CHAPTER A-6 FIRE PROTECTION

Similar documents
APPENDIX H (DESIGN SUBMISSION CRITERIA)

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

I. INTRODUCTION Codes, Rules, Laws, & Requirements

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

AUTOMATIC FIRE SPRINKLER SYSTEMS

ICC CODE CORNER 2012 IFC Code & Commentary

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

January 1, 2014 Mandatory Effective Date

Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours

UNIFIED FACILITIES CRITERIA (UFC)

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

FIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

BUILDING/FIRE CODE REFERENCES 2006 EDITION

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

PERFORMANCE COMPLIANCE METHODS

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

Narrative Reports As Regulated by 780 CMR, Section 903.0

UNIFIED FACILITIES GUIDE SPECIFICATIONS

American Fire Sprinkler Association. An Introduction to the IBC and IFC

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Page 1 of 5 1/29/2016 4:08 PM. First Correlating Revision No. 3-NFPA [ Section No ] Submitter Information Verification

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE


COMPLIANCE ALTERNATIVES

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

PLAN REVIEW CHECKLIST

Large Family Daycare Guideline

Plan Submittal Checklist

Fire Prevention Coffee Break Training. February 2017

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Florida Building Code 2010

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

WEST VIRGINIA UNIVERSITY

Center for Life Safety Education

FIRE PREVENTION AND PROTECTION*

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

FIRE AND SAFETY PROJECT REVIEW REPORT

PERFORMANCE COMPLIANCE METHODS

SAF-BCF SECOND REVISIONS WITH STATEMENTS

Design & Construction Standards, Revised January

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

PERFORMANCE COMPLIANCE METHODS

Report on First Revisions with Statement June 2014 NFPA 101

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

~ j~z~_ ~. Kirk Caldwell Mayor

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

ICC CODE CORNER 2015 International Fire Code

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

EC 5.10 FIRE PREVENTION MANAGEMENT

Chapter 2: Definitions

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

NFPA 45 NFPA 211 NFPA 1600

COMPLIANCE ALTERNATIVES

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

2012 International Fire Code Errata (Portions of text and tables not shown are unaffected by the errata)

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

CHAPTER 8 ELECTRICAL

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

El Reno Fire Department Fire Alarm Plan Review Worksheet

Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code

Distribution Restriction Statement

UNIFIED FACILITIES CRITERIA (UFC) FIRE PROTECTION ENGINEERING FOR FACILITIES

UNIFIED FACILITIES GUIDE SPECIFICATIONS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Agency for Health Care Administration

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

FIRE & LIFE SAFTEY STANDARD

1301: Fire protection systems.

UNIFIED FACILITIES CRITERIA (UFC) FIRE PROTECTION ENGINEERING FOR FACILITIES

FIRE PROTECTION ENGINEERING FOR FACILITIES

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B

Date Issued: December 14, 2017 Revision: 2.1

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

Impairments to Fire Protection Equipment

Pre-Bid Meeting Minutes 2018 A & E RFP February 6, :00 a.m.

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

Engineering and Design of Fire Alarm Systems

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

Design & Construction Standards, Revised January

Transcription:

CHAPTER A-6 FIRE PROTECTION 6.1 GENERAL 6.1.1 Scope 6.1.2 Purpose 6.1.3 Qualifications of Fire Prevention Engineer 6.1.4 Required Design 6.1.5 Critical Projects 6.2 APPLICABLE PUBLICATIONS 6.3 PRECONCEPT SUBMITTAL REQUIREMENTS 6.4 CODE 3 DESIGN REQUIREMENTS 6.5 CONCEPT/EARLY PRELIMINARY (35 PERCENT) DESIGN SUBMITTAL REQUIREMENTS 6.5.1 Concept/Early Preliminary Design Analysis 6.5.2 Concept/Early Preliminary Fire Prevention/Life Safety Drawing(s) 6.5.3 Concept/Early Preliminary Fire Prevention Engineer Certification 6.6 SIXTY PERCENT SUBMITTAL REQUIREMENTS 6.7 PRELIMINARY DESIGN SUBMITTAL REQUIREMENTS (FORMAL 60% SUBMITTAL) 6.8 FINAL (100 PERCENT) DESIGN SUBMITTAL REQUIREMENTS 6.8.1 Final Design Analysis 6.8.2 Final Fire Prevention/Life Safety Drawing(s) 6.8.3 Final Fire Prevention Engineer Certification 6.8.4 Final Specifications 6.9 CORRECTED FINAL DESIGN SUBMITTAL REQUIREMENTS 6.9.1 Notice 6.9.2 Compliance 6.10 REQUIREMENTS FOR DESIGN/BUILD RFP PACKAGES A-6-i

CHAPTER A-6 FIRE PROTECTION 6.1 GENERAL. 6.1.1 Scope. This chapter provides general guidance for the preparation and development of the Fire Prevention/Life Safety design. 6.1.2 Purpose. The purpose of Fire Protection design is to establish optimum safeguards against loss of life and property by fire that are consistent with the mission, the risk involved, and economic utilization. Fire Protection design shall be coordinated with the Architectural, Structural, Environmental, Electrical, and Mechanical sections. At a minimum, the design shall conform to the applicable standards contained in the current National Fire Code - published by the National Fire Protection Association (NFPA) - and other criteria referenced in paragraph 6.2, APPLICABLE PUBLICATIONS. In case of conflict between NFPA codes and other criteria referenced hereinafter, UFC 3-600-01 shall govern. The NFPA codes are not the final criteria for Fire Protection design unless the other referenced criteria so state, or those criteria do not address an issue. Unless otherwise noted, the designer shall use the most current version of the publications listed or referenced in this chapter as of the date of contract award. 6.1.3 Qualifications of Fire Prevention Engineer. The design of Fire Protection features shall be by a registered Professional Engineer or Registered Architect who is a full "Member" - in good standing - of the Society of Fire Protection Engineers (SFPE), or by an individual who is a registered Fire Protection Engineer and whose principle duties are Fire Prevention Engineering. The Fire Prevention Engineer shall certify in written form that the design complies with the NFC and other referenced codes and criteria as applicable to the project under design. The name and credentials (education and experience) of the Fire Prevention Engineer shall be submitted with the initial contract documents and approved by the District Fire Protection Engineer prior to issuance of the Notice To Proceed. 6.1.4 Required Design. A Fire Protection design is required and shall be included in every project. Sufficient copies of the design submittals shall be provided for submission to Architectural, Structural, Environmental, Electrical, Mechanical, and Energy Analysis Sections for review. 6.1.4.1 Design Analysis. A Fire Protection design analysis is required for every project and shall include the following: a. Type of construction, including interior finish materials (per IBC 2015). b. Classification of occupancy (per both IBC 2015 and NFPA 101). c. Building separation or exposure protection. A-6-1

d. Fire protection criteria. e. Location of all fire-rated walls including fire-rated doors and dampers with identification as to application (fire walls, fire partitions, and smoke partitions, with their fire resistive ratings). f. Life safety provisions (exit travel distances, exit unit widths based on the capacity and occupant load, horizontal exits, exit signs, and lighting). g. Automatic extinguishing systems (identification of all sprinklered areas and areas protected by other automatic suppression systems). h. Water supplies. i. The type and location of the backflow preventer assemblies for each service main (in accordance with the requirements of the water services provider). j. Smoke control system. (Smoke compartments and the requirements for smoke dampers, smoke detectors, and smoke partitions shall be provided. The smoke control system shall be delineated by schematic diagram, when applicable, indicating the operations of the normal HVAC mode and the smoke removal mode.) k. Fire alarm system (type of alarm system and location of the fire alarm equipment, and the fire zones.) l. Fire detection system (type of detection system and location of detectors, and fire zones.) m. Location of fire extinguisher cabinets and fire hose standpipes. n. Interior finish ratings. 6.1.4.2 Fire Prevention/Life Safety Drawing(s). 6.1.4.2.1 A separate Fire Prevention/Life Safety floor plan drawing(s) shall be submitted for all projects that are: a. Places of assembly, or b. Educational or institutional type facilities, or c. Commissaries or any other buildings exceeding 930 square meters (10,000 square feet) in gross area, or d. Three stories or greater above grade, or A-6-2

e. As required by the Specific Instructions. 6.1.4.2.2 Fire Prevention/Life Safety drawings are to be labeled as, For reference use only. A statement is to be made on the drawing explaining that it is not part of the construction contract, and that all information contained on it is called for elsewhere. Acceptable drawings shall show at least the following items of interest to Fire Protection/Life Safety personnel. a. Location and hourly rating of fire and smoke carriers (walls). b. Location of exit paths and the maximum travel distance of each. c. Fire hazard and occupancy classification. d. Building construction type as to its fire resistance capability. e. Exit units required and at each exit, the number of exit units available. f. Location of hand-held fire extinguisher and fire hose cabinets. g. Location and description of automatic sprinkler system. h. Location of building sprinkler entrance. i. Number of gpm per square foot by sprinkler system to each area. j. Location and notation of class of stand-pipe systems. k. Location of all smoke and fire detectors and a statement of their type. l. Location of manual pull boxes and audible/visual signaling devices. m. Description of any special fire protection features. 6.1.4.3 Fire Prevention Engineer's Credentials. A copy of the Fire Prevention Engineer's credentials and the approval provided by the Savannah District s Fire Protection Engineer shall be a part of each required fire protection submittal. 6.1.5 Critical Projects. Projects identified as "Critical Projects" shall have a complete, fully detailed design of all Fire Protection, Detection, and/or Life Safety Systems. Critical Projects include the following facilities: a. Medical facilities b. Aircraft maintenance and storage facilities A-6-3

c. Engine test cells/areas d. Missile assembly facilities/areas e. Ordinance facilities or exposed explosives areas f. Facilities which include significant data processing/telecommunications systems, as defined by UFC 3-600-01 g. POL facilities h. Flight simulators/computer based training facilities. i. Warehouses with high piled or high rack storage j. JSOC/SOTF facilities k. Mission-essential facilities l. Any facility occupied (during normal working or sleeping times) by 100 or more persons 6.2 APPLICABLE PUBLICATIONS. Designs shall be created using the most current version of applicable publications as of the date of contract award. UFC 1-200-01 General Building Requirements, (20 Jun 2016) UFC 3-230-01 Water Storage, Distribution, and Transmission, with Change 2 (1 July 2014) UFC 3-600-01 Fire Protection Engineering for Facilities, with Change 1 (1 Nov 2016) UFC 4-510-01 Design: Medical Military Facilities (1 May 2016) IBC International Building Code, 2015 NFPA ECB 2015-17 ETL 98-8 ETL 02-15 (With modifying criteria.) National Fire Codes (NFC) Changes to Reduce False Activations of High Expansion Foam Systems in Army Hangars (applies to Army facilities, only) Fire Protection Engineering Criteria - Existing Aircraft Facilities - U.S. Air Force, 25 Jun 1998 Fire Protection Engineering Criteria - New Aircraft Facilities - U.S. Air Force, 3 Dec 2002 (Applies to Air Force facilities, only. Contact AFCEC for relevant modifying criteria) A-6-4

6.3 PRECONCEPT SUBMITTAL REQUIREMENTS. No requirements for this section. 6.4 CODE 3 DESIGN REQUIREMENTS 6.4.1 Submittals. Submittal content and format shall be as described in UFC 3-710-01A, Technical Instructions for Code 3 Design with Parametric Estimating. 6.5 CONCEPT/EARLY PRELIMINARY (35 PERCENT) DESIGN SUBMITTAL REQUIREMENTS. 6.5.1 Concept/Early Preliminary Design Analysis. A consolidated submittal is required to include features of paragraph 6.1.4.1, Design Analysis. Submittals shall comply with the requirements of this chapter as well as chapters A-2, STRUCTURAL ; A-3, ARCHITECTURAL ; A-4, MECHANICAL ; A-5, ELECTRICAL ; A-7, ENERGY ANALYSIS (if necessary); and A-8, ENVIRONMENTAL. 6.5.2 Concept/Early Preliminary Fire Prevention/Life Safety Drawing(s). This drawing (if required) shall contain all the project features required in paragraph 6.1.4.2, Fire Prevention/Life Safety Drawing(s), for review. The drawing need not be in final form for this submittal; however, changes in content shall not be made except by the direction of Savannah District technical personnel through the Project Manager. 6.5.3 Concept/Early Preliminary Fire Prevention Engineer Certification. This submittal shall include written certification by the A-E's Fire Prevention Engineer that the design of the project meets all appropriate listed criteria. 6.6 SIXTY PERCENT SUBMITTAL REQUIREMENTS. 6.6.1 Sixty Percent Design Analysis. This shall be an updated version of the Concept/Early Preliminary Design Analysis incorporating review comments and design changes. 6.6.2 Sixty Percent Fire Prevention/Life Safety Drawing(s). This shall be an updated version of the Concept/Early Preliminary Fire Prevention/Life safety Drawing(s) incorporating review comments and design changes. 6.6.3 Sixty Percent Fire Prevention Engineer Certification. This submittal shall include written certification by the A-E's Fire Prevention Engineer that the design of the project meets all appropriate listed criteria. 6.7 PRELIMINARY DESIGN SUBMITTAL REQUIREMENTS (FORMAL 60% SUBMITTAL). 6.7.1 Preliminary (60 Percent) Design Analysis. This shall be an updated version of the Concept/Early Preliminary Design Analysis incorporating review comments and design changes. A-6-5

6.7.2 Preliminary (60 Percent) Fire Prevention/Life Safety Drawing(s). This shall be an updated version of the Concept/Early Preliminary Fire Prevention/Life safety Drawing(s) incorporating review comments and design changes. 6.7.3 Preliminary (60 Percent) Fire Prevention Engineer Certification. This submittal shall include written certification by the A-E's Fire Prevention Engineer that the design of the project meets all appropriate listed criteria. 6.8 FINAL (100 PERCENT) DESIGN SUBMITTAL REQUIREMENTS. 6.8.1 Final Design Analysis. The final Fire Protection design analysis shall be developed from the design analysis submitted with the concept submittal. It shall be an updated version, not an amendment to earlier work. It shall incorporate all Fire Protection requirements, calculations, analyses, determinations, etc. required by all technical sections and chapters of this handbook and shall accurately reflect the final project design. The submittal shall be logically separated into subsections relating to the various technical disciplines involved. 6.8.2 Final Fire Prevention/Life Safety Drawing(s). The final drawing(s) shall be complete and shall accurately reflect the final design features. 6.8.3 Final Fire Prevention Engineer Certification. The A-E's Fire Prevention Engineer shall certify the final design in written form. This is a separate certification from that required at the Concept submittal. The certification shall be included in the Fire Protection Design Analysis package. 6.8.4 Final Specifications. 6.8.4.1 Typed project specifications with electronic copy shall be submitted in accordance with chapter A-11, SPECIFICATIONS. 6.8.4.2 Specifications will not be restrictive. Generally, the description will be such that at least three manufacturers can meet the specified requirements. Do not use trade names in the specifications. 6.8.4.3 Specifications for fire suppression systems shall be CEGS adapted for the project. Components such as smoke detectors, heat actuated devices, and control panels for a Halon system shall be specified in the Fire Suppression specifications. 6.8.4.4 The subparagraphs on "Electrical Work" shall be carefully coordinated with the electrical section of the specifications. There shall be no conflicts as to which section covers starters, controls, or wiring, and no conflicts as to the type of starters required for the individual items of equipment. 6.9 CORRECTED FINAL DESIGN SUBMITTAL REQUIREMENTS. A-6-6

6.9.1 Notice. Corrected Final submittals are not considered a normal design level, and are required only when Final submittals must be revised or corrected due to error or omission. 6.9.2 Compliance. Comments affecting Fire Protection that are generated during the Final Design review shall be incorporated into the design analysis and drawing(s) in the Corrected Final submittal. Recertification by the Fire Prevention Engineer shall be required. 6.10 REQUIREMENTS FOR DESIGN/BUILD RFP PACKAGES. To be provided with specific instructions for the contract or delivery order. *** End of Section *** EXHIBITS There are no exhibits for this chapter. A-6-7