Rupture Discs with B.D.I. Alarm System

Similar documents
B.D.I. The B.D.I. (Burst Disc Indicator) Alarm System is designed for use with Continental Disc

B.D.I. The B.D.I. (Burst Disc Indicator) Alarm System is designed for use with Continental Disc

BDI-FLX B URST SY STE M BENEFITS BDI-FLX AVAILABLE FOR INDUSTRIAL AND SANITARY APPLICATIONS

WELL ACTIVATION TYPE A & TYPE I AND SAFETY PROTECTION RUPTURE DISCS FEATURES BENEFITS

L+T GASETECHNIK. Klöpper-Waldmann GmbH & Co. K G. Alarm unit LSG4

Model 144H. Product Data Sheet , Rev DB February Content

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

OIL & GAS EXPERTS PRESSURE RELIEF & PRESSURE ACTIVATION WE ARE THE RIGHT SOLUTION

Model 144H. Product Data Sheet , Rev DB February Content

Dependable Solutions for Gas Detection

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

Rosemount 2090P Pulp and Paper Pressure Transmitter

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20

Sanitary Pressure Transmitter

DB5 Intrinsically Safe Sounder Type DB-5

EtherCAT Box Modules (EPxxxx-xxxx)

Intrinsically Safe Solutions

Annubar Flowmeter Series

Ramsey Series Motion Monitoring Systems Accurate Sensing of Speed Conditions on Rotating Shafts and Machinery

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

EUROPEAN DIRECTIVES Explosive atmospheres ATEX 2014/34/EU

SET-2000 Hi Level/Oil

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Dräger Polytron 7000 Fixed gas detector

Commercial/Industrial Combustion Control Level Three Announcement

Thermo Scientific Ramsey TM Series Sensing Speed Conditions on Rotating Shafts and Machinery

First Line of Safety: Farris Engineering

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

Dräger Polytron 8200 Stationary gas detector (CatEx)

Integrated Process Solutions. Series 46 Heaters HEATER JACKETS FOR STAINLESS STEEL PIPING SIZES 1 1/2 TO 4 (NW 40 TO NW 100)

C6097A,B Pressure Switches

A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

CNA-Series - Large Industrial Heaters Tankless Water Heating Solutions

Dräger Polytron 8310 Stationary gas detector (DSIR)

OPTIBAR DP 7060 Supplementary Instructions

OPTIWAVE X500 Supplementary Instructions

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Absolute and Gage Pressure Transmitter

Vent-Saf. BSBsystems.com BSBipd.com Visit our website for the most complete, up-to-date information

Frequently asked questions: Intelligent Transmitter Series

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

Brooks MT3600 Series Metal Tube Variable Area Flowmeters

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

A. Product Data: Include rated capacities, furnished specialties and accessories.

Rosemount 2090F Sanitary Pressure Transmitter with HART Protocol

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

Rosemount 4500 Hygienic Pressure Transmitter. Start

SET Installation and Operating Instructions. Level switch for one sensor

Ultrasonic Point Level Switches

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

96.2% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS CON X US REMOTE CONNECT. MODBUS AND BACnet MSTP PROTOCOL

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

MSM400 Ultrasonic Suspended Solids Monitoring and Control System

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

VERSAFLOW VORTEX Supplementary instructions

ULTRA-SAFE Explosion-proof Duct Heaters

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

PANELBOARD PROTECTION ON A GLOBAL SCALE

SNA-SKID Series - Preassembled Safety Shower Heater Skid Tankless Water Heating Solutions

DICTATOR Hold-Open Systems for Hazardous Areas

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Dräger Polytron 8000 Stationary gas detector (EC)

4) Intrinsic Safety Certification

Rosemount 2090F Hygienic Pressure Transmitter

CONTROL BE MADE CHANGES MAY NOT. Page 1

AlarmLine Linear Heat Detector

Ramsey Motion Monitoring Systems

MODEL A18 SOLVENT RECOVERY SYSTEMS (EXPLOSION PROOF UNITS)

Commercial and Light Industrial Fire Alarm Control Panel

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Unfired Steam Generators (Series RB) Installation, Operation and Maintenance

Intrinsically Safe Flame Detector Installation Guide

Sensall Sapphire. Thermo MeasureTech ULTRASONIC POINT LEVEL SYSTEM

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

C1N Series - Light Industrial Heaters Tankless Water Heating Solutions

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

Instrumentation and Controls Group

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

Installation Requirements for Models:

ClampOn DSP Pig Detector

SECTION DOMESTIC WATER PIPING SPECIALTIES

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

Dräger REGARD -1 Control System

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTRUCTION & SERVICE MANUAL

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

Inductive slot sensor

HazLoc Essential Guides:

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

SEC 2000 Millenium Infrared Gas Detector

Transcription:

Rupture Discs with B.D.I. Alarm System ASME Code Symbol Stamp Available When Specified China Manufacture License Available When Specified ATEX Directive for MTB-700 Alarm Monitors Available When Specified Continental Disc Corporation has representatives located throughout the world. Contact the C.D.C. office nearest you for the authorized representative in your area. CORPORATE HEADQUARTERS Continental Disc Corporation 3160 W. Heartland Drive Liberty, Missouri 64068-3385 USA Phone: FAX: E-mail: Website: (816) 792-1500 (816) 792-2277 / 5447 pressure@contdisc.com www.contdisc.com THE NETHERLANDS GERMANY UNITED KINGDOM CHINA DUBAI Continental Disc Corporation Energieweg 20 2382 NJ Zoeterwoude-Rijndijk The Netherlands Phone: + (31) 71-5412221 FAX: + (31) 71-5414361 E-mail: cdcnl@contdisc.com Continental Disc Deutschland GmbH Virmondstrasse 151 47877 Willich Germany Phone: + (49) 2156-490802 FAX: + (49) 2156-492547 E-mail: cdd@contdisc.com Continental Disc UK Ltd. Unit C, The Business Centre Faringdon Avenue, Harold Hill, Romford Essex RM3 8EN United Kingdom Phone: + (44) 1708-386444 FAX: + (44) 1708-386486 E-mail: cduk@contdisc.com Continental Disc Corporation 2026 The Executive Center 20/F The Center 989 Changle Rd. Shanghai, 200031 P.R. China Phone: + (86) 21-5117-5848 Fax: + (86) 21-5117-5849 Mobile: + (86) 137-8897-2291 E-mail: jyang@contdisc.com Continental Disc Corporation P.O. Box 2234 Dubai, U.A.E. Phone: + (971) 43214490 Fax: + (971) 43438840 Mobile: + (971) 508129525 E-mail: kannan@contdisc.com Continental Disc Corporation reserves the right to alter the information in this publication without notice. Reproduction without written permission prohibited. 1983-2007 Continental Disc Corporation Printed in U.S.A. 06072000BP 5-7701-5

BURST DISC INDICATOR Continental Rupture Discs with the B.D.I. * Alarm System The Continental B.D.I. (Burst Disc Indicator) Alarm System is designed specifically for use with Continental Rupture Discs. It signals the operator of a system when a rupture disc has burst to relieve an overpressure condition. The heart of the system is the B.D.I. Alarm Strip. Upon disc rupture, the Burst Disc Indicator Alarm Strip is severed, disrupting the flow of electric current through the strip. An attached alarm monitor can then transmit a warning and/or activate appropriate equipment. The B.D.I. Alarm System should be specified: When warning of pressure relief is essential for plant safety When immediate notice is needed of relief of an overpressure or vacuum condition to indicate process malfunction When indication is vital that a rupture disc has burst and toxic substances are venting When emergency equipment must be triggered immediately upon disc rupture to alter or stop a process When loss or contamination of product will occur if a rupture disc is not replaced immediately When monitoring of rupture discs is important in hard-to-reach locations Proven Design The Burst Disc Indicator Alarm Strip is designed to break when its corresponding rupture disc bursts. Continental's design has been proven through years of testing, both in the field and in our ASME accepted flow testing laboratory. This testing has proved the reliability of the Alarm Strip when used with Continental Rupture Discs. The does not affect the life or performance of the rupture disc. The Continental is carefully designed and manufactured with the following features in mind: Resistant to chemicals and weather Usable over a wide range of temperatures Easily replaceable upon disc rupture Compatible with standard design Continental Rupture Discs ATEX Directive Compliant The and the MTB-700 Alarm Monitor have been certified for use in potentially explosive atmospheres according to the requirements of the European Union, ATEX Directive 94/9/EC. ATEX type approval and quality assurance notification certificates are available on our website at www.contdisc.com. Typical Applications Rupture disc applications which can incorporate the B.D.I. Alarm System are unlimited. They occur in all major industries anywhere quick notice of an overpressure or vacuum condition and release is required. Relief Valves Isolating relief valves with a rupture disc protects internal valve parts from corrosive media. The B.D.I. Alarm System signals when a disc rupture relieves an overpressure condition, enabling the operator to correct the process and restore protection to the relief valve. Installing a rupture disc with a B.D.I. Alarm Strip on the outlet side of a relief valve notifies the operator when a valve has relieved. This is an especially important application when handling toxic or corrosive substances. Processing Vessels Rupture discs with the B.D.I. Alarm System are used on processing tanks and vessels requiring protection from overpressure or vacuum conditions. The system warns when a disc ruptures. Chemical Reactors When processing temperatures and pressures are critical, the B.D.I. Alarm System gives immediate warning when service is interrupted due to relief of an overpressure condition. B.D.I. ALARM STRIP B.D.I. ALARM SYSTEM OPERATING SCHEMATIC NORMAL CLOSED STATE Connector Leadwire OPEN STATE Tank Transports The B.D.I. Alarm System signals immediately when a rupture disc has burst, thereby releasing product to the atmosphere. Pipeline Pumping Stations Rupture discs relieve pressure buildup in pumping stations caused by blocked pipelines. The system signals as relief occurs and can trigger shutdown of pumping systems. B.D.I. ALARM MONITOR Optional Switching Connection Annunciator or Control Panel B.D.I. ALARM MONITOR Annunciator or Control Panel Visual Warning Audio Warning Fermentation Vessels Products requiring gaseous blankets to prevent spoilage or product contamination must be protected from the atmosphere. Immediate warning of disc rupture permits quick corrective action, reducing loss of product and expensive gases. 2

Storage/Silo Tanks Storage tanks which damage easily from overpressure or vacuum conditions are protected with the CAL-VAC Rupture Disc or POS-A-SET Rupture Disc. Often these discs are located in hard-to-reach areas. The B.D.I. Alarm System warns immediately when the rupture disc bursts. Distillation Equipment Distilled products must be free from contamination. Operator warning is vital when a product batch is contaminated from the intake of an outside atmosphere during vacuum relief. The B.D.I. Alarm System provides the needed warning. The Heart of the System: The The Burst Disc Indicator Alarm Strip is designed to break when its corresponding rupture disc bursts. This creates an open circuit which is detected by the B.D.I. Alarm Monitor, or other suitable monitoring device. Design Specifications Maximum current: 50 milliamps Maximum voltage: 24 VDC RMS Operating temperature range: -40 F to +400 F (-40 C to +204 C) Components The is composed of copper conductors adhered to a thin strip of Kapton ** film. Tantalum conductors are available for some applications. The tail of the strip, extending from the rupture disc seating area to the B.D.I. Connector, is protected with polyolefin heat shrink tubing. A strain brace is attached to most designs to prevent undue stress to the B.D.I. Alarm Strip and premature alert. Each is carefully adhered to a Teflon ** membrane to insure proper breakage upon disc rupture. Care is also taken to position the alarm strip where it will be gripped properly by the rupture disc flanges without crushing the conductors. This design prevents the B.D.I. system from signaling prematurely upon installation. The is manufactured as either an Integral Fit or a Universal design, dependent upon the rupture disc product it is to mate with. Refer to photo on page 4-5 for examples. It is compatible with assemblies designed to install between flange bolting classes including ANSI, DIN, JIS, BSI and sanitary clamping designs. Custom designs are also available. Contact the factory for details. Linking the to the monitoring system is the B.D.I. Connector. A two-pin bullet terminal with O-rings protects the terminals at the connecting point against moisture. It is abrasion resistant, flexible, and highly weather-resistant, even in sub-zero climates. The Interconnecting Leadwire between the B.D.I. Connector and a monitor or junction box is unfinished on one end to permit connection dictated by local electrical codes. It is available in standard lengths from 6 ft. to 500 ft. (1.8m to 152m). Open end available in various lengths From Leadwire From B.D.I. Strip To protect the tail of the B.D.I. Alarm Strip, each comes with a Leadwire Strain Relief Device. This device prevents undue stress on the alarm strip by securing the B.D.I. Interconnecting Leadwire in place. Option Sanitary Design Holder Insert Design Assembly When there is a distance of 15 feet or more between the and the monitoring device, a junction box is recommended. This box protects the alarm strip from the weight of the long cable and from environmental elements. Shielded cable (such as blue Beldon #8412 cable) should be used for cable runs between a junction box and the B.D.I. Alarm Monitor, to prevent triggering of a false alarm. If the cable is run through conduit, a less expensive cable (such as Beldon #8441 instrumentation cable) can be used. * Burst Disc Indicator (B.D.I.) Alarm System incorporates U.S. patent no. Re.34,308 and 4,408,194; Australia patent no. 539415; Canada patent no. 1199990; Germany patent no. 3174227.0; Belgium, France and United Kingdom patent no. EP 0 033 867; Japan patent no. 2032464. ** Kapton and Teflon are registered trademarks of E.I. du Pont de Nemours and Company used under license. 3

VARIOUS B.D.I. APPLICATIONS Supplied with Integral Fit For the Integral Fit design, the copper strip is adhered to a Teflon membrane which has been formed to the same configuration as the mating rupture disc. Then, the B.D.I. Membrane is permanently affixed to the rupture disc, usually on the downstream side. A strain brace is attached to the disc or the 3-D flow direction tag to avoid damage to the strip extension. GRAFSERT Rupture Disc The GRAFSERT Rupture Disc is for applications requiring resistance to most commercial chemicals. designed for operation up to 90% of the disc's rated burst pressure. The is mounted directly between the disc and the arcuate, passing out of the sanitary clamping device through the bolt opening. ENVIRO-SEAL Rupture Disc The ENVIRO-SEAL is for systems requiring economical protection for low pressure atmospheric storage vessels, downstream isolation of safety relief valves and protection of equipment from corrosive environments. It is designed for operations at up to 50% of rated burst pressure. The is mounted directly to the outlet side of the rupture disc. Supplied with Universal Vent Panels The Universal incorporates a copper strip adhered to a full Teflon membrane and mounted between non-asbestos gaskets. The Universal design alarm strip is positioned on the downstream side of the holder outlet when installed in service. Vent Panels are designed to minimize structural or mechanical damage that may be caused by expanding gases resulting from the deflagration of dust, gases, or mists in equipment, rooms, buildings or other enclosures. The is mounted directly to the outlet side of the vent panel. MICRO X Rupture Disc The MICRO X Rupture Disc is a cross-scored tension type disc for systems with normal operating pressures up to 80-85% of the burst pressure rating of the rupture disc. The is permanently mounted between the outlet side of the rupture disc and the non-asbestos gasket. ULTRX, MINTRX, STAR X, & LOTRX Rupture Discs CAL-VAC / POS-A-SET Rupture Discs This unique family of semicircular scored reverse-acting rupture discs are for liquid or gas systems with operating pressures to 90% of the rupture disc stamped rating and are superior for cyclic operating conditions. CAL-VAC Rupture Discs provide ultra-low vacuum relief in addition to positive pressure relief. Vacuum relief begins as low as 1" water column. POS-A-SET Rupture Discs provide ultra-low positive pressure relief in addition to vacuum relief. Positive pressure relief begins as low as 1" water column. RCS Rupture Disc Supplied with Either Integral Fit or Universal Standard Rupture Disc The RCS Rupture Disc is a crossscored reverse-acting design disc for gas service and 90% operating-to-burst ratio. KBA Rupture Disc The KBA is for systems requiring exceptional burst accuracy and operating pressures to 90% of the burst pressure rating on the rupture disc. ZAP Rupture Disc The ZAP Rupture Disc is for systems where conditions of pressure, pulsations and cycles exist. It withstands operating pressures up to 90% of the rupture disc burst rating and backpressure to 110% of the disc rating. The Standard Rupture Disc is for systems with normal operating pressures up to 70% of the burst pressure rating of the rupture disc. The Integral Fit is available for sizes 1-1/2" to 12" (40mm to 300mm). All others use the Universal. Composite Rupture Disc The Composite Rupture Disc is for systems with operating pressures up to 80% of the burst pressure rating of the rupture disc. It is especially suitable for systems requiring low pressure relief. An Integral Fit B.D.I. Strip is available for sizes 1-1/2" to 12" (40mm to 300mm). All other size Composite rupture discs use a Universal. s can, in general, be applied in any of the following holder classes: 150/300# ANSI...1" - 24" MSS SP-44 150#...28" - 36" DIN 10/16...25mm - 900mm On both the CAL-VAC and the POS-A-SET, the is mounted directly to the Teflon seal. Upon disc rupture, in either direction, the alarm strip activates a signal to the monitoring device. JIS 10/16...25mm - 200mm Integral Fit Design SANITRX Rupture Disc SANITRX Rupture Discs are ideal for applications requiring reliable overpressure protection for sanitary systems, equipment and vessels. This disc is Contact the factory for available configurations with the LOTRX Rupture Disc. Integral Fit Design Universal Style Universal Style 4 Integral Fit Design Universal Style 5 Available sizes and disc pressure ratings subject to material availability and conditions of the application. Consult factory for special applications.

VARIOUS B.D.I. APPLICATIONS Supplied with Integral Fit For the Integral Fit design, the copper strip is adhered to a Teflon membrane which has been formed to the same configuration as the mating rupture disc. Then, the B.D.I. Membrane is permanently affixed to the rupture disc, usually on the downstream side. A strain brace is attached to the disc or the 3-D flow direction tag to avoid damage to the strip extension. GRAFSERT Rupture Disc The GRAFSERT Rupture Disc is for applications requiring resistance to most commercial chemicals. designed for operation up to 90% of the disc's rated burst pressure. The is mounted directly between the disc and the arcuate, passing out of the sanitary clamping device through the bolt opening. ENVIRO-SEAL Rupture Disc The ENVIRO-SEAL is for systems requiring economical protection for low pressure atmospheric storage vessels, downstream isolation of safety relief valves and protection of equipment from corrosive environments. It is designed for operations at up to 50% of rated burst pressure. The is mounted directly to the outlet side of the rupture disc. Supplied with Universal Vent Panels The Universal incorporates a copper strip adhered to a full Teflon membrane and mounted between non-asbestos gaskets. The Universal design alarm strip is positioned on the downstream side of the holder outlet when installed in service. Vent Panels are designed to minimize structural or mechanical damage that may be caused by expanding gases resulting from the deflagration of dust, gases, or mists in equipment, rooms, buildings or other enclosures. The is mounted directly to the outlet side of the vent panel. MICRO X Rupture Disc The MICRO X Rupture Disc is a cross-scored tension type disc for systems with normal operating pressures up to 80-85% of the burst pressure rating of the rupture disc. The is permanently mounted between the outlet side of the rupture disc and the non-asbestos gasket. ULTRX, MINTRX, STAR X, & LOTRX Rupture Discs CAL-VAC / POS-A-SET Rupture Discs This unique family of semicircular scored reverse-acting rupture discs are for liquid or gas systems with operating pressures to 90% of the rupture disc stamped rating and are superior for cyclic operating conditions. CAL-VAC Rupture Discs provide ultra-low vacuum relief in addition to positive pressure relief. Vacuum relief begins as low as 1" water column. POS-A-SET Rupture Discs provide ultra-low positive pressure relief in addition to vacuum relief. Positive pressure relief begins as low as 1" water column. RCS Rupture Disc Supplied with Either Integral Fit or Universal Standard Rupture Disc The RCS Rupture Disc is a crossscored reverse-acting design disc for gas service and 90% operating-to-burst ratio. KBA Rupture Disc The KBA is for systems requiring exceptional burst accuracy and operating pressures to 90% of the burst pressure rating on the rupture disc. ZAP Rupture Disc The ZAP Rupture Disc is for systems where conditions of pressure, pulsations and cycles exist. It withstands operating pressures up to 90% of the rupture disc burst rating and backpressure to 110% of the disc rating. The Standard Rupture Disc is for systems with normal operating pressures up to 70% of the burst pressure rating of the rupture disc. The Integral Fit is available for sizes 1-1/2" to 12" (40mm to 300mm). All others use the Universal. Composite Rupture Disc The Composite Rupture Disc is for systems with operating pressures up to 80% of the burst pressure rating of the rupture disc. It is especially suitable for systems requiring low pressure relief. An Integral Fit B.D.I. Strip is available for sizes 1-1/2" to 12" (40mm to 300mm). All other size Composite rupture discs use a Universal. s can, in general, be applied in any of the following holder classes: 150/300# ANSI...1" - 24" MSS SP-44 150#...28" - 36" DIN 10/16...25mm - 900mm On both the CAL-VAC and the POS-A-SET, the is mounted directly to the Teflon seal. Upon disc rupture, in either direction, the alarm strip activates a signal to the monitoring device. JIS 10/16...25mm - 200mm Integral Fit Design SANITRX Rupture Disc SANITRX Rupture Discs are ideal for applications requiring reliable overpressure protection for sanitary systems, equipment and vessels. This disc is Contact the factory for available configurations with the LOTRX Rupture Disc. Integral Fit Design Universal Style Universal Style 4 Integral Fit Design Universal Style 5 Available sizes and disc pressure ratings subject to material availability and conditions of the application. Consult factory for special applications.

B.D.I. ALARM MONITORS Burst Disc Indicator Alarm Monitors The B.D.I. Alarm System uses a normally closed electrical circuit. A continuous signal flows between the and the Alarm Monitor under normal conditions. Once the rupture disc bursts, the Alarm Strip breaks, opening the electrical circuit. Each Continental B.D.I. Monitor contains replaceable modules with individual channel relays. Each channel relay connects to one Alarm Strip. As the rupture disc and B.D.I. strip break, a specific relay is actuated, sending a signal to the control panel. Control panels, annunciators, light panels or other signalling devices can be used to warn of a ruptured disc. The Alarm System is versatile to adapt to a variety of warning devices. Individual relay circuitry allows the user to monitor several B.D.I. alarm strips at once. Pumps, valves, and other systems may also be activated to respond to an overpressure or vacuum situation by the break of a specific alarm strip. Definitions As used in the SB-100, BB-100A, BB400A and MTB-700 Alarm Monitor descriptions: *INTRINSICALLY SAFE is defined as: Apparatus, including wiring, in which any spark or thermal effect produced either normally or in specified fault conditions... is incapable under test conditions of causing ignition of a specified mixture of flammable or combustible material in air. **FAIL SAFE, as generally accepted by industry and the military: If any one component in the sensing section should fail, the alarm must either continue to work properly or activate the alarm. Specifications Continental's B.D.I. Alarm Monitors are offered in five standard, off the shelf models (pictured on page 7, items 1, 2, 3, 4, and 6). Customized alarm monitors, built to specification, are also available (pictured page 7, item 5). Features common to standard models SB-100, BB-100A, BB-400A and LCB-400 are: Terminals for 115/230 VAC @ 50 to 60 Hz or 12 VDC ± 1 volt power input Each relay has independent common terminals Output relay contacts (one per channel) rated as follows: 2 AMPS @ 120 V Resistive 1 AMP @120 V Inductive 2 AMPS @ 24 V Inductive Monitor box is intended for indoor use to provide a degree of protection against dust and dripping liquids Operating temperature range: -40 F to 104 F (-40 C to +40 C) ➀ Model SB-100 Alarm Monitor Designed for wall mounting, the SB-100 has a front-mounted annunciator panel, incorporating audio and visual alarms. The unit features modular construction with all sensing and alarm relays in one easily replaceable module. Monitors two discs separately and continuously Intrinsically safe* signal output to B.D.I. Strip: 6 VDC @ 0.1 MA max Latching mode only. Once the alarm is triggered, it must be reset manually Fail-safe** circuitry design for alarm sensing and activation circuitry Contains easily replaceable incandescent alarm indicator lamps Contains alarm buzzer, alarm master test switch, alarm master resetacknowledge switch Replacement module for the SB-100 Monitor: specify AF-100 ➁ Model BB-100A Alarm Monitor The BB-100A Monitor is a wall mount design and provides information to the operator's control panel. The unit features modular construction with all sensing and alarm relays in one easily replaceable module. Monitors two discs separately and continuously Intrinsically safe* signal output to : 6 VDC @ 0.1 MA max Each channel can be set for latching or non-latching circuitry, where alarm reset is handled manually or automatically Fail-safe** circuitry design for alarm sensing and activation circuitry Intrinsically Safe* Replacement module for the BB-100A Monitor: specify NAF-100 6

B.D.I. ALARM MONITOR SPECIFICATIONS ➅ MTB-700 Alarm Monitor ➂ ➁ ➄ ➀ ➂ Model BB-400A Alarm Monitor The BB-400A Monitor is a larger version of the BB-100A. It uses the same replaceable sensing and alarm relays module, but it can accommodate four modules for a total of eight different rupture discs, monitored individually and continuously. Identical to Model BB-100A Intrinsically Safe* Replacement module for the BB-400A Monitor: specify NAF-100 ➃ ➃ Model LCB-400 Alarm Monitor The LCB-400 is designed for use where an intrinsically safe* sensor signal is not required. The unit is a wall mount design and provides information to the operator's control panel. It features modular construction with eight easily replaceable modules. Monitors eight discs separately and continuously Highly regulated low current signal output to disc: 12 VDC @ 0.5 MA max Replacement module for the LCB-400 Monitor: specify LCAF-100 ➄ Custom Built Monitor ➅ Custom designed alarm monitors are available for specific applications, such as the two-channel unit pictured. Contact the factory for details. The MTB-700 Monitor incorporates Intrinsically Safe Galvanically Isolated Barriers, approved for use in many countries worldwide. Upon disc rupture, these barriers activate signals and/or output relays to warn operators and actuate pumps, valves, or other equipment connected to the system. The unit is modular in construction, and can be purchased with a single MTL two-channel barrier, or it can be upgraded to four channels. Each channel features one DPDT relay for auxiliary contacts, capable of operating a 1/8 HP motor at 120/240VAC for a maximum carrying current of 7 AMPS. When purchased with an annunciator panel, the monitor provides both visual and auditory warning capabilities. The monitor may also be tested and reset from a remote location, i.e. control room, laboratory, etc. 100% galvanically isolated barriers 2 channels, expandable to 4 Supply voltage: 24 VDC, 120/240 VAC With or without annunciator panel Maximum intrinsically safe output level: 7 VDC @ 22 MA Latching mode on all channels Intrinsically safe barrier approvals: USA (Factory Mutual): Class I, II & III: Division I, Groups A-G UK (BASEEFA): [EEx ia] IIc Australia (SA): [EEx ia] IIc Denmark (DEMKO): [EEx ia] IIc Finland (SETI): [EEx ia] IIc Canada (CSA): Class I, II & III: Division I, Groups A-G Japan (RIIS): 3aG6 Operating temperature range: -20 C (-4 F) to 45 C (113 F) Enclosure Nema ratings 4, 4X, 12 and 13 7