INDIRECT FIRED, SEMI-INSTANTANEOUS STEAM & BOILER WATER HEATER. Compact Design. High Recovery. Energy Efficient. Stainless Alloy Construction

Similar documents
Packaged Semi-Instantaneous Steam Fired Water Heater

Semi-Instantaneous Indirect Fired Water Heater

Heat Transfer Packages

Packaged Steam Fired Water Heater

ASME Packaged Indirect Fired Water Heater

SuperTherm (VS Series) Indirect Fired, Semi-Instantaneous, Steam and Boiler Water Heater

High Capacity Instantaneous Steam Fired Water Heater

SWH Series. STONESTEEL Packaged Copper Coil Water Heaters Steam/Boiler Water/High Temperature Hot Water Vertical or Horizontal

SEH Series. Stainless Steel Instantaneous Packaged Steam Fired Water Heaters

Commercial Semi-Instantaneous Water Heaters

Water Heaters. Solar Applications

P-K COMPACT SEMI-INSTANTANEOUS INDIRECT WATER HEATERS

Plate Water Heaters Brazed Plate Water Heaters-BPH Series Plate and Frame Water Heaters-PFH Series

Bryan Water-Pak Indirect Systems 360,000 BTU to 4,500,000 BTU Inputs 199 to 3,533 Gallons Storage Capacity

USG Series. Unfired Steam Generators Generate Clean Steam With Boiler Steam or High Temperature Hot Water as the Energy Source

Plate Water Heaters Brazed Plate Water Heaters-BPH Series Plate and Frame Water Heaters-PFH Series

SECTION PLUMBING EQUIPMENT

COBREX. Semi-Instantaneous. Steam-Fired Domestic Hot Water Generator. Up to 7000 MBH 150/ 175/ 215 Gallon Tank 25-year Warranty. PVI.

Instant hot water Feed-Forward system unlimited supply accurate to +/- 4 F

SECTION WATER HEATERS

Indirect Fired Water Heater

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

OPERATING AND MAINTENANCE MANUAL FOR BOILER WATER OR HIGH TEMPERATURE HOT WATER (HTHW) POWERED WATER HEATER

STORAGE TANK INSTALLATION and OPERATION MANUAL

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

LOW NOx, HIGH EFFICIENCY, HOT WATER SUPPLY AND HYDRONIC HEATING BOILERS

Packaged Instantaneous Domestic Hot Water Generator Energy Source: Boiler Water

SECTION DOMESTIC WATER HEATERS

SPH Series. Vertical Packaged Storage Boiler Water Fired Plate Heat Exchanger Water Heaters CEMLINE CORPORATION

SECTION STEAM CONDENSATE PUMPS

Operation & Maintenance Manual

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

SECTION PLUMBING EQUIPMENT

Unfired Steam Generators (Series RB) Installation, Operation and Maintenance

BASCO U-TUBE & TANK IMMERSION HEAT EXCHANGERS. ...world leaders in heat transfer technology

TABLE OF CONTENTS BRADFORD WHITE BOILERS

Design and Construction Standards SECTION PLUMBING EQUIPMENT

2015 UPC Chapter 8 Indirect Wastes RV

FFH Series. Steam Fired Instantaneous Feed Forward Water Heaters

Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW

Niles Steel Tank Hot Water Generator Installation and Operation Manual

TURBOMAX USE & CARE MANUAL WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

SAMPLE SPECIFICATIONS

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL

EZ Plate Instantaneous

SECTION ROTARY-SCREW WATER CHILLERS

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

Technical Data Manual Model Nos. and pricing: see Price List

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Installation, Operation and Maintenance

Suggested Specifications Prestige Excellence 110

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

IN THE MARINE INDUSTRY

SECTION ELECTRIC WATER HEATERS

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Armstrong Flo-H2O Water to Water Instantaneous Heater Installation and Maintenance & Operation

Owner s Manual Therma-Stor II Heat Recovery System

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

SECTION HEATING BOILERS

INTRODUCING THE BRADFORD WHITE 24/7 EXPERT SUPPORT CENTER. TABLE OF CONTENTS. Technical Support: Warranty Support:

Domestic Pump Condensate Transfer Equipment

DIVISION FINNED WATER-TUBE BOILERS

DUKE UNIVERSITY DESIGN GUIDELINES

DIVISION FINNED WATER-TUBE BOILERS

ASME Packaged Electric Water Heater

Engineering Bulletin Rev B. Contents. Piping Arrangements for Heat Pump Water Heating Systems

ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL

1.1 This section applies to air handling units for HVAC Systems.

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

GOLD Plus 30/40/60/80

FINNED WATER-TUBE POOL HEATERS

SECTION PACKAGED HEAT TRANSFER SYSTEM

TURBOPOWER. Non-Condensing Gas, Oil or Combination Gas/Oil Storage Water Heater. 199 to 4000 MBH 150 to 4500 Gallons Tanks 25-year Warranty. PVI.

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

International Reactor Bulletin 1100 Corporation. Standard and Custom Reactors for the Chemical Process Industries

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

DIVISION FINNED WATER-TUBE BOILERS

Models 1005, 1505, 2005 Up to 99% thermal efficiency!

EHB Series. STONESTEEL Commercial Electric Water Heaters Individually Mounted Elements Vertical or Horizontal CEMLINE CORPORATION


SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR

Williams & Davis Boilers

A complete, compact steam heat exchange solution for process and domestic water heating requirements.

199,000 to 4,000,000 Btu/h 150 to 4500 Gallons Storage

FXLF-9. High Efficiency Water Heaters and Boilers

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

TANKLESS PRODUCT GUIDE

WATER-TUBE POOL HEATERS

INDIRECT FIRED EQUIPMENT INSTALLATION FORM

Transcription:

INDIRECT FIRED, SEMI-INSTANTANEOUS STEAM & BOILER WATER HEATER Compact Design High Recovery Energy Efficient Stainless Alloy Construction Factory Packaged Integral Safety System ASME Constructed & Stamped

DHT VTSI & VSI SERIES The DHT VTSI & VSI series of semi-instantaneous water heaters is the engineered solution where high recovery capacity is required and space is at a premium. The DHT VTSI & VSI series are constructed of stainless steel pipe and other non-ferrous materials to insure long leak-free operation. Designed for continuous high peak loads, the VTSI & VSI series are ideal for high demand applications such as hospitals or dormitories. Units are custom engineered using steam, boiler water or HTHW as the heating medium. VTSI & VSI units are supplied as a complete packaged system with components engineered to specific application requirements. The user simply connects domestic water to the supply and return connections in the field. Use the DHT selection tables to select the correct size and match components for peak performance. Semi-instantaneous operation provides high output by channeling the incoming cold water directly over the tubes of the heat exchanger in a controlled manner maximizing the heat transfer rates when compared to conventional stratified heat exchanger convection systems. Water is heated to the desired outlet temperature via the control valve as it exits the VTSI or VSI outlet. Velocity of water and pressure drop are controlled by changing water flow directly across the heat exchanger, which increases heat transfer and inhibits scale formation. High gain response is achieved by locating the temperature sensing probe in the outlet flow of water exiting the system thereby eliminating any stagnation zones which cause false readings. DHT water heater systems are the perfect choice where high capacity is required and space is limited. The vertical configuration requires less than four square feet of floor space and the tube bundle can be removed straight out or downward from the bottom of the unit. No overhead space or extra clearances are required for service or maintenance. Horizontal configurations, with rack-mounted stands, are also available making the DHT VTSI & VSI series a perfect fit in any mechanical room. APPLICATIONS Commercial VTSI & VSI series capacity ranges are well suited for meeting the large hot water demands of hotels, apartment buildings, military barracks and hospitals. Typically utilized in facilities with a central heating energy source, the units are perfect choices for installation in smaller satellite equipment rooms. Units may be piped in parallel or series to provide additional capacity or emergency backup. Institutional - VTSI & VSI series are widely used in facilities that exhibit high demand loads at varying intervals throughout the day. Dormitories, schools and correctional complexes exhibit strong sudden demands that are difficult for conventional convection heaters to sustain. Smaller units may be combined with storage tanks to ease the energy source requirements during minimal use periods. Industrial - VTSI & VSI series are used for high demand process applications that require a continuous flow of hot water. Other uses such as equipment food service wash down and cafeteria needs are also served by this versatile system. Construction DHT fabricates most units specifically to customer requirements. Stock systems are available for quick or emergency needs. All materials used in the construction of VTSI & VSI series systems are copper alloy or 316 stainless steel to assure long life and rust free domestic water. Each unit is fabricated by skilled technicians certified to ASME Sect IX, inspected, and stamped in accordance to ASME Sect VIII requirements. Working pressures up to 300 psig are available. The heat exchanger section is fabricated from copper, copper nickel or double wall tubes as well as 316 stainless steel for deionized water heating. Each heat transfer bundle is engineered to provide proper velocity and pressure drops while providing optimal heat transfer. The DHT VTSI & VSI series will provide exceptional long life, dependability and ease of maintenance. Seismic rated construction is available to meet IBC and other codes. Water Heater Control Panel STANDARD FEATURES Microprocessor Based Two Line Alpha-Numeric 40 Character LCD Display 3 Function Keys Isolated 24VDC Sensor Power 4/20MA 1 Analog Input 8 Digital Inputs 1 Analog Output 4 Relay Outputs 5 AMP. Fully User Programmable in English Pop Up Alarm Screens P.I.D. Setpoint Control RS485 MODBUS Data Port Compatible with BMS/BAS INPUT Temperature Set Point High Limit Temperature Set Points OUTPUT Power Normal High Temperature Alarm 2

Sizing DHT Semi-Instantaneous Water Heater To size DHT Semi-Instantaneous Water Heater you must determine the total water flow rate. First you have to determine total fixture units for all fixtures by using hot water demand in fixture units tables, then determine the demand GPM of hot water from the chart below. HOT WATER FLOW RATE CURVE 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 SEE ENLARGED DETAIL ON CHART AT RIGHT FIXTURE UNITS RESTAURANTS HOSPITALS, NURSING HOMES, NURSES RESIDENCE, APT. HOUSES, HOTELS & MOTELS OFFICE BUILDINGS AND HIGH SCHOOLS FIXTURE UNITS HOT WATER DEMAND IN FIXTURE UNITS (140 F WATER) Sizing: Determine the total fixture units for all fixtures by using the above table. Determine the required GPM from the above Hot water flow rate curve. Select the model of the water heater from Water heater selection chart according to the calculated GPM and the given steam pressure or boiler water temperature. EXAMPLE: Apartment building has 20 apartments: Bathtubs 1.5 x 20 = 30 Dishwashers 1.5 x 20 = 30 Kitchen Sinks 0.75 x 20 = 15 Total 75 Demand from the curve above (Green color): 30 GPM If steam pressure supplied to the Building 5 psig, the unit model is VTSIS24HB8A2-4-30, or VSISB8A2-4-30 (USING CHARTS FOR TEMPERATURE RISE 40-140 ON PAGES 5 & 7. FOR BOILER WATER USE CHART ON PAGE 8) 3

DHT VTSI (TANK) SERIES DHT VTSI Series Semi-Instantaneous Water Heater Overall Dimensions Heating Source: STEAM WATER OUTLET INSULATION & JACKETING WATER SOLENOID T & P VALVE PROBE & WELL STEAM INLET THERMOMETER AQUASTAT CONTROL BOX STEAM STRAINER PILOT PRESSURE GAUGE WATER INLET B A CONTROL VALVE DRIP STRAINER DRIP TRAP CONDENSATE E C RECIRCULATING PUMP CONDENSATE STRAINER MAIN TRAP F D RECIRCULATION VTSIS18HB6A2-X-XX VTSIS24HB8A2-X-XX VTSIS30HB10A2-X-XX VTSIS30HB12A2-X-XX 51.0 48.0 40.0 50.0 52.0 49.0 48.0 52.0 57.0 54.0 54.0 57.0 58.0 55.0 59.0 59.0 NOTE: Above dimensions are company s standard model. For customers who wish to have a custom build, please consult with the engineering department. (Steam pilot shown, pneumatic and electric control available). 4

DHT VTSI (Tank) Series Semi-Instantaneous Water Heater Selection Chart GPM 10 20 30 40 50 60 70 80 90 100 GPM 10 20 30 40 50 60 70 80 90 100 Heating Medium (Steam) Temperature Rise From 40 o -140 o F Steam Inlet Pressure (PSI) Pressure in lines / Pressure in heat exchanger 5/2 10/5 15/10 25/15 50/25 VTSIS18HB6A2-3-36 VTSIS18HB6A2-5-30 VTSIS18HB6A2-5-30 VTSIS18HB6A2-6-30 VTSIS18HB6A2-7-24 VTSIS24HB6A2-3-36 VTSIS24HB6A2-4-36 VTSIS24HB6A2-5-36 VTSIS24HB8A2-6-36 VTSIS18HB8A2-5-30 VTSIS24HB8A2-4-30 VTSIS24HB8A2-6-30 VTSIS24HB8A2-5-24 VTSIS24HB8A2-5-24 VTSIS24HB8A2-6-24 VTSIS24HB8A2-6-36 VTSIS24HB8A2-6-36 VTSIS24HB8A2-5-30 VTSIS24HB8A2-5-30 VTSIS24HB8A2-6-30 VTSIS24HB8A2-3-36 VTSIS24HB8A2-4-36 VTSIS24HB8A2-5-36 VTSIS24HB8A2-5-30 VTSIS24HB8A2-5-30 VTSIS30HB10A2-8-36 VTSIS30HB10A2-5-30 VTSIS30HB10A2-8-30 VTSIS30HB10A2-8-30 VTSIS30HB10A2-6-24 VTSIS30HB10A2-6-36 VTSIS30HB10A2-8-36 VTSIS30HB10A2-8-36 VTSIS30HB10A2-6-30 VTSIS30HB10A2-6-30 VTSIS30HB12A2-4-30 VTSIS30HB10A2-4-36 VTSIS30HB10A2-6-36 VTSIS30HB10A2-5-30 VTSIS30HB10A2-6-30 VTSIS30HB12A2-4-36 VTSIS30HB12A2-6-36 VTSIS30HB12A2-6-30 VTSIS30HB12A2-4-24 VTSIS30HB12A2-5-24 VTSIS30HB12A2-4-36 VTSIS30HB12A2-5-36 VTSIS30HB12A2-5-30 VTSIS30HB12A2-6-30 VTSIS30HB12A2-4-24 Heating Medium (Steam) Temperature Rise From 40 o -120 o F Steam Inlet Pressure (PSI) Pressure in lines / Pressure in heat exchanger 5/2 10/5 15/10 25/15 50/25 VTSIS18HB6A2-6-24 VTSIS18HB6A2-6-24 VTSIS18HB6A2-6-24 VTSIS18HB6A2-6-24 VTSIS18HB6A2-6-24 VTSIS24HB6A2-5-30 VTSIS24HB6A2-4-30 VTSIS24HB8A2-4-24 VTSIS24HB6A2-4-24 VTSIS18HB6A2-6-24 VTSIS24HB8A2-6-24 VTSIS24HB6A2-5-36 VTSIS24HB6A2-6-36 VTSIS24HB6A2-4-30 VTSIS24HB6A2-5-30 VTSIS24HB8A2-6-30 VTSIS24HB8A2-4-24 VTSIS24HB8A2-5-24 VTSIS24HB8A2-6-24 VTSIS24HB8A2-6-24 VTSIS24HB8A2-4-30 VTSIS24HB8A2-5-30 VTSIS24HB8A2-6-30 VTSIS24HB8A2-6-30 VTSIS24HB8A2-6-24 VTSIS30HB10A2-5-24 VTSIS30HB8A2-3.5-30 VTSIS30HB8A2-4-30 VTSIS30HB8A2-6-30 VTSIS24HB8A2-6-30 VTSIS30HB10A2-8-30 VTSIS30HB10A2-4-24 VTSIS30HB10A2-6-24 VTSIS30HB10A2-6-24 VTSIS30HB10A2-6-24 VTSIS30HB12A2-4-30 VTSIS30HB10A2-5-30 VTSIS30HB10A2-5-30 VTSIS30HB10A2-6-24 VTSIS30HB10A2-6-24 VTSIS30HB12A2-4-36 VTSIS30HB10A2-4-36 VTSIS30HB10A2-4-30 VTSIS30HB10A2-4-24 VTSIS30HB10A2-5-24 VTSIS30HB12A2-4-36 VTSIS30HB12A2-5-36 VTSIS30HB12A2-4-30 VTSIS30HB12A2-6-30 VTSIS30HB12A2-4-24 NOTE: For performance rating greater or less then the table provided above, please consult with company s engineering department for further details. For performance rating for units with double wall tubes please consult with company s engineering department. 5

DHT VSI (VERTICAL) SERIES DHT VSI Series Semi-Instantaneous Water Heater Selection Chart Heating Source: STEAM TEMPERATURE TRANSMITTER OR PROBE CHECK VALVE PUMP BALL VALVE DOMESTIC WATER OUTLET T & P RELIEF VALVE THERMOMETER WATER SOLENOID VALVE CONTROL PANEL INSULATION & JACKET I/P TRANSDUCER SHUTOFF SOLENOID VALVE STEAM CONTROL VALVE STEAM STRAINER DOMESTIC WATER INLET CONDENSATE STRAINER DRIP LEG THERMODYNAMIC TRAP WITH STRAINER CONDENSATE L MAIN F & T TRAP Vertical Stand Configuration DHT WATER HEATER SYSTEM DIMENSIONS (inches) (Vertical Configuration) DHT Model Number OH OL H L VSISB6A2-X-XX 79 28 VSISB8A2-X-XX 79 32 VSISB10A2-X-XX 79 38 VSISB12A2-X-XX 93 42 Width (not shown) 38 24 23.75 38 30 23.75 38 30 23.75 40 34 25.75 NOTE: Above dimensions are company's standard models. For customers who wish to have a custom build, please consult with the DHT Engineering Department. (Pneumatic control shown, pilot, and electric available) 6

DHT VSI (Vertical) Series Semi-Instantaneous Water Heater Selection Chart VSISB6A2-3-36 VSISB6A2-5-30 VSISB6A2-5-30 VSISB6A2-6-30 VSISB6A2-7-24 VSISB6A2-3-36 VSIS6A2-4-36 VSISB6A2-5-36 VSISB8A2-6-36 VSISB8A2-5-30 VSISB8A2-4-30 VSISB8A2-6-30 VSISB8A2-5-24 VSISB8A2-5-24 VSISB8A2-6-24 VSISB8A2-6-36 VSISB8A2-6-36 VSISB8A2-5-30 VSISB8A2-5-30 VSISB8A2-6-30 VSISB8A2-3-36 VSISB8A2-4-36 VSISB8A2-5-36 VSISB8A2-5-30 VSISB8A2-5-30 VSISB10A2-8-36 VSISB10A2-5-30 VSISB10A2-8-30 VSISB10A2-8-30 VSISB10A2-6-24 VSISB10A2-6-36 VSISB10A2-8-36 VSISB10A2-8-36 VSISB10A2-5-30 VSISB10A2-6-30 VSISB12A2-4-30 VSISB10A2-4-36 VSISB10A2-6-36 VSISB10A2-5-30 VSISB10A2-6-30 VSISB12A2-4-36 VSISB12A2-6-36 VSISB12A2-6-30 VSISB12A2-4-24 VSISB12A2-5-24 VSISB12A2-4-36 VSISB12A2-5-36 VSISB12A2-5-30 VSISB12A2-6-30 VSISB12A2-4-24 VSISB 6A2-6-24 VSISB 6A2-6-24 VSISB 6A2-6-24 VSISB 6A2-6-24 VSISB 6A2-6-24 VSISB 6A2-5-30 VSISB 6A2-4-30 VSISB 8A2-4-24 VSISB 6A2-4-24 VSISB 6A2-6-24 VSISB 8A2-6-24 VSISB 6A2-5-36 VSISB 6A2-6-36 VSISB 6A2-4-30 VSISB 6A2-5-30 VSISB 8A2-6-30 VSISB 8A2-4-24 VSISB 8A2-5-24 VSISB 8A2-6-24 VSISB 8A2-6-24 VSISB 8A2-4-30 VSISB 8A2-5-30 VSISB 8A2-6-30 VSISB 8A2-6-30 VSISB 8A2-6-24 VSISB 10A2-4-24 VSISB 8A2-3.5-30 VSISB 8A2-4-30 VSISB 8A2-6-30 VSIS 8A2-6-30 VSISB 10A2-8-30 VSISB 10A2-4-24 VSISB 10A2-6-24 VSISB 10A2-6-24 VSISB 10A2-6-24 VSISB 12A2-4-30 VSISB 10A2-6-30 VSISB 10A2-5-30 VSISB 10A2-6-24 VSISB 10A2-6-24 VSISB 12A2-4-36 VSISB 10A2-4-36 VSISB 10A2-4-30 VSISB 10A2-4-24 VSISB 10A2-5-24 VSISB 12A2-4-36 VSISB 12A2-5-36 VSISB 12A2-4-30 VSISB 12A2-6-30 VSISB 12A2-4-24 NOTE: For performance rating greater or less then the table provided above, please consult with company s engineering department for further details. For performance rating for units with double wall tubes please consult with company s engineering department. 7

DHT VSI (VERTICAL) SERIES DHT VSI Series Semi-Instantaneous Water Heater Selection Chart Heating Source: BOILER WATER TEMPERATURE TRANSMITTER OR PROBE CHECK VALVE DOMESTIC WATER OUTLET T & P RELIEF VALVE THERMOMETER WATER SOLENOID VALVE OH BALL VALVE I/P TRANSDUCER SHUTOFF SOLENOID VALVE PUMP DOMESTIC WATER INLET CONTROL PANEL INSULATION & JACKET TWO OR THREE WAY WATER CONTROL VALVE H BOILER OR HTHW OUTLET BOILER OR HTHW INLET L OL Vertical Stand Configuration DHT WATER HEATER SYSTEM DIMENSIONS (inches) (Vertical Configuration) DHT Model Number OH OL H L VSISW6A2-X-XX 88 28 VSISW8A2-X-XX 88 32 VSISW10A2-X-XX 88 38 VSISW12A2-X-XX 96 42 Width (not shown) 42 24 23.75 42 30 23.75 42 30 23.75 42 34 25.75 NOTE: Above dimensions are company's standard models. For customers who wish to have a custom build, please consult with the DHT Engineering Department. (Pneumatic control shown, pilot, and electric available) 8

DHT VSI Series Semi-Instantaneous Water Heater Selection Chart Heating Source: BOILER WATER VSIW6A2-2.5-40 VSIW8A2-4-36 VSIW8A2-2.5-36 VSIW8A2-2.5-40 VSIW10A2-4-30 VSIW10A2-4-36 VSIW10A2-4-36 VSIW10A2-2.5-36 VSIW10A2-4-40 VSIW10A2-2.5-40 VSIW12A2-2.5-36 VSIW12A2-2.5-38 VSIW6A2-2.5-36 VSIW6A2-2.5-36 VSIW8A2-4-30 VSIW8A2-2.5-30 VSIW8A2-2.5-30 VSIW10A2-2.5-24 VSIW10A2-4-30 VSIW10A2-4-30 VSIW10A2-4-30 VSIW10A2-4-38 VSIW10A2-4-30 VSIW10A2-4-30 VSIW8A2-2-40 VSIW10A2-4-36 VSIW10A2-3-36 VSIW10A2-2.5-40 VSIW10A2-2.5-40 VSIW12A2-2-36 VSIW12A2-2.5-40 VSIW12A2-2.5-42 VSIW12A2-4-48 VSIW12A2-2.5-48 VSIW14A2-4-48 51 76 102 128 153 204 255 306 357 409 511 VSIW6A2-2-36 VSIW8A2-2.5-36 VSIW8A2-4-40 VSIW10A2-4-30 VSIW10A2-2.-30 VSIW10A2-6-36 VSIW10A2-4-38 VSIW10A2-3-40 VSIW12A2-4-36 VSIW12A2-4-36 VSIW12A2-4-36 500,000 750,000 1,000,000 1,250,000 1,500,000 2,000,000 2,500,000 3,000,000 3,500,000 4,000,000 5,000,000 NOTE: For performance rating greater or less then the table provided above, please consult with company s engineering department for further details. For performance rating for units with double wall tubes please consult with company s engineering department. 9

Double-Wall Tube Bundles for Water Heaters Meets Uniform Plumbing Code requirements for heating potable water. Prevents cross-contamination. Easy Inspections and low maintenance Fully visible, 360 vented leak detection between tubesheets. Bolting and gaskets for potable water and heating medium are completely independent. Individual tube access for easy maintenance. Optional: Tubesheet contacting potable water is solid 304 stainless steel Used to upgrade present single-wall tube bundles Available semi-instantaneous water heaters and exchangers with copper or cupro-nickel tubes and carbon steel or stainless steel tube sheets (Up to 400 PSIG with. cupro-nickel tubes) Double Wall Protection Performance Tube failure can be caused by corrosion, erosion, and vibration, and can result in the contamination of the domestic water system to be contaminated by a heating medium such as steam, hydronic water, glycol solution, etc. There is no practical way to have the heating medium sterile or free from harmful treatment compounds or corrosion by-products. A low pressure heating medium circuit does not ensure contamination protection of indirect, single-wall water heaters. Whether they are shell and tube, shell and coil, plate and frame, or any other type, all consist of relatively thin wall heat transfer surface separating the heating medium from the domestic water system. Therefore, the potential for cross contamination is real and in some instances contamination has occured. Several states and cities are now insisting on double-wall vented construction in all indirect type domestic water heaters. Plumbing codes have also been re-written to include double-wall protection. DHT has developed the most practical, state-of-the-art double tube wall heaters to preclude any possibility of contaminating the domestic water system. The heat transfer surface is 5/8 O.D. x.04 thick inner wall and 3/4 O.D. x.04 outer wall SB-75 or SB-111 copper tubing. The.04 dimensions are actual net tube wall thicknesses which equal.08 thickness of total wall separation. This is more than twice the thickness of many single wall water heater products. Both inside and outside tube surfaces are smooth (prime) with no fins or surface irregularities to promote scale formation or corrosion attack. Double-wall tubing has a similar overall heat conductivity as a single wall tube of equivalent wall thickness. The heat transfer capabilities were determined by actual tests. Each tube has multiple parallel and continuous vent paths. 10

DHT VTSI & VSI SERIES Stainless Steel Semi-Instantaneous Steam-Water Heating Systems DHT stainless steel semi-instantaneous water heater system is a very efficient, high quality and high capacity system for use with steam, boiler water, or high temperature water as a heating medium. DHT steam-water heater system has a small compact size and a wide range of capacities that are designed for many standard hot water applications. DHT s compact design makes it an ideal replacement unit where space is at a premium. Also the compact design and size reduces the installation time to the minimum. The customers only need to provide the connection line for cold and hot water, steam, condensate and electricity to service. DHT s stainless steel semi-instantaneous water heater system provides both designer flexibility and space saving design. Standard DHT Stainless Steel Semi-Instantaneous Water Heater System Material of Construction Coil Material: Standard - - - - - Copper Optional - - - - - -Cupro-Nickel Optional - - - - - -Stainless Steel Optional - - - - - -Double Wall Copper or Cupro-Nickel Shell - - - - - - - - - - - - - - - - - - - - - - - - High Alloy Stainless Steel Piping - - - - - - - - - - - - - - - - - - - - - - - Copper, Brass Insulation - - - - - - - - - - - - - - - - - - - - Fiberglass Protection Jacket - - - - - - - - - - - - - - -20 Gauge Steel/Vinyl Support Skid - - - - - - - - - - - - - - - - - - Carbon Steel OPTIONAL: 1. Electric Control Box 2. Recirculator Package 3. Double Solenoid Safety System Standard DHT Stainless Steel Steam or Boiler Water Heater System Package Includes: Compact Design A.S.M.E.CODE Construction (225 PSIG of water pressure at 300 ) High Alloy Stainless Steel Tanks/Shells High Alloy Stainless Steel Threaded Connections (domestic water only) Fiberglass Insulation 20 Gauge Steel Jacket Carbon Steel Support Base A.S.M.E Relief Valve-Pressure and Temperature Temperature gage Pressure Gauge Drain Valve Solenoid Safety System Temperature Control Valve (self conatined or pneumatic) Steam, Condensate Strainers (steam only) F&T Traps (steam only) 3-Way - Optional Control Valve with Safety Solenoid Drip Strainer 11

DHT VTSI & VSI SERIES (PIPING LAYOUTS) Steam Water Heater Single Unit Hot Water Out Recirculation Steam Supply T / To Drain Cold Water In Condensate Return Condensate to Gravity Free Drain or to Pump to Lift P Drain Steam Water Heater Dual Unit T / P T / P 12

Steam Water Heater Single Unit with Storage Tank Hot Water Supply To Drain Hot Water Out Condensate Return Condensate to Gravity Free Drain or to Pump to Lift Steam Supply P T Drain / To Drain Recirculation Cold Water In Hot Water Return Storage Tank Boiler Water Heater Single Unit Hot water Outlet To Drain Recirculation Boiler Water Supply T / Cold Water In Boiler Water Return Drain 13

Specifications for DHT Water Heater Each heater shall be capable of being disassembled and the heat exchanger section removed for inspection and service without breaking water connections. The bolting between the steam bonnet, tube sheet and shell flange shall be independent of each gasket to allow inspection and replacement of either gasket without disturbing the other gaskets. Each heater shall have easy access to the individual tubes without moving the heater from its installed position. Steam to Water Furnish and install where shown on the plans water heater(s), Model Number, manufactured by Diversified Heat Transfer, Inc. Each heater shall be factory assembled package rated to heat.gpm of water from F to _ F and control the outlet within 4 F of the selected temperature, when supplied with psig saturated steam before the control valve. The domestic water pressure drop through the heater shall not exceed psig. Each heater shall be constructed and stamped in accordance with Section VIII of the ASME Code for a working pressure of 150 psig. Inspection form U -1 shall be furnished. Each packaged heater shall consist of the following components completely factory assembled so that the contractor need only connect to service. 1. Water heater with stainless steel shell and heat exchanger wrapper, copper or Cu-Ni tubes, non ferrous or carbon steel with non-ferros liner tube sheet and baffles, carbon steel steam chamber, steel vertical support skids and lifting lug. 2. Steam strainer. 3. Temperature control valve ( pilot operated or air operated). 4. Condensate strainer. 5. Main steam trap. 6. Auxiliary steam trap. 7. Water thermometer and steam pressure gauge. Thermometer installed with separable thermowell. 8. ASME pressure relief valve for domestic water. 9. Insulation: 1-1/2 fiberglass covered with a galvanized steel or plastic gasket. 10. Bronze circulator 115 volt/60 cycle/single phase, wired for continuous operation. (Optional Yes, No) 11. Component piping. 12. Solenoid Safety System ( Single, Double) 13. Electric Control Box (Optional Yes, No) 14. Installation and operating instructions. The manufacturer shall assume the operational responsibility for all components of the package. Water to Water Furnish and install where shown on the plans water heater(s), Model Number, manufactured by Diversified Heat Transfer, Inc. Each heater shall be factory assembled package rated to heat.gpm of water from F to _ F and control the outlet within 4 F of the selected temperature, when supplied with boiler water. The domestic water pressure drop through the heater shall not exceed psig. Each heater shall be constructed and stamped in accordance with Section VIII Inspection form U -1 shall be furnished. of the ASME Code for a working pressure of 150 psig. Each packaged heater shall consist of the following components completely factory assembled so that the contractor need only connect to service. 1. Water heater with stainless steel shell and heat exchanger wrapper, copper or Cu-Ni tubes, non ferrous or carbon steel with non-ferros liner tube sheet and baffles, carbon steel steam chamber, steel vertical support skids and lifting lug. 2. Temperature control valve ( pilot operated or air operated). 3. Water thermometer and steam boiler water pressure gauge. Thermometer installed with separable thermowell. 4. ASME pressure relief valve for domestic water. 5. Insulation: 1-1/2 fiberglass covered with a galvanized steel or plastic jacket. 6. Bronze circulator - 115 volt/60 cycle/single phase, wired for continuous operation. (Optional Yes, No) 7. Component piping. 8. Solenoid Safety System ( Single, Double) 9. Electric Control Box (Optional Yes, No) 10. Installation and operating instructions. The manufacturer shall assume the operational responsibility for all components of the package. INDIRECT FIRED SEMI-INSTANTANEOUS STEAM & WATER HEATER Manufacturers and Designers Since 1938. www.dhtnet.com www.dhtcoils.com Tel: 1-800-221-1522 Pub DHT03R1 12/15