PERFORMANCE OF EARTH TUBE HEAT EXCHANGER COOLING OF AIR A REVIEW

Similar documents
EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Performance Study of Triple Concentric Pipe Heat Exchanger

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Enhancement of COP using Nanoadditives in Domestic Refrigerator

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Performance investigation of Air-conditioning system using ejector as expansion device

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

INDIRECT EVAPORATIVE COOLING A PAST REVIEW

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Use of Earth to Air Heat Exchangers for Cooling M. Santamouris University of Athens, Greece

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Adsorption refrigeration system using waste heat

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Heat transfer and heating rate of food stuffs in commercial shop ovens

Simulation Of Pneumatic Drying: Influence Of Particle Diameter And Solid Loading Ratio

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Analysis of Coefficient of Performance & Heat Transfer Coefficient on Sterling Cycle Refrigeration system.

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

*Corresponding author;

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Modified Air Cooler with Split Cooling Unit

Solar Drying Techniques And Performance Analysis: A Review

Global Journal of Engineering Science and Research Management

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Performance Analysis of Heat Pipe using Different Screen Mesh Sizes Manikandan.K * 1, Senthilkumar.R 2,

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

ANALYSIS OF DESICCANT COOLING SYSTEM

Experimental assessment of a PCM to air heat exchanger storage system for building ventilation applications

ABSTRACT I. INTRODUCTION

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

An Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

STUDY OF PERFORMANCE AND POSSIBLE CONFIGURATION OF HYBRID AIR CONDITIONING SYSTEM WITH AND WITHOUT COMBINED PELTIER MODULE AND EARTH HEAT EXCHANGER.

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Enhancement of Heat Exchanger Performance by the Extended Surfaces-Fins

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Waghmare Tushar Ramrao, D.S.Nakate

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

DESIGN AND ANLYSIS OF MODIFIED HYBRID SOLAR SYSTEM USING NANO FLUIDS

Recent Advances in Energy, Environment and Economic Development

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

STUDY OF HEAT TRANSFER IN A CORRUGATED PLATE HEAT EXCHANGER USING AL 2 O 3 MICROPARTICLES

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Performance Analysis for the Double- Pass Solar Air Collector with and Without Porous Media

η second law = Second law efficiency

PULLOUT CAPACITY OF HORIZONTAL AND INCLINED PLATE ANCHORS IN CLAYEY SOILS

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Transcription:

Int. J. Mech. Eng. & Rob. Res. 2015 Ashish Kumar Chaturvedi and V N Bartaria, 2015 Review Article ISSN 2278 0149 www.ijmerr.com Vol. 4, No. 1, January 2015 2015 IJMERR. All Rights Reserved PERFORMANCE OF EARTH TUBE HEAT EXCHANGER COOLING OF AIR A REVIEW Ashish Kumar Chaturvedi 1 * and V N Bartaria 1 *Corresponding Author: Ashish Kumar Chaturvedi, achaturvedi452@gmail.com The temperature of earth at a certain depth about 2 to 3 m the temperature of ground remains nearly constant throughout the year. This constant temperature is called the undisturbed temperature of earth which remains higher than the outside temperature in winter and lower than the outside temperature in summer. When ambient air is drawn through buried pipes, the air is cooled in summer and heated in winter, before it is used for ventilation. The earth air heat exchanger can fulfil in both purpose heating in winter and cooling in summer. This paper investigates the experimental studies on earth air heat exchanger system in parallel connection in the summer climate. In the proposed work to investigates the experimental studies on earth tube heat exchanger cooling of air in summer and heating with air in winter climate in LNCT Energy Park Raisen Road Bhopal, M.P. Keywords: Earth tube heat exchanger, Investigations, Cooling air INTRODUCTION The Energy consumption of buildings for heating and cooling purpose has significantly increased during the decades. Energy saving are of major concern everywhere is a particular challenge in desert climates. The desert climate can be classified as hot and arid and such condition exists in anumber of areas throughout the world. In general most people feel comfortable when the temperature is between 20 C and 26 C and relative humidity is within the range of 40 to 60%.These condition are often achieved through the use of air conditioning. Air conditioning system is widely employed for the comfort of occupant as well as the industrial productions. It can be achieved effectively by vapour compression machines, but due to the depletion of ozone layer and global warming by using chlorofluorocarbons and the need to minimize high grade energy consumption various passive techniques are now a day s introduced, one such method is earth air heat exchanger. An earth air heat exchanger consist in one or more tubes lied under the ground in order to cool in summer or pre-heat in winter 1 ME Department, LNCT, Bhopal, MP, India. 378

air to be supplied in a building. The physical phenomenon of earth air heat exchanger is simple: the ground temperature commonly higher than the outdoor air temperature in winter and lower in summer, so it makes the use of the earth convenient as warm or cold sink respectively. Both of the above uses of earth air heat exchanger can contribute to reduction in energy consumption. Several researchers have described the Earth-to-Air Heat Exchangers (EAHE) coupled with buildings as an effective passive energy source for building space conditioning. An earth-to-air heat exchanger system suitably meets heating and cooling energy loads of a building. Its performance is based upon the seasonally varying inlet temperature, and the tunnel-wall temperature which further depends on the ground temperature. The performance of an EAHE system depends upon the temperature and moisture distribution in the ground, as well as on the surface conditions. WORKING PRINCIPAL OF EARTH TUBE HEAT EXCHANGER The principal of using the principle of using ground inertia for heating and cooling is not a new concept, but rather a modified concept that goes back to the Ancients. This technology has been used throughout history from the ancient Greeks and Persians in the pre- Christian era until recent history (Santamouris and Asimakopoulos, 1996). For instance the Italians in the middle Ages used caves, called colvoli, to nprecool/preheat the air before it entered the building. The system which is used nowadays consists of a matrix of buried pipes through which air is transported by a fan. In the summer the supply air to the building is cooled due to the fact that the ground temperature around the heat exchanger is lower than the ambient temperature. During the winter, when the ambient temperature is lower than the ground temperature the process is reversed and the air gets preheated. TYPES OF EARTH TUBE HEAT EXCHANGER Ther are two types of heat exchanger: 1. Open type Earth tube heat exchanger 2. Closed type Earth tube heat exchanger Open System In open system, ambient air passes through tubes buried in the ground for preheating or pre-cooling and then the air is heated or cooled by a conventional air conditioning unit before entering the building. Closed System In this case heat exchangers are located underground, either in horizontal, vertical or oblique position, and a heat carrier medium is circulated within the heat exchanger, transferring the heat from the ground to a heat pump or vice versa. LITERATURE REVIEW The Heat transfer to and from Earth tube heatexchanger system has been the subject of many theoretical and experimental investigations. By having a review on previous research papers published by many authors we can have an idea on how it works.sehli et al. proposed a one-dimensional numerical model to check the performance of EAHEs installed at different depths. It was concluded that EAHE systems alone are not sufficient to 379

Proposed Setup Diagram Note: Here:T i = inlet temp.; T o = outlet temp.; T md = middle temp. create thermal comfort, but can be used to reduce the energy demand in buildings in South Algeria, if used in combination with conventional airconditioning system. Ghosal et al. developed a simplified analytical model to study year around effectiveness of an EAHE coupled greenhouse located in New Delhi, India. They found the temperature of greenhouse air on average 6-7 C more in winter and 3-4 C less in summer than the same greenhouse when operating without EAHE. Shukla et al. developed a thermal model for heating of greenhouse by using different combinations of inner thermal curtain, an earthair heat exchanger, and geothermal heating. Bansal et al. investigated the performance analysis of EAHE for summer cooling in Jaipur, India. They discussed 23.42 m long EAHE at cooling mode in the range of 8.0-12.7 C and 2-5 m/s flow rate for steel and PVC pipes. They showed performance of system is not significantly affected by the material of buried pipe instead it is greatly affected by the velocity of air fluid. They observed COP variation 1.9-2.9 for increasing the velocity 2-5 m/s. Santamouris et al. investigated the impact of different ground surface boundary conditions on the efficiency of a single and a multiple parallel earth-to-air heat exchanger system. EXPERIMENTAL SETUP The experimental setup is an open loop flow system has been designed and fabricated to conduct experimental investigation on the temperature difference for inlet and Outlet section, heat transfer, coefficient of performance and fluid flow characteristics of 380

a pipe in parallel connection. The experimental data are to be used to find the increase of cooling rate for the summer (May 2014) condition, and heating rate of winter (November 2014) conditiuonheat transfer coefficient. The Earth Tube Heat Exchanger Taken One horizontal pipe of 50 mm inner diameter with total length of 9 m. Three pipe each length of 3 m are connected in Series connection, made up of GI pipes and buried at a depth of 3 m in a flat land with dry soil. The Series connection of GI pipes exhaust manifold for air passage. Ambient air was sucked through the pipe by means of a centrifugal blower by a 2 phase, 0.25 hp, 230 V and 2800 rpm motor. The blower is used to suck the hot ambient air through the pipelines and delivered the cool air for required place in Summer (May 2014) climate and hot air required place in winter (November 2014). CONCLUSION In this paper the performance of earth air heat exchanger system was investigated and we have observed the following. 1. If the length of the pipe is so small and the blower is high voltage then the system is useless because the temperature difference between inlet and out let is very less. 2. The material of pipe is not affected in the output result. 3. If cooling or heating rate is more achieve, then the length of pipe kept at least 100 m and blower some around 400 W. REFERENCES 1. Baxter D O (1992), Energy Exchange and Related Temperature of an Earth-Tube Heat Exchanger in Heating Mode, Vol. 35, No. 1, pp. 275-285, Trans. ASAE. 2. Baxter D O (1994), Energy Exchange and Related Temperature of an Earth-Tube Heat Exchanger in Cooling Mode, Vol. 37, No. 1, pp. 257-267, Trans. ASAE. 3. Capozza A, De Carli M and Zarrella A (2012), Design of Borehole Heat Exchangers for Ground-Source Heat Pump: A Literature Review, Methodology Comparison and Analysis on the Penalty Temperature, Energy and Buildings, Vol. 55, No. 12, pp. 369-379. 4. Esen H, Inalli M and Esen M (2007a), Numerical and Experimental Analysis of a Horizontal Ground-Coupled Heat Pump System, Building and Environment, Vol. 42, pp. 1126-1134. 5. Esen H, Inalli M, Esen M and Pihtili K (2007b), Energy and Exergy Analysis of a Ground- Coupled Heat Pump System with Two Horizontal Ground Heat Exchangers, Building and Environment, Vol. 42, pp. 3606-3615. 6. Hellström G (1991), Ground Heat Storage, Thermal Analysis of Duct Storage Systems: Theory, Doctoral Thesis, Department of Mathematical Physics, University of Lund, Sweden. 7. Kim S K, Bae G O, Lee K and Song Y (2010), Field-Scale Evaluation of the Design of Borehole Heat Exchangers for the Use of Shallow Geothermal Energy, Energy, Vol. 35, No. 2, pp. 491-500. 381

8. Nam Y, Ooka R and Hwang S (2008), Development of a Numerical Model to Predict Heat Exchange Rates for a Ground-Source Heat Pump System, Energy and Buildings, Vol. 40, No. 12, pp. 2133-2140. 9. Santamouris M, Mihalakaha G, Balaras C A, Argirioua Asimakopoulos D and Vallinaras M (1995), Use of Buried Pipes for Energy Conservation in Cooling of Agricultural Greenhouse, Solar Energy, Vol. 35. pp. 111-124. 10. Scott N R, Parsons R A and Kochler T A (1965), Analysis and Performance of an Earth-Tube Heat Exchanger, ASAE Paper No. 65-840. St. Joseph, Michigan, ASAE. 11. Sharan G and Jadhav R (2003), Soil Temperature Regime at Ahmedabad, Journal of Agricultural Engineering, (forthcoming). 12. Spengler R W and Stombaugh D P (1983), Optimization of Earth-Tube Heat Exchanger for Winter Ventilation of Swine Housing, pp. 1186-1193, Trans. ASAE. 13. Yavuzturk C, Spitler J D and Rees S J (1999), A Transient Two-Dimensional Finite Volume Model for the Simulation of Vertical U-Tube Ground Heat Exchangers, ASHRAE Transactions, Vol. 105, No. 2, pp. 465-474. 14. Zarrella A, Scarpa M and De Carli M (2011a), Short Time-Step Performances of Coaxial and Double U-Tube Borehole Heat Exchangers: Modeling and Measurements, HVAC&R Research, Vol. 17, No. 6, pp. 959-976. 15. Zarrella A, Scarpa M and De Carli M (2011b), Short Time Step Analysis of Vertical Ground-Coupled Heat Exchangers: The Approach of CaRM, Renewable Energy, Vol. 36, No. 9, pp. 2357-2367. 16. Zarrella A and De Carli M (2013), Heat Transfer Analysis of Short Helical Borehole Heat Exchangers, Applied Energy, Vol. 102, No. 2, pp. 1477-1491. 17. Zeng H, Diao N and Fang Z (2002), A Finite Line-Source Model for Boreholes in Geothermal Heat Exchangers, Heat Transfer-Asian Research, Vol. 31, pp. 558-567. 382