DOW1171 / DCW1151 Radio fire detection system

Similar documents
FDCW221 / DOW1171 / SMF121 SMF6120 (repair/replacement) Radio fire detection system

DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

Radio fire detection system

SWING radio fire detection system

DC1192 Input /Output module

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

DT1101A / DT1102A / DO110xA Automatic fire detectors

OH720, OP720, HI720, HI722

DM1153H-Ex / DM1154H-Ex Manual call point 'Heavy Duty'-Ex

DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules

DF1151-Ex Infrared flame detector

FDM273 Radio manual call point Mounting

DBS721, DBS729 Sounder interbase, Sounder beacon interbase

Manual call points. Sinteso / Cerberus PRO FDM225, FDM226

OOH740, OOHC740 Automatic fire detectors

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

FDCL221-M Multi line separator module

ASA linear smoke detector

FDCW241 Radio gateway Mounting

FDOOT241-9, FDOOT241-A, FDO241, FDT241

Multi line separator module

Input module, input/output modules

Output module (230 V)

DM1131 / DM1133 / DM1134 Manual call points

FDBZ290 Air sampling smoke detection kit

DF1101-Ex Infrared flame detector

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

FDCIO223 (ES 45) Transponder

FDBZ290 Air sampling smoke detection kit

FDOOT221, FDO221, FDT221

DM1101 / DM1103 / DM1104 DM1103-L / DM1103-S Manual call points Manual release button and emergency stop button

Synova TM product catalog.

Room thermostat with 24-hour time switch and large LCD

XC10 Extinguishing control panels

Input module, input/output module

13 tones to choose from, 2 programmable alarm levels Adjustable sound levels up to 93 dba

Fire control panels FC726 FC726-XA

Cerberus FIT conventional system

Manual call point. Sinteso Cerberus PRO FDM223H, FDM224H. 'Heavy Duty' manual call point addressed (FDnet/C-NET)

FC722 Fire control panel

FDL241-9 Linear smoke detector Mounting Commissioning

Fire control panels FC360

Interbases. Sinteso FDSB221, FDSB228, FDSB229

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

FC2020 Fire control panel

FDOOT241-A9-Ex Multisensor fire detector

REA22 Room Temperature Controller

FC722 Fire control panel

Mimic display driver, LED ribbon cable

Frost Protection Thermostat

FC723 Fire control panel

Product Documentation

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

FC724 Fire control panel

FDCL221 Line separator

Consultant Specification AGILE Wireless Fire Detection System

FC724 Fire control panel

OOH740-A9-Ex Multisensor fire detector

OOH740-A9-Ex Multi-sensor fire detector

Call stations and extensions

Intrunet Wireless Portfolio for Intrunet SPC Series Intrunet SI Series and IC60

FDOOT241-A3, FDOOT241-A4, FDOOT241-A5, FDOOT241-A9, FDOOT241-8

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FDCL221-Ex Line adapter (Ex)

FT2080 Fire terminal (Touch) Mounting Installation

FT2080 Fire terminal (Touch) Mounting Installation

Overview. Wireless Overview QLD NSW VIC Fundamentals. Operation. Features.

FDCI221, FDCIO221 Input module, input/output module Technical Manual

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Healthy. Atmosphere. for Pigs and Poultry. for a

XC10 combined fire detection and extinguishing control

Sinteso TM product catalog.

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

RVL479. Heating Controller. for use with a partner unit

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Fire control panel for modernization

Room Temperature Sensor

SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon

XC10 combined fire detection and extinguishing control

Frost Units for air temperature monitoring

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM.

OH720, OP720, HI720, HI722 Automatic fire detectors Technical Manual

SHEPHERD. Smart solutions to protect and manage what matters the most to you

Semi flush-mount room thermostats

Products. PX-1 Smoke Alarm Device PX-1C Radio-Linked Smoke Alarm Device PX- ip Gateway Pyrexx App.

Installation & Operating Instructions

ABAX two-way wireless system

IC60 Sintony 60 Intrusion Control Panel

FS20 Fire detection system

OH110, OP110, HI110 Automatic fire detectors

Duct Temperature Sensors

Electronic timeswitch

Product Guide MAN7030-2

FC2040. Fire control panel. Sinteso. FS20 series, MP6

Control Products & Systems OEM

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

>WIRELESS> ALARM SYSTEM CR200

Wireless room thermostat with LCD

Transcription:

DOW1171 / DCW1151 Radio fire detection system Interactive AlgoRex Complete integration in the interactive fire detection system CS1140 Simultaneous operation of wired and wireless fire detectors New possibilities for systems engineering Adaptation to change of building utilization Rapid implementation of customers` requirements Transmission reliability practically the same as wired systems System integration test every 30 seconds Automatic specification of the optimum basic and backup radio channels Automatic change of channel in the event of radio interference 2 integrated antennae (antenna diversity) Bi-directional data traffic in SRD band Radio smoke detector with optimum signal evaluation through special computing procedures Individual detector addressing for easy identification of location Transmission of 4 danger levels Up to 30 detectors can be connected to each radio gateway Long battery service life (more than 5 years) Control Products and Systems

Application The chief application for the DS11 interactive wireless fire detection system is where for structural or aesthetic reasons, or for reasons of architectural conservation, only restricted use of cable or conduit is permitted. Typical fields of application Rooms of great historical value, e.g.: Museums Churches Libraries Rooms which permit only the shortest interruption to operations for wiring, e.g.: Hotel rooms Management secretariat Congress halls Aim and purpose In purpose-built premises, fire detection systems are optimized, planned and installed according to the requirements of the initial user. Experience shows that even the initial user's requirements are outpaced in the shortest possible time. The company expands the utilization and structures change and constructional changes are the result. These conditions can be dealt with by simply and quickly extending the DS11 system with the radio fire detection system. System overview The radio gateway DCW1151, which is connected to the interactive detector bus, communicates by radio with up to 30 DOW1171 radio smoke detectors. Each detector has its own location address. The radio gateway transmits the signals received from the radio smoke detectors via the detector bus to the fire detection control unit and passes on commands from the control unit to the radio smoke detectors. The radio fire detection system operates in the SRD band from 868-870MHz, a frequency range with the highest transmission and functional reliability, with clear instructions for all users. Control unit DS11 detector bus interactive DCW1151 DCW1151 CS114x DOW1171 DOW1171 Radio chamber 1 Radio chamber 2 2

Radio smoke detector DOW1171 Uniform response to the most varied types of fire Dynamic analysis of the sensor signal Smoke in the detector itself Built-in diagnostic algorithms with automatic self-test High immunity to false alarms and ambient influences High-quality optoelectronic sensor system Automatic compensation for soiling Simple exchange of detector and battery Radio gateway DCW1151 Functions Four danger levels allow the actuation of different counter-measures as well as an early warning in the event of an incorrect application. Self-test. Periodically or upon command the detector carries out a comprehensive self-test. Algorithms. Special computing procedures in the detector processor allow optimum signal evaluation as assigned to the detector. This ensures high immunity to interference and operational reliability. Measured value compensation. This gives the detector practically constant sensitivity throughout its entire service life. A built-in response indicator signals an alarm on the spot. Supply The DOW1171 radio smoke detector is supplied by two 9 V lithium batteries. In normal operating condition they have a service life of more than 5 years. Separate monitoring of each battery guarantees up to 30 days' operation of the detector even if one battery malfunctions. Installation Mounting with detector base DBW1171. The detector must only be inserted in the base during commissioning (address allocation). The detector can be inserted and removed using a detector exchanger up to a height of 7 meters. Signal transmission from and to the control unit Signal conditioning and monitoring of up to 30 detectors As programmable opener or closer relay contact to actuate fire control systems on the spot Supply The radio gateway DCW1151 is supplied via the detector bus. The additional 9 V battery guarantees the operation during commissioning or when the detector bus is dead. In normal operating condition the battery is switched off which leads to a service life of well over 5 years. Installation The housing with cover DCA1191 and the terminal plate DWB1151 are required for installation. Six M20x1.5 threaded cable entries are provided on the housing to feed in the cable. The DWA1151 electronics unit is only inserted after the wiring check during commissioning. 3

Radio test set DZW1171 The mobile radio test set DZW1171 enables the project manager to easily determine the exact propagation of the radio waves through the building. To ensure a safe project planning, i.e. the determination of radio gateway and radio smoke detector locations, we would recommend to carry out field strength measurements. Dimensions Radio Gateway DCW1151 65 135 Radio smoke detector DOW1171 with base DBW1171 Ø 119 135 73 6xM20 Ø 115 4

Technical data DOW1171 DCW1151 Transmitter/receiver antenna 2 (antenna diversity) 2 (antenna diversity) Radio frequency 868... 870 MHz (SRD band) 868... 870 MHz (SRD band) Channel width 25 khz 25 khz Transmitting power < 5 mw ERP < 5 mw ERP Transmission distance in the building in the open air max. 40 m max. 200 m max. 40 m max. 200 m Signal processing and monitoring max. 30 detector addresses Electromagnetic compatibility ETS 300 220 / 683 EN 50130-4 VdS (zone with increased danger, GSM) Supply 3 V/m 10 V/m 30 V/m two 9 V lithium brownstone batteries, separately monitored 3 V/m 10 V/m 30 V/m from detector bus, plus a 9 V lithium brownstone battery, monitored Battery service life min. 5 years min. 5 years Connection factor 1 to 7 detectors 8 to 30 detectors IMK = 8 / ITK = 1 IMK = 1 per detector + 1 / ITK = 1 Operating temperature -10... + 55 C -10... + 55 C Humidity (no condensation) 95% rel. 95% rel. Protection category (IEC60529) IP44 IP56 Color white, ~RAL 9010 white, ~RAL 9010 Standards EN54-7 EN54-17, EN54-18 5

Details for ordering Type Part no Designation Weight DOW1171/ S24218-F62-A5 Radio smoke detector complete with 0.330 kg DBW1171 base DBW1171 and two 9 V lithium brownstone batteries DOW1171 S24218-F62-A6 Radio smoke detector 0.170 kg DBW1171 S24218-F316-A1 Base 0.090 kg Base accessories DBZ1190 BPZ:4585260001 Detector locking device 0.001 kg DBZ1193A BPZ:4864330001 Designation plate (10x) 0.085 kg DBZ1192 BPZ:4588140001 Base attachment wet 0.265 kg DBZ1194 BPZ:4677110001 Protective cage 0.135 kg Gateway DCA1191 BPZ:4588560001 Housing 0.265 kg DWA1151 BPZ:5472200001 Electronics unit EP5 0.100 kg DWA1151-B A5Q00002905 Electronics unit EP7F 0.100 kg DWB1151 BPZ:5472330001 Terminal plate 0.095 kg DBZ1190-AA BPZ:4677080001 Micro terminal 0.28...0.5 mm 2, 4-pole 0.001 kg A5Q00004478 Metal screwed cable gland M20 x 1.5 0.035 kg Radio test set DZW1171 BPZ:5762200001 Radio test set 0.550 kg Battery A5Q00004142 Lithium brownstone battery 9 V / 1 Ah (1 Block) 0.035 kg Issued by Siemens Switzerland Ltd Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies Siemens Switzerland Ltd, 2015 Technical specifications and availability subject to change without notice. Dokument Nr. 001968_i_en_-- Manual S11 Ausgabe 2016-04-20 Section 5