - If the needle moves back, ingress of water inside the system or leakage at the joints are considered. - Check every joint and then loosen the nut once and tighten it again firmly. After that, repeat step 2 to 5. Step 6: Remove the blind cover of the gas stop valve and liquid stop valve. Step 7: Open the gas stop valve for about 3 seconds with a hexagon wrench, then quickly close it firmly. Step 8: Check the connections marked with for leakage. - Apply soapsuds to the connections and inspect carefully. - After checking, wipe them off completely. Step 9: Disconnect the gauge manifold. Step 10: Open the liquid and gas stop valve completely. Step 11: Tighten up the blind cover of the liquid stop valve. Step 12: Tighten up the service port cover and the blind cover of the gas stop valve. 4. FIELD WIRING 4.1. FIELD WIRING - All field wiring and components must be provided by a licensed electrician and must comply with the relevant local and national codes. - Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. - Wire in accordance with the wiring diagrams (see figure 9~11) and outlook diagram (see figure 1). The required electrical power supply is stated on the unit's nameplate. Parts table:... protective earth C1R,C2R... running capacitor F1U... field fuse F2S,F3S... surge arrester F3C... overcurrent relay K1M... compressor contactor K2R... magnetic relay L... live M1C... compressor motor M2F... fan motor 4.2. FIELD CABLE AND FIELD FUSE N... neutral Q1CL... overcurrent overload switch Q2L... overload protector Q3M, Q4M... thermal protector Q5E... field earth leak detector R1P... reverse phase protector S1T... thermostat X1M... terminal strip X2A,X3A... connector Z1F... noise filter 4.2.1. Cautions - Use solid core cables to avoid loosening of the wires. - Do not use flexible or stranded wires to avoid the risk for short circuit! - Remove maximum 8mm of the PVC wire insulation when connecting the wires to the terminals. (see figure 6) 4.2.2. Minimum recommended field cables and field fuses MODEL field fuse interconnection cable section 5. DISPOSAL REQUIREMENTS NOTES R25V11 12A 1.5 mm 2 R35V11 12A 1.5 mm 2 R45V11 16A 1.5 mm 2 R45W11 12A 1.5 mm 2 BLK... black wire BLU... blue wire BRN... brown wire GRN/YLW... green/yellow wire GRY... grey wire ORG... orange wire RED... red wire WHT... white wire YLW... yellow wire Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.

Zandvoordestraat 300, B-8400 Oostende, Belgium 4PWE09344-1