DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

Similar documents
University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Western Michigan University Facilities Management Engineering Division

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

A. This section includes design and performance information for fire protection and suppression systems.

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

Worldwide Contacts.

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

Linear Heat Detection Engineering Specifications

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

Box-in-Box Cold Storage Fire Protection Options

SECTION WET-PIPE SPRINKLER SYSTEMS

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

FIRE SUPPRESSION SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Gas Station & C Store SECTION CWM Job No

ADDENDUM NO. 3 March 19, 2018

Port of St Helens SIA Aircraft Hanger Scappoose, OR

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

Sprinkler Solutions for Storage Applications

2. Welding Materials and Procedures shall conform to the ASME Code.

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

CONSTRUCTION REQUIREMENTS

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

SECTION DRY-PIPE SPRINKLER SYSTEMS

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

Deluge & Preac tion Systems

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

FM-200 In-Cabinet Series

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Technical Data. Installation

SECTION FM-200 FIRE SUPPRESSION SYSTEM

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

DONALD H. BERG, ARCHITECT

SECTION DRY-PIPE SPRINKLER SYSTEMS

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION Fire Pumps

DIVISION 21 FIRE SUPPRESSION

Design & Construction Standards, Revised January

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

SPECIFICATION: ARGONITE Engineered Fire Suppression System

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

D. Reference Standards (Utilize latest editions available):

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

1.3 REFERENCE STANDARDS

SPRINKLERS TABLE OF CONTENTS

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SECTION FIRE-SUPPRESSION STANDPIPES

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

TOTALPAC2 Integrated Fire Protection System

APPENDIX H (DESIGN SUBMISSION CRITERIA)

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

Fire Protection Systems

FIRE PROTECTION BASIC MATERIALS AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

SECTION : FIRE PROTECTION SYSTEMS

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

Simple On The Outside...

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

DIVISION 21 - FIRE SUPPRESSION

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Transcription:

PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned Group A Plastics Commodity, up to 9.1 m of single, double or multiple row rack storage, up to 10.7 m of building height (VanQuish Fire Sprinkler System). 1. The VanQuish fire protection system for cold storage and/or unheated warehouses shall be designed and installed by a Quell Licensee sprinkler contractor based upon section 2.2(A) or (B) of this specification, taking into consideration the information contained in Tyco Fire & Building Products (TF&BP) Technical Data Sheet #372. 2. The fire sprinkler system shall utilize a Tyco double interlock pre-action dry system components with Tyco Ultra K-16.8 (K24.2 litre/kpa) 141 c sprinklers, all as manufactured by TF&BP. The contractor shall be responsible for complete working systems throughout the facility. All equipment is to be U.L Listed and/or Factory Mutual approved for the intended use. The fire sprinkler system shall be hydraulically calculated, and water delivery times for each pre-action system shall be verified by the contractor using SprinkFDT Q software as applicable. The system design including shop drawings, calculations, equipment drawings, and water delivery calculations shall be submitted to the owner, his insurance company, and all local authorities having jurisdiction for approval prior to the commencement and completion of installation. All drawings, hydraulic calculations, and water delivery calculations shall be revised for the actual as-built system and shall be submitted to the owner or the owner s representative following installation of the system(s). 1.2 QUALIFICATIONS A. Installation of the entire sprinkler system is to be performed by a vanquish Licensee sprinkler contractor with a minimum of five years of design and installation experience with sprinkler system installations in cold and unheated warehousing similar to the one specified under this contract. Evidence of such experience must be submitted with the bid for this project. If such information is lacking or incomplete, the owner and/or the owner s representative reserve the right to refuse to accept said contractor(s) quotation for the project. B. The preparation of the sprinkler shop drawings is to be performed by, or be under the direct supervision of the vanquish Licensee with at least ten (10) years of experience in Automatic Sprinkler System Layout and Design, with specific design experience in cold storage applications. Evidence of such experience must be submitted with the bid for this project. C. A Quality Assurance check of the completed installation shall be performed by an independent registered professional engineer. Evidence of such experience must be submitted with the bid for this project. The finished installation is to be compared to the sprinkler contractor s design drawings for completeness and 1

correctness. The shop drawings, hydraulic calculations and water delivery calculations shall be amended and re-submitted to the owner s representative to document the as built conditions. The revised hydraulic and water delivery calculations will confirm the ability of the installed system to meet the required system performance. Should the revision result in unacceptable performance, the sprinkler contractor will be responsible for all required modifications to correct the performance at said contractor s expense. Substitution of material or equipment for previously submitted materials required by this specification will not be accepted, and all costs associated with the removal and replacement will be at the sprinkler contractor s expense. The individual certifying the system shall sign the contractor(s) material and test certificate. D. The Fire Detection contractor shall be or be represented by an authorized representative of Safe Fire Detection, Inc. (SAFE) for the design and installation of linear heat detection components required by section 2.2C2. Person must have successfully completed SAFE s technical training seminar and show proof of same by means of a Safe Detection issued certification. The individual(s) listed on the certificate must be employed by the company and be present at the time of the testing and commissioning or the certification is invalid. The certification is valid for a period of two years from the date of issuance shown on the certificate. PART 2 - DESIGN CONSIDERATIONS, SYSTEM COMPONENTS AND HARDWARE 2.1 GENERAL A. All materials and devices essential to successful system operation shall be UL Listed and/or FM Approved. Within this specification, listed shall mean UL Listed or FM Approved. B. The installing sprinkler contractor shall submit data sheets for all intended materials and equipment. Such information shall include but not be limited to sprinklers, valves, valve trim, pipe, fittings, and all other items that are incorporated into the fire sprinkler system(s). Materials purchased by the sprinkler contractor prior to receiving all required approvals and authorization will be done at said contractor s risk. C. The installing sprinkler contractor shall install all sprinklers, pipe, fittings, and other equipment in accordance with the material submission. Substitution of alternate products or materials for previously submitted and approved items will not be accepted. D. The use of anti-freeze in the fire sprinkler systems is not permitted. 2.2 DESIGN CONSIDERATIONS A. Cartoned Group A Plastic Commodity, up to 9.1 m (30ft) of single, double or multiple row rack storage, up to 10.7 m (35ft) building height (VanQuish Fire Sprinkler System). 1. A VanQuish Fire Sprinkler System utilizing performance based design shall be furnished and incorporate the following: 2

a. The system shall be in accordance with TF&BP Technical Data Sheet #372 including minimum water delivery time for the 4 least hydraulically remote sprinklers, and maximum water delivery time for the 4 most hydraulically remote sprinklers. TF&BP Technical Data Sheet #372 also includes requirements for sequential operation of the first, second, third, and fourth most hydraulically remote and least hydraulically remote sprinklers. b. Guidance on design number of sprinklers: i. Utilization of Underwriters Laboratories Fire Performance Evaluation of Dry-pipe Sprinkler Systems for Protection of Class I, II, III and Group A Plastic Commodities Using K-16.8 Sprinkler Project 06NK05814, EX 4991), Fire Performance Evaluation of Dry-pipe Sprinkler Systems for Protection of Group A Unexpanded Plastic Commodity Using K-16.8 Sprinkler Project 06NK25135, EX 4991and guidance provided by TF&BP Technical Data Sheet #370. ii. Accurate water delivery times for the VanQuish design require the utilization of SprinkFDT Q (Fluid Delivery Time VanQuish ) software. This software is capable of calculating the required minimum water delivery of the 4 least hydraulically remote sprinklers and maximum water delivery of the 4 most hydraulically remote sprinklers. This software can also calculate the required sequential sprinkler operation of the first, second, third, and fourth least hydraulically remote and most hydraulically remote sprinklers. Such calculations shall be submitted for review and approval as a part of the sprinkler shop drawing and equipment submittal package B. Class I,II & III Commodity, up to 12.2 m (40ft) of single, double or multiple row rack storage, up to 14.6m (48ft) building height (VanQuish Fire Sprinkler System). 1. A VanQuish Fire Sprinkler System utilizing performance based design shall be furnished and incorporate the following: a. The system shall be in accordance with TF&BP Technical Data Sheet #372 including minimum water delivery time for the 4 least hydraulically remote sprinklers, and maximum water delivery time for the 4 most hydraulically remote sprinklers. TF&BP Technical Data Sheet #372 also includes requirements for sequential operation of the first, second, third, and fourth most hydraulically remote and least hydraulically remote sprinklers. b. Guidance on design number of sprinklers: i. Utilization of Underwriters Laboratories Fire Performance Evaluation of Dry-pipe Sprinkler Systems for Protection of Class II, III and Group A Plastic Commodities Using K-16.8 Sprinkler Project 06NK05814, EX 4991), Fire Performance Evaluation of Dry-pipe Sprinkler Systems with 12.2m (40 ft) of Class III Commodity Stored Under a 14.6m (48 ft) Ceiling 3

ii. Using K-16.8 Sprinkler Project 06NK23629, EX 4991and guidance provided by TF&BP Technical Data Sheet #370. Accurate water delivery times for the VanQuish Fire Sprinkler System design require the utilization of SprinkFDT Q (Fluid Delivery Time VanQuish ) software. This software is capable of calculating the required minimum water delivery of the 4 least hydraulically remote sprinklers and maximum water delivery of the 4 most hydraulically remote sprinklers. This software can also calculate the required sequential sprinkler operation of the first, second, third, and fourth least hydraulically remote and most hydraulically remote sprinklers. Such calculations shall be submitted for review and approval as a part of the sprinkler shop drawing and equipment submittal package. C. Fire Detection in areas protected by the VanQuish Fire Sprinkler System shall be furnished and incorporated in the following manner: 1. Fire Detection shall be arranged such that during a fire event the fire detection shall occur prior to sprinkler operation. 2. Linear heat detection manufactured by SAFE shall be installed on each pipe fitted with sprinklers in accordance with the manufacturers recommended installation instructions and the guidance provided by TF&BP in Technical Data Sheet #372. a. Guidance on placement and location of linear heat detection: i. Utilization of Underwriters Laboratories Fire Performance Evaluation of Dry-Pipe Sprinkler Systems with 12.2m (40 ft) of Class III Commodity Stored Under a 14.6m (48 ft) Ceiling Using K-16.8 Sprinklers Project 06NK23629 EX4991. 2.3 AUTOMATIC SPRINKLERS 1. Automatic sprinklers shall be warranted by the manufacturer for ten (10) years against defects in material and workmanship. B. Automatic Sprinklers used for the Protection of Refrigerated Warehousing 1. Tyco Ultra K17 (16.8 K-factor) Upright, Standard Response, 141 C / 286 F. (TY7153) 2. Sprinklers installed in areas not subject to cold storage/unheated warehousing shall meet the requirements as set forth in NFPA 13-2007, and shall be Tyco appropriate model sprinkler(s). 2.4 ABOVEGROUND PIPING AND FITTINGS 4

1. Grooved fittings and couplings shall be warranted by the manufacturer for ten (10) years against defects in material and workmanship B. Steel Sprinkler Piping and Fittings 1. Sprinkler pipe shall be at least equivalent to medium steel tube complying with the requirements of a) AS1074, b) AS1579, subject to minimum thickness of 4.76mm; or c) AS4041 and shall be UL listed and FM approved or SSL Listed for fire protection service. Refer AS4118.2.1 and AS2118.9. Dry system piping shall be hot-dip galvanized and shall comply with the requirements of AS1670 (see AS2118.9). Conduit shall be Schedule-10 and/or Schedule-40 sprinkler pipe. 2. Grooved mechanical pipe couplings and fittings shall be cast iron, class 125, conforming to ANSI B16.1, ductile iron, conforming to ASTM A-536 Grade 65-45-12, or fabricated steel conforming to ASTM A-53 Grade B, as per requirements of AS2118.9 and AS4118.2.1. 3. Grooved couplings used in refrigerated spaces shall be Grinnell Figure 772 rigid type using Tri-Seal Grade E gaskets. Only silicone gasket lubricant shall be utilized. a. In other portions of the occupancy, where ambient temperatures are maintained above 4.4 C (40 F), Grinnell Figure 772 rigid type couplings or Grinnell Figure 705 flexible type couplings, both using a standard Grade A gasket, are acceptable. 4. Where steel pipe is used in pre-action and dry pipe systems using the Ultra K17 sprinkler, piping materials shall meet section 2.4.B.1 for dry system piping. Non-galvanized fittings and couplings shall be permitted. 2.5 VALVES 1. Tyco wet riser valves, dry pipe valves, pre-action single/double interlock valves, Tyco Model CV-1F check valves and sprinklers shall be warranted by the manufacturer for ten (10) years against defects in material and workmanship. Fivalco Grooved Butterfly valves shall be warranted by the manufacturer for 12 months as per manufacturers warranty. B. Pre-action Valves 1. General a. Fire protection valves and appurtenances for refrigerated and cold storage areas shall meet or exceed the requirements of NFPA #13 / AS 2118.1 for such service. Where jurisdictional requirements exceed or conflict with those of NFPA, the more stringent shall apply. b. All components of pneumatic, hydraulic, or electrical systems shall be compatible and shall be listed for their intended use. c. The system(s) shall be provided with a mechanical manual means for operation that is independent of detection devices and sprinklers (Pre-action systems). 5

d. Conforming, listed pressure gauges shall be installed. e. Where a system in a refrigerated space is supplied by an automatic air compressor or plant air system, the air shall be moisture free, and any device or apparatus used for automatic maintenance of air pressure shall be of a type specifically listed for such service and capable of controlling the required air pressure on, and maximum airflow to, the system. Piping details shall be consistent with those referenced in NFPA #13-2007, Section 7.9 - Refrigerated Spaces. Where utilized, nitrogen shall be introduced through a pressure regulator set to maintain system pressure. f. Spacing of detection devices shall meet the recommendations as noted in TFP #372 which shall take precedence over the manufacturers specified spacing requirements if shown to be greater than TFP guidance and shall be positioned to operate prior to the automatic sprinklers protecting the area. All detection devices shall be listed and suitable for the environment into which they are installed. 2. Pre-action Systems a. Pre-action systems shall be double interlock systems using listed valves and trim that actuate and admit water to sprinkler piping upon operation of both detection devices and automatic sprinklers. b. Double interlock pre-action systems shall be of a tree design. Grid and loop designs shall not be permitted. c. All electronic controls for the pre-action system shall be listed for their intended use and shall be capable of signaling trouble and alarm conditions. The controls shall operate on 240v AC input and all outputs shall be 24v DC. The panels shall be equipped with added contacts for local and remote transmission of trouble and alarm signals, and shall also be equipped with a minimum of four DPDT dry contacts for associated equipment shutdown. Controls shall be provided with 24v DC battery back-up capable of providing a 72 hour stand-by function in the event of a loss of power. All alarm and detection circuits shall be supervised with Class B supervision per the requirements of NFPA 72. Where the requirements of Factory Mutual must be met, the circuits shall be supervised, Class A type. C. Components and Hardware 1. Double Interlock Pre-action Systems utilizing Electric/Electric Actuation shall be a listed combination of the Tyco Model DV-5 Deluge Valve fitted with a Tyco Model CV-1F Check Valve to create the pre-action system or equivalent. A VanQuish Fire Sprinkler System design shall utilize the Tyco Model DV-5 deluge valve, Tyco Model CV-1F check valve, Potter 4410RC control panel and the Tyco Model QRS electronic accelerator configured as an electric/electric double interlock pre-action system. 2. Dry Pipe Systems (Non VanQuish applications-example-loading dock protection) shall utilize the TF&BP Model DPV-1 Dry Pipe Valve, TF&BP 6

Model QRS electronic accelerator with Potter 4410RC control panel (when a quick opening device is required), and corresponding trim assembly. Utilization of a TF&BP DV-5 Pre-action valve (incorporating the CV-1 check valve) is acceptable as an alternative to the DPV-1 permitting AHJ approval. 2.6 FIRE DETECTION 1. Fire Detection devices and auxiliary components for refrigerated and cold storage areas shall meet or exceed the requirements specified in AS1670.1. Where jurisdictional requirements exceed or conflict with those of NFPA, the more stringent shall apply. 2. Fire Detection in those areas protected by a VanQuish system shall consist of an approved linear heat detector designed and installed to activate prior to the first sprinkler head. 3. Linear heat detection circuits shall be supervised, Class B. Where the requirements of Factory Mutual must be met, the circuits shall be supervised, Class A type. 4. Linear Heat Detector shall be warranted by the manufacturer for one (1) year against defects in material and workmanship. B. Linear Heat Detection 1. The Linear Heat Detector shall be a fixed temperature 68 C (155 F) single line-sensing element consisting of two electrical current carrying wires separated by a heat sensitive coating. The temperature must be clearly printed on the detector. C. Components and Hardware 1. Linear heat detector shall be SAFE ThermoCable digital linear heat detection cable. 2. Linear heat detector mounting hardware shall be of the same make and brand as the linear heat detector. 2.7 ALARMS A. Alarms - the alarm apparatus for pre-action systems shall consist of alarms actuated independently by the detection system and the flow of water. 7