AQ475A Aquatrol Outdoor Temperature Compensator for Boilers

Similar documents
Aquatrol Outdoor Temperature Compensators AQ675A for Floating Control Valves AQ775A for Injection Pumps

T7079A,B Solid State Remote Temperature Controllers

T6984F,G Electronic Floating Control Thermostats

C554A Cadmium Sulfide Flame Detector

M6063A Compact Rotary Mixing Valve Actuator

RA889A Switching Relay

The T6140A,B Remote Bulb Temperature Controller

AQ250 Series Hydronic Control Panels

T4098A,B Deluxe Electric Heat Thermostats

T6984 A,D,E Electronic Floating Control Thermostats

T4398A,B High Performance Electric Heat Thermostats

T7984 A,B,C Electronic Modulating Control Thermostats

C6097A,B Pressure Switches

qualified heating installer/service technician

CR7075 Two-Stage Lighting Controller

Commercial/Industrial Combustion Control Level Three Announcement

- Data Brochure D 260. Boiler Control /09

L8151A Triple Aquastat Relay

L8005A,B; LS8005A,C,D Electronic Pool and Spa Controllers

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

Solid Core and Split Core Fixed Current Status Switches CSS-O,C; CSP-O,C -F (FIXED) SERIES

WWSD. Power. DHW Demand. Maximum. Supply. Minimum Boiler DHW. Zone 1 / Cooling. Pump / Vlv. System Pump. UnOccupied. of full output NRTL/C LR 58223

- Data Brochure Mixing Control 361

C7031D,G,J C7041B,C,D,F,J,K,P,R Series 2000 Electronic Temperature Sensors

SC-3 Controller INSTALLATION AND OPERATING INSTRUCTIONS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS. SC-3 Applications CONTENTS

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA

- Data Brochure Mixing Control 360

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

H1008A,D Automatic Humidity Controls

Outdoor Reset IQ Option Card, p/n

- Data Brochure Steam Control 279

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

Outdoor Reset IQ Option Card, p/n

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 423

SC-9 Controller INSTALLATION AND OPERATING INSTRUCTIONS. SC-9 Applications CONTENTS

Instruction manual. WMCR-2, WMCR-3, WMCR-4 and WMCR-6 Circulator Zone Controllers WMCR-1E and WMCR-4E Expansion Modules

T8011R Programmable Heat Pump Thermostat

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand

Aquastats. Aquatrol Indoor/Outdoor Control. Automatic Changeover Switch 16/05/08

AQ252 Universal Injection/Mixing Boiler Reset Control Panels

- Data Brochure Addendum

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats XE88/XE100 SERIES

- Data Brochure Boiler Control 264e

T834C Heating-Cooling Thermostat

T874 Multistage Thermostat and Q674 Subbase

- Data Brochure Boiler Control 264

B-40/B-41 Modulating Temperature Controller

- Data Brochure Addendum

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

Solid Core and Split Core 4-20 ma Output Current Sensors CTS-20; CTP-20

F150E Media Air Cleaner

Radiant Mixing Block

AQ255 and AQ257 Series Expansion Zoning Panels

- Data Brochure Mixing Control 360e

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

- Data Brochure Boiler Control 268

Q7800H Integrated Burner Control Subpanel

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

- Data Brochure Boiler Control 274

RA889A Switching Relay

T8411R Electronic Heat Pump Thermostat

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

- Essay Control Functions and Benefits

F200E Charged-Media Air Cleaner

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

- Data Brochure Universal Reset Control 364

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

F25F Media Air Cleaner

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

Product Number L4006A1017 L4006A1132 L4006A1967 L4006A2007 L4006B1007 L4006B1155 L4006B1163 3/4 (19) L4006H1004

Energy Manager INSTALLATION INSTRUCTIONS. Keep these instructions with the boiler at all times for future reference

L Honeywell. L4068 has spst switch; L6068 has spdt switch. L4068A,C,E,F have adjustable FAN OFF and differential settings.

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

Installation & Operation Manual

The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and efficiency provided by a hydronic

Instruction Sheet 00 Variable Speed Delta T (00-VDT)

ARM SERIES Switching Relays With Priority

Installation & Operation Manual

T4398A,B Precision Electric Heating Thermostat

Installation & Operation Manual

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING

ARGO DPM-2 OUTDOOR TEMPERATURE SETBACK CONTROL

ProRadiant Basic Heating Control Installation Manual 2013

T8112 Programmable Thermostat

Advanced Snow Melt Control Installation Manual

BB3000 Series. Application. Features. Injection Pump Control General Instructions

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

prestige Control Application Supplement - Type 5 MCBA WARNING

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats

C7232A,B Sensor and Controller

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

prestige Control Application Supplement - Type 5 MCBA WARNING

Deluxe Programmable Heat Pump Thermostat T8611M

c0094 form 2. Project Identification Year: 2001 Project nº: 910

Transcription:

A Aquatrol Temperature Compensator for s Features PRODUCT DATA Adjustable settings for boiler maximum temperature, boiler minimum temperature and outdoor low (design) temperature. Selectable Warm Weather Shut Down () at 70 F ( C) to prevent summer boiler operation. Domestic Hot Water () priority. Replaceable circulator relay common to other Honeywell replacement controls. and outdoor sensors included. Automatic boiler operating differential. Automatic system circulator exercising. Long-life DC relay drive control technology. Troubleshooting LEDs. Push-to-test button. Full size screw terminals. Functional replacement for Honeywell T475A Reset Controller and W964F Aquatrol (on-off mode). Application The A Aquatrol Temperature Compensator automatically regulates boiler water temperature to provide outdoor reset. The Priority option operates the boiler at the aximum Temperature setting to heat domestic hot water and can operate or shut down the system circulator. The boiler High Limit safety function must still be provided by the boiler manufacturer s high limit. Contents Application... Features... Specifications... Ordering Information... Installation... Wiring... Settings... 4 Operation... 7 Checkout and Test... 8 Troubleshooting... 8 Copyright 999 Honeywell Inc All Rights Reserved 68-07-

A AQUATROL TEPERATURE COPENSATOR FOR S SPECIFICATIONS ORDER INFORATION Specifications Important The specifications given in this publication do not include normal manufacturing tolerances; therefore, an individual unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed. odel: The A Aquatrol Temperature Compensator automatically cycles the boiler to regulate heating supply water temperature using an outdoor reset curve. The A includes a supply and outdoor sensor, tie-clamp, mounting bracket and wire-nuts. Electrical Ratings: L-L Power : 0 Vac,60 Hz, 00 VA. C-C Output: 0 Vac, 0 A; / hp (7.4 AFL, ` 44.4 ALR); 40 VA pilot duty powered contact. T-T Output: 4 to 0 Vac,.7 AFL,. ALR maximum; 40 VA pilot duty, isolated (dry) contact. Demand input opto-isolated: 4 to 40 Vac. R-W Thermostat input: Dry contacts from thermostat or end switches; 4 Vac, 0.0 A. Temperature Control Ranges: () aximum: 0 F to 5 F (50 C to 07 C). Low (Design): 50 F to 0 F ( 46 C to C). inimum:, 80 F to 80 F (, 7 C to 8 C). Temperature Ratings: Control: F to F (0 C to 50 C). s: -50 F to 55 F (-45 C to 5 C). Humidity Ratings: Less than 90% RH, non-condensing. Electrical Connections: No. 6 wire clamp screw terminals. and s: 0 kω @ 77 F (5 C), NTC ±%, beta = 950. Lead Length: 4 in. (067 mm). Approvals: Canadian Standards Association C/US Certified, LR: 959- Dimensions: See Fig.. Cross Reference: Functionally replaces Honeywell T475A Reset Controller and W964F Aquatrol configured in on-off mode. Thermostat Compatibility: Contemporary Honeywell electromechanical and electronic -wire thermostats. Replacement Parts: 0090-00 Replacement Relay. 0000-00 or. Fig. A Approx. mounting dimensions in inches (mm) Fig.. Dimensions in inches (mm) -5/ (9) 7/ (6) Diameter ounting Hole 5/ (0) /() -/8 (5) -/ (89) 4-/4 (08) / () Diameter Diameter -7/8 (48) 7/8 () Diameter Keyhole Type ounting Hole /8 (0) -7/8 (48) 4-/ (4) /8 (0) -5/6 (75) Knockout for / () Conduit () 5-/4 () Ordering Information When purchasing replacement or modernization products from your wholesaler or distributor, refer to the price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:. Your local Home and Building Control Sales Office (check white pages of your phone directory.). Home and Building Control Customer Logistics Honeywell Inc. 885 Douglas Drive North inneapolis, innesota 554-486 (6) 95-000 In Canada - Honeywell Limited/HoneywellLimitée, 55 Gordon Baker Road, North York, Ontario H N7. -800-565-68 International Sales and Service Offices in all principal cities of the world. anufacturing in Australia, Canada, Finland, France, Germany, Japan, exico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. 68-07-

A AQUATROL TEPERATURE COPENSATOR FOR S INSTALLATION Installation When Installing this Product. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.. Installer must be a trained, experienced service technician. 4. After installation is complete, check out product operation as provided in these instructions. 5. Follow local codes for installation and application. Wiring Control ounting To mount the A control:.position the control on the wall at the selected location and mark the mounting holes. See Fig... Start a screw in the upper right corner for the keyhole type mounting hole. Screw it down within about /8 in. ( mm) of the surface, or until the keyhole slot slides tightly on the screw.. Hang the control on the keyhole screw, position the case, and install the bottom screw. Locate the sensor: in a shady location out of direct sunlight. at least three feet from dryer, bathroom, or other vents. above the expected snow line where ice and debris cannot cover it. on the North side of the house. See Fig. for typical placement.! Caution Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. Fig.. sensor mounting location All wiring must comply with applicable local codes, ordinances and regulations. Refer to Fig. through 9 for typical mechanical, wiring diagrams for the A. Route wiring away from LEDs to avoid pinching wires under the bezel when reinstalling the cover Important Use a maximum of 4 AWG wire for wiring terminals. All wiring must be rated for 00 V. Important Do not run sensor wires parallel or close to telephone or power cables. Cross all power and telephone wiring at right angles. If sensor wires are located in an area with strong sources of electromagnetic interference, use twisted pair, shielded cable, or run wires in a grounded metal conduit. When using shielded cable or conduit, connect the shield wire to earth ground ONLY at the A panel. DO NOT connect the shield (or conduit if used as a shield) to earth ground at any other location or electromagnetic shielding will be ineffective. Connect 8 AWG (or larger) wire to the two sensor wires using the wire nuts provided. Wiring must be rated for 00 V. Location Control Locate the A on a panel or wall near the equipment to be controlled. ake sure the location is accessible for installation and service and that the ambient temperature at the selected location does not exceed 0 F (50 C). To mount the outdoor sensor:. Place the sensor in the plastic mounting clamp provided.. Insert the screw provided through the hole in the mounting clamp and fasten the sensor in place.. Run an extension wire from the sensor lead wires to the control. Insulate all connections and strain relief wires. 68-07-

A AQUATROL TEPERATURE COPENSATOR FOR S Location cont d The ideal supply sensor mounting location is in a well in the boiler shell. The supply sensor may also be mounted on the main supply pipe as follows:. ount the sensor feet ( m) downstream from the main or primary circulator to ensure adequate water mixing. If the circulator is on the boiler return, mount the sensor after the first elbow away from the boiler supply outlet.. Secure the sensor with the tie-wrap (included).. Wrap the sensor with insulation and secure with high quality electrical or duct tape. Settings Reset Curve It is not necessary to calculate the reset curve, the A calculates this automatically. To adjust it:. Set the Low dial to the coldest actual winter temperature (design temperature, available from your local weather service).. Set the aximum Temperature dial to the maximum for the desired heating supply water temperature (refer to manufacturer and industry recommendations for heating distribution, see Table ). Table. Typical Aquatrol settings for Heating Distribution Systems. Distribution Type Radiation Type aximum Temperature Direct Fan Coil Low Temperature Free-standing Radiator Baseboard Convector Heating Only Heating/Cooling Floor Radiant Ceiling Radiant 70-90 F (75-85 C) 80-00 F (80-90 C) 50-80 F (65-80 C) 0-40 F (50-60 C) 90-0 F (-4 C) 0-40 F (45-60 C) The values of these two settings determine the maximum operating point for the heating system based on an as sumed balance point of 7 F ( C) for both supply water temperature and outdoor temperature. The reset curve will be overriden by either the inimum Temperature setting or the Demand input, which ever is active. If the outdoor temperature falls below the Low setting, the boiler operating temperature is limited to 0 F (5.5 C) above the aximum Temperature setting. Fig. 4. Typical mechanical, wiring hookups for A with multiple zones, and domestic hot water valve. Fig.. Typical mechanical, wiring hookups for A with one zone, no domestic hot water. A. ECHANICAL T-T Thermostat A. ECHANICAL T - T Aquastat and Valve, E E E Thermostats C-C C-C ON DE ON DE ZONE VALVE VALVE END SWITCHES E... E E E 4 Vac L L (HOT) L L (HOT) ULATOR Power supply. Provide disconnect means and overload protection as required. Power supply. Provide disconnect ULATOR means and overload protection as required. Anticipator Current 0.A Anticipator Current 0.A 68-07- 4

A AQUATROL TEPERATURE COPENSATOR FOR S Notes: are a potential burn hazard if the exposed surface temperature is allowed to exceed 40 F (60 C). Discomfort results if radiant floor heating surface termperature is above 87 F ( C). Building materials can also be damaged at high temperatures. Thermostat Anticipator Thermostat anticipator settings are based on the rate of temperature rise in the space. The hotter the supply water, the faster the thermostat needs to cycle to maintain accurate temperature control. The A Aquatrol supplies water just hot enough to heat the space, except when overridden by Demand input or the inimum setting. If neither feature is used, (re)set the electromechanical thermostat anticipator to longest and the electronic thermostat cycle rate to the lowest setting to prevent system short cycling. Thermostatic Radiator (TRVs) If the A is used with non-electric room controls such as thermostatic radiator valves, jumper the R-W thermostat input to simulate a constant call for heat; the TRVs will trim the space temperature for each zone. Fig. 6. Typical mechanical, wiring hookups for A, R8889 Hydronic Valve Panel with priority. A. ECHANICAL T - T C-C E E4 E E ON DE Aquastat and Valve Fig. 5. Typical mechanical, wiring hookups for A with multiple zones, domestic hot water circulator with priority. A. ECHANICAL Aquastat Pump and Check Valve T - T E E Thermostats L L (HOT) C-C Check Valve ULATOR VALVE END SWITCHES E... E E DE ON ULATOR L L (HOT) TDR PUP N L ZONE ZONE THEROSTAT ZONE THEROSTAT ZONE 4 THEROSTAT R- R-4 C A B C R8889 ENABLE BURNER CONTROL ON VALVE VALVE VALVE VALVE 4 L L H H ES ES V V ES ES V V ES ES V V ES ES V V E E E4 E Power supply. Provide disconnect means and overload protection as required. e5 Power supply. Provide disconnect means and overload protection as required. Anticipator Current 0.A 0 0 minute time delay optional to limit priority over space heating 5 Slide PriorityEnable switch to ON for priority. 68-07-

A AQUATROL TEPERATURE COPENSATOR FOR S Fig. 7. Typical mechanical, wiring hookups for A, circulator with priority, R8889 Hydronic Valve Panel. Fig. 8. Typical mechanical, wiring hookups for A, R8888 Hydronic Panel with priority. A. ECHANICAL E A. ECHANICAL Thermostats Aquastat, Pump and Check Valve T-T E E T-T, PUP AND CHECK VALVE C-C Check Valve s Check ON DE TDR ON DE PUP TDR L L (HOT) N L L L (HOT) N L ULATOR R8889 R8888 L L R C L L R- R-4 C ZONE THEROSTAT ZONE THEROSTAT ZONE THEROSTAT A B C ENABLE BURNER CONTROL ON VALVE VALVE VALVE H H ES ES V V ES ES V V ES ES V V E E E ZONE THEROSTAT ZONE THEROSTAT A B C BURNER CONTROL ZONE ON ENABLE ZONE ZONE L ZC H H C C C C C C PUP ULATOR ULATOR Power supply. Provide disconnect means and overload protection as required. Set switch to to disable main circulator for priority. 0 0 minute time delay optional to limit priority over space heating. ZONE 4 THEROSTAT ZONE 4 C C ULATOR 4 Power supply. Provide disconnect means and overload protection as required. Slide Priority Enable switch to ON for priority 68-07- 6

A AQUATROL TEPERATURE COPENSATOR FOR S Fig. 9. Typical wiring hookups for replacing T475A Reset Controller, or W964F Aquatrol Reset Controller configured for on-off control. L T475A inimum Temperature minimum temperature control is activated when the inimum Temperature dial is not set to. Determine the setting based on the boiler manufacturer recommendations. This operation is only active when there is a call for heat from the space thermostat. Notes: To prevent condensation of flue gases, do not set the inimum Temperature dial lower than the manufacturer s recommendation. It is important that the supply sensor accurately reflects boiler temperature. See the ounting section,. The A inimum Temperature setting does NOT replace the low limit function of a Triple Aquastat Control. ake sure that the inimum Temperature setting is less than the aximum Temperature setting or reset control will be disabled. Burner Differential D C W964F B A T T T T 0 V 60 Hz 4 Vac ON- ode TO BURNER Jumper 4 L L 4 L TO BURNER T T A Power supply. Provide disconnect means and overload protection as required. W964F power supply may be 0Vac or 4Vac depending on model. A requires 0V 60Hz. Burner contact may be line or low voltage. A has isolated contacts for compatibility with either style. Replace sensors and reuse wiring. The A automatically calculates the best operating differential for the boiler. No installer setting is necessary or supplied. Warm Weather Shut Down () Slide the slide switch to ON to activate warm weather shut down. When selected, the boiler will not turn on for a heat call if the outdoor temperature is above 70 F ( C). The boiler only responds to Demand in warm weather. 7 Domestic Hot Water Priority () ing 4 to 40 Vac power to the Demand input sets the boiler control point to the aximum Temperature setting until the call is satisfied. If has its own circulator and requires absolute priority over space heating, set the switch to PUP to disable the main circulator during a call for domestic hot water. If is controlled by a zone valve, set the switch to VALVE. Note: If domestic hot water has priority over heating, space temperature will not be maintained while there is a call. To maintain comfort level in the event of failure use a normally- closed 0 to 0 minute time-delay-on relay in series with the input to limit the operation of. See Fig. 5 for a typical wiring diagram. Night Setback Night setback control may be added to the system using a programmable thermostat. To minimize thermal stresses in the system during recovery periods, use a thermostat with a gradual warm-up, such as the Honeywell Chronotherm III or Chronotherm IV thermostat with the Adaptive Intelligent Recovery feature. Because the outdoor temperature compensator accurately calculates the heat required based on the outdoor temperature, allow at least two hours for recovery to the desired comfort temperature. Note: The recovery time needed for high mass systems, such as thick slab radiant floor heating, is too long to make night setback practical. OPERATION The thermostat R-W heat input provides 0.0A at 4 Vac for power stealing thermostats or thermostats with heat anticipators. If the thermostat anticipator cannot be set lower than 0.5A, replace the thermostat or install a R8845U Universal Switching Relay to power the thermostat. If using a zone control relay box, use an isolated end switch to create the call for heat. The Demand input requires 4 to 40 Vac from either a zone control relay box, zone valve, or Aquastat Control. If using a relay box, the signal is provided from the zone output terminals and is typically 4 Vac. The circulator output is 0V switched from the power supply of the Aquatrol. The T-T boiler Aquatrol control output is an isolated and unpowered (dry) relay contact closure rated up to 0 Vac. Note:The A performs the function of an operating (non-limit) Aquastat Control. For consistent operation, set the existing operating control on the boiler to its highest setpoint if the boiler is started by zone thermostat(s) or zone valve end switches. If the existing boiler is not integrated to space temperature demand, for example, if the boiler runs at constant temperature and the thermostats control the circulators, set the operating control to its lowest setpoint and wire the A T-T outputs in parallel. /Domestic Hot Water () Demand On a call for heat, the thermostat, zone valve end switch, or zone panel closes the R-W input. The circulator relay turns on if the system is not in. The T-T boiler Aquastat Control output contact makes to start the burner until the supply sensor is satisfied according to the calculated reset curve. 4 to 40 Vac supplied to the Demand input forces the A to control the boiler at the aximum cont d 68-07-

A AQUATROL TEPERATURE COPENSATOR FOR S Heat/Domestic Hot Water () Demand cont d Temperature setting, and either turns the system circulator on (if the switch is set to VALVE), or off (if the switch is set to PUP). does not allow the circulator or the boiler to run, even when a call for heat (R-W) is present. is enabled with a slide switch and occurs whenever the outdoor air temperature is warmer than 70 F ( C). The LED turns on when it is selected and the outdoor temperature is warmer than 70 F ( C). If a call for heat is made during, the LED also turns on. While in, if a Demand occurs, the boiler operates at the aximum Temperature setting until the demand is satisfied. Operation The reset ratio is determined by the adjustments Low, aximum Temperature, inimum Temperature and a preset outdoor high temperature of 7 F ( C). Once a call for heat is present, the control operates the boiler to reset the supply water temperature to a lower value that corresponds to the observed outdoor air temperature. When a Demand is present, the control operates the boiler at the temperature set by the aximum Temperature dial. The minimum boiler operating temperature is equal to the inimum Temperature setting. During the summer months, if the is turned off and a call for heat is present, the control operates the boiler at the inimum Temperature setting. When a thermostat call for heat ends, the circulator runs for ten seconds to remove excess heat from the boiler. Note: Factory supplied boiler controls can also energize the boiler independently from the A. The boiler switching differential is automatically determined by the auto differential algorithm to optimize boiler cycling frequency. Exercising If the circulator has not been operated in the past 7 hours, the A turns on the C-C output for ten seconds to reduce the chance of circulator seizure during the summer months. LED Operation Power/Test ON when power on to Compensator. FLASHES during TEST mode. (Summer Off) ON when Temperature is above 70 F ( C). FLASHES if either supply or outdoor sensor fails. (Thermostat On) ON when R-W input is shorted. FLASHES if supply sensor fails or if control fails self-test. Dem. (Hot Water On) ON when there is a demand for domestic hot water. FLASHES if control fails self-test. ON when power supplied to circulator(s). ON when T-T output made. CHECKOUT AND TEST! Caution Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect all power supplies before installation. Press the Test button as follows to cycle the control through the test routine: First press Control enters the test mode and Power/Test LED flashes. Second press relay turns on. Third press relay turns on. Fourth press and boiler relays turn off and control exits the test routine. NOTE: If the Test button is not pressed for five minutes during the test mode, the control automatically resumes normal operation. Troubleshooting Error Results Action fails (open or short circuit). fails (open or short circuit). Self-test sequence error. The control continues to operate assuming the outdoor temperature is F (0 C) and the LED flashes. Space temperature may be too hot or too cold depending on outdoor temperature. The control turns on the circulator relay and boiler for up to 50% of a 0-minute cycle depending on the thermostat setting and Demand. Both the and LEDs flash. Temperature may be too hot or too cold depending on outdoor temperature. The control attempts to operate normally. Both the and Call for Heat LEDs flash. Check wiring for open or short circuit; if wiring is okay, replace the outdoor sensor. Check wiring for open or short circuit; if wiring is okay, replace the supply sensor. Replace the control. Home and Building Control Honeywell Inc. 985 Douglas Drive North Golden Valley, N 554 Honeywell Limited - Honeywell Limitée 55 Gordon Baker Road Toronto, ON H N7 68-07- RJ 7/99 Printed in U.S.A. www.honeywell.com