SEL-3422 Motor Relay HMI Quick-Start Guide

Similar documents
AB Parts. ControlNet Coax Tap. Installation Instructions. (Cat. Nos TPR, -TPS, -TPYR, -TPYS) What s in This Document

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

Siemens Automation Products Siemens AG All rights reserved A5E AB, 08/2017 1

Certification Supplement Manual

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

Certificate of Compliance

POINT I/O Field Potential Distributor Module

Lumination TM Volumetric Retrofit Kit

GETTING STARTED GUIDE. NI 9212 and TB TC, ±78 mv, 24 Bit, 95 S/s/ch Simultaneous, Isothermal Terminal Block

Product ID. General. TE CONNECTIVITY SENSORS /// EXxxHyy Ex-Atex & NA 09/2017 Page 1

INSTRUCTIONS. OJ-DV-Relay-Module. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. Optional module for OJ-DV motor controller

Safe Operation Manual. Honeywell IQ Force Gas Detector

GETTING STARTED GUIDE NI TC, ±78 mv, 24 Bit, 75 S/s Aggregate

Concerning the use of GP4000 Series Graphic Operator Interface for applications in potentially explosive atmospheres (Zones 2/22)

Compact I/O End Caps/Terminators

UNI 321. User s Guide

Power Supply Display Module PSDM. Installation and Operation Manual

GETTING STARTED GUIDE NI DI, 30 V, Sourcing, 7 μs

standards: standards:

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

Certificate of Compliance

GARAGE DOOR OPENER KIT

Certificate of Compliance

Certificate of Compliance

IntelliDoX Operator Manual

INSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations

Instruction Sheet. DANGER Indicates a potentially or imminently hazardous situation which, if not avoided, will result in death or serious injury.

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

GETTING STARTED GUIDE NI AI, ±29.4 mv/v, 24 Bit, 10 ks/s/ch Simultaneous, 350 Ω Quarter-Bridge Completion

LS Condensate Removal Pump Installation, Operation and Service Instructions

ChemScan mini Analyzer for Low Ammonia Monitoring Installation, Operation and Maintenance Manual

INSTALLATION INSTRUCTION In-Ground

GETTING STARTED GUIDE NI DIO, 5 V/TTL, Bidirectional, 7 μs

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

GETTING STARTED GUIDE NI AI/8 AO/4 DIO, 0 V to 5 V, 12 Bit, 20 ks/s Aggregate

Certificate of Compliance

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

WSD-E WHEEL DETECTOR QUICK REFERENCE GUIDE JUNE 2016 DOCUMENT NO. SIG-QG VERSION A

GETTING STARTED GUIDE NI RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Tetra MAX. LED Lighting System. BEFORE YOU BEGIN Read these instructions completely and carefully. Installation Guide

Manual Power relay SR853

Certificate of Compliance

GETTING STARTED GUIDE NI Channel, 0 ma to 20 ma, 16-Bit Analog Output Module. This document explains how to connect to the NI 9265.

Operating Instructions Edition 11/2005. Process monitoring Ex-barrier for Diagnostics Unit SITRANS DA400 7MJ2010-1AA. sitrans

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Industrial Automation Enclosure

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

INSTRUCTION MANUAL. D2xB1XH1 & D2xB1XH2 Xenon Beacons For use in Hazardous Locations

ShockLink. Important Product Information.

Square D Clipsal Outdoor Light-Level Sensor

Installation Instructions

POINT I/O Field Potential Distributor Modules

AGA TOTAL CONTROL. Model No. - TC3

AD XT. Air Dryer Service Manual. Innovation with Integrity. Version 003 NMR

Power. Average noise level (DIN EN ISO 4871)

AD SP. Air Dryer Maintenance Manual. Innovation with Integrity. Version 001 NMR

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

INSTRUCTION & SERVICE MANUAL

Operating Instructions SIPLUS CMS4000 MCN11. Preface 1. Product Overview 2 SIPLUS CMS4000. Installation 3. Media Converter Node (MCN11) Wiring 4

CONTROL BE MADE CHANGES MAY NOT. Page 1

1495D. Installation and Operation Manual, 230 Voltage 2/16/2017

SkyNEST WASP Portable Kit, Smart Receiver and SCADA Gateway with Solar Panel USER MANUAL

Certificate of Compliance

SITESTAR CABINET DESCRIPTION

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

HEATING SYSTEMS Systèmes de chauffage. THERMO PRO 50 Eco. Spare Parts List Liste de pieces détachées

INSTALLATION INSTRUCTION In-Ground Color Changing

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Technical Manual for the Fire Alarm Call Point - SM87 PBL

Stopper Station Series SS-2008 Push Button Pneumatic Timer Button

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

MBCE-110/230UV Flame Sensor Module

Stopper Station Series Push Button Models SS2xx2, SS2xx5, SS2xx9

ADT. Pulse 2017ADT LLC

Technical Manual for the Strobe - SM87 HXB

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Foot control. No instrument selected. A Raise chair Chair to working position 1 B Incline backrest Chair to spitting. positioning

MODELS SafeSite LED Linear, Class I Div. 1 2 & 4 Versions

XM-441 Expansion Relay Module

HEATING SYSTEMS Systèmes de chauffage. THERMO PRO 50 Eco. Spare Parts List Liste de pieces détachées

QUICK START GUIDE. Lono, LLC 686 East 110 South, Suite 102 American Fork, UT 84003

SYNRAD Laser Safety 101

Operation and Maintenance Manual

FLOW METER KIT #

Outside Humidity and Temperature Sensor

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

Operating Instructions

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Flopurge TS. Operation Manual

Illuminated Stopper Station Push Button

Transcription:

SEL-3422 Motor Relay HMI Quick-Start Guide Overview The SEL-3422 Motor Relay HMI indicates the SEL-849 operation status through the ten LEDs on its front panel. Eight of these LEDs are programmable. The SEL-3422 has pushbutton control for the LOCAL/REMOTE and START/STOP control selection of the relay and a TARGET RESET pushbutton. WARNING - POTENTIAL ELECTROSTATIC CHARGING HAZARD What s in the Box? Gasket (1) Label Removal Tool Screws for Panel Mounting (4) Panel Cutout Sheet DIN Rail Clip (1)* SEL-3422 Motor Relay HMI Quick-Start Guide DIN Rail Supports (2)* * Not suitable for hazardous locations applications Safety Information Dangers, Warnings, and Cautions See the product manual for additional safety information. This manual uses three kinds of hazard statements, defined as follows: DANGER Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage. WARNING To avoid the risk of electrostatic discharge when using the SEL-3422 HMI, take one of the following precautions: 1) touch the front panel with an insulated object, 2) use ESD shoe covers to insulate shoes from the ground before touching the front panel, or 3) step on an insulated mat before touching the front panel. Date Code 20171110 *PLS3422-01* SEL-3422 Motor Relay HMI

2 Safety Symbols The following symbols are often marked on SEL products. CAUTION Refer to accompanying documents. ATTENTION Se reporter à la documentation. Earth (ground) Terre Protective earth (ground) Terre de protection Direct current Alternating current Both direct and alternating current Courant continu Courant alternatif Courant continu et alternatif Instruction manual Manuel d instructions Safety Marks The following statements may apply to this device. General Safety Marks For use in Pollution Degree 3 environment. Pour l'utilisation dans un environnement de Degré de Pollution 3. Per UL compliance, ambient air temperature shall not exceed 40 C (104 F). Terminal Ratings Tightening Torque Compression Plug: 0.5 1.0 Nm (4.4 8.8 in-lb) Compression Plug Mounting Ear Screw: 0.18 0.25 Nm (1.6 2.2 in-lb) Stripping Length: 8 mm Holes in the enclosure for mounting and wiring the HMI shall not be greater than 775 mm 2. Conforme à la norme UL, la température ambiante desera de l'air ne doit pas dépasser les 40 C (104 F). Spécifications des bornes Couple de serrage Fiche à compression : 0,5 1,0 Nm (4,4 8,8 livres-pouce) Vis à oreille de montage de la fiche à compression : 0,18 0,25 Nm (1,6 2,2 livres-pouce) Longueur de dénudement : 8 mm Les trous dans boîtier pour le montage et le câblage de l IHM ne doivent pas dépasser 775 mm 2. Hazardous Locations Safety Marks WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I, Division 2. For use on a flat surface of a Type 12 enclosure. a For ATEX compliance, the ambient temperature range shall be 20 C to +40 C ( 13 F to +104 F). For UL Class I, Division 2 compliance, the ambient temperature range shall be 25 C to +40 C ( 13 F to +104 F). AVERTISSEMENT DANGER D'EXPLOSION La substitution de composants peut détériorer la conformité à Classe I, Division 2. Destiné à l'utilisation sur une surface plane d'un boîtier de Type 12. Pour conformer à la norme ATEX, la plage de températures ambiantes sera de 20 C à +40 C ( 4 F à +104 F). Pour conformer à la norme UL Classe I, Division 2, la plage de températures ambiantes sera de 25 C à +40 C ( 13 F à +104 F). a. The SEL-3422 is not suitable for use in hazardous locations and will lose the Type 12 rating when mounted on a DIN-rail. SEL-3422 Motor Relay HMI Date Code 20171110

3 Hazardous Locations Approval In North America, the device is approved for Class I, Division 2, Groups A, B, C, and D, and temperature class T3 in the 25 C to +40 C temperature range. To comply with the requirements of the UL Class I, Division 2 for hazardous locations, the SEL-3422 shall be installed on a flat surface of a Type 12 enclosure that is accessible only with the use of a tool and connected to the HMI port of the SEL-849. The SEL-3422 must be connected to the SEL-849, which is covered under ATEX Certificate No. DEMKO 17 ATEX 1832X. The SEL-3422 must be connected to the SEL-849 for hazardous locations suitability. To comply with the requirements of the European ATEX standard for hazardous locations, the SEL-3422 must be installed on the wall of the same ATEX certified enclosure as the SEL-849 in which any door/cover can only be opened by use of a tool and that provides a degree of protection not less than IP54, in accordance with EN 60079-0. The enclosure must be marked WARNING Do not open when an explosive atmosphere is present. For ATEX certification, the gasket must be aligned and installed properly. Failure to do so could allow for the ingress of dust or moisture. The SEL-3422 has not been evaluated for exposure to UV light and must be installed in a location where UV light is not present. The SEL-3422 is intended for panel mounting only. DIN-rail mounting is not suitable for hazardous location applications. Installation Drawings Drill Template 3.85 (97.79) 2.86 (72.69) 1.98 (50.31) LEGEND in (mm) 3.15 (80.01) 2.11 (53.64) 0.62 (15.95) 1.00 (2.54) SEL-3422 Drill Template 4 x 0.14 (4.49) Date Code 20171110 SEL-3422 Motor Relay HMI

4 Panel Mount GASKET Note: To ensure that the electrical connections are completely enclosed, make sure the HMI is mounted with a gasket and that the enclosure has punch holes for the RJ45 connector and the screws. SEL-3422 Motor Relay HMI Date Code 20171110

5 Gasket Installation for the SEL-3422 Panel Mount Step 1. Remove the inner rectangular section from the gasket. Step 2. Peel off the paper to expose the adhesive. Step 3. Position the gasket, with the adhesive side to the rear of the SEL-3422, so that the gasket is inside the outer edge of the plastic casing and the four screw holes are inside the inner rectangle of the gasket. Step 4. Press the gasket to the rear of the SEL-3422 to create a seal around the edge of the SEL-3422. Date Code 20171110 SEL-3422 Motor Relay HMI

6 DIN Rail Mount Connection The RJ45 port on the rear of the SEL-3422 connects to the HMI port on the SEL-849 Relay and receives power from the HMI port. Connection to the relay requires an RJ45 Ethernet cable, such as the SEL-C627M, double-shielded, 600 V, MCC-rated, category 5e Ethernet cable, with a maximum length of 7.62 meters (25 feet). When the relay is turned on, the HMI displays the status of each LED, as shown in the product photo in Overview. Refer to Section 8: Human Machine Interface and Section 1: Introduction and Specifications in the SEL-849 Instruction Manual for more details on the HMI operations and specifications. NOTE: Make sure the relay, HMI, and SELBOOT firmware revisions are compatible. Refer to Appendix A: Firmware and Manual Versions in the SEL-849 Instruction Manual. Accessories Note: DIN rail mounting is not suitable for hazardous location applications. For customizing the LED labels on the SEL-3421/SEL-3422 modules, order Configurable Label Kit, P/N 915900268. Order P/N 915900269 for replacement screws, DIN rail clips, and DIN rail supports for as many as five SEL-3421/SEL-3422 HMIs. The SEL-3422 does not ship standard with an SEL-C627M Ethernet cable. To purchase an SEL-C627M cable, please visit https://selinc.com/products/category-5e-ethernet/. SEL-3422 Motor Relay HMI Date Code 20171110

7 Technical Support We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at: Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163-5603 U.S.A. Telephone: +1.509.338.3838 Fax: +1.509.332.7990 Internet: selinc.com/support Email: info@selinc.com Date Code 20171110 SEL-3422 Motor Relay HMI

8 2016 2017 by Schweitzer Engineering Laboratories, Inc. All rights reserved. All trademarks are the property of their respective holders. SEL products appearing in this document may be covered by U.S. and Foreign patents. The information in this document is provided for informational use only and is subject to change without notice. Date Code 20171110