Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Similar documents
DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

FOAM MAKER MODEL - FMA & FMA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA INSTALLATION, TESTING AND MAINTENANCE APPLICATION SPECIFICATION

SPRINKLER ALARM TECHNICAL DATA SPRINKLER ALARM MODEL - GA

WATER POWERED OSCILLATING MONITOR

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Deluge & Preac tion Systems

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Worldwide Contacts.

TotalPac X Single interlock SUREFIRE system

Instructions for Installation, Operation, Care and Maintenance

mechanical. OPERATION Rapidrop Global

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

TotalPac X Firecycle III Preaction Double interlock system

TotalPac 3 Firecyle III Deluge Remote controlled system

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. 319a. January 27, 2012

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

BERMAD Fire Protection

TOTALPAC2 Integrated Fire Protection System

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Model DDX Deluge Valve

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Technical Data. Installation

TotalPac 3 Wet pipe system c/w retard chamber

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

BROCHURE COMMERCIAL FIRE SPRINKLER CONNECTIONS. Product Submittal A PART OF

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Design Criteria. Installation

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

The Series LFII (TY3596) Residential

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

TotalPac 3 Deluge, Electric release Self-contained system

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

CONSTRUCTION REQUIREMENTS

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

M Series Fan Filter Units

Simple On The Outside...

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

OWNERS MANUAL MODEL 451 (-101 & -201)

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Inline Heater for Solvent or Gas. Installation and Operation Manual

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

GRUNDFOS INSTRUCTIONS CMBE. Installation and operating instructions. Drinking Water System Component NSF / ANSI 61 NSF / ANSI 372

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

INSTRUCTION MANUAL HS-229G

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Sprinkler Identification Numbers

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models

Electric Duct Heaters

D2E Duct Smoke Detector

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

FireFlex DUAL Double Interlock, Self-contained system

Model 4001 Series Single Channel Controller

OPEN SPRINKLER SYSTEM

Checklist For Life Safety

Technical Data Approvals UL Listed and FM Approved. Refer to Tables 1, 2, and 3, as applicable.

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

BACKUP BATTERY INSTALLATION INSTRUCTIONS

User s Manual and Warranty Information for Counterweighted Chain Drive ThyssenKrupp Access

TECHNICAL DATA. model c-2

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Fire Protection Products Technical Data Book Table of Contents, August 2017

EVD-1 Installation, Operation, and Instruction Manual

DBF 4XL Dryer Booster Fans

LV-5 Direct Contact Low Voltage Detector and LV-5/K01 Kit including LV-PT Tester, Holster and Available Accessories

Model/Sprinkler Identification Numbers

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

INSTALLATION, OPERATION AND MAINTENANCE

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Transcription:

Pre-Pack INTEGRATED PRE-ACTION SYSTEM HD FIRE PROTECT TECHNICAL DATA MODEL Pre-Pack SIZE DELUGE VALVE MODEL RISER CHECK VALVE MODEL WATER MOTOR GONG BELL MAXIMUM WORKING PRESSURE SYSTEM END CONNECTION RELEASE PANEL WATER FLOW SWITCH 50, 80, 100, 150 & 200 NB DV-H3, UL Listed CH UL Listed (Optional supply) 17.5 Kg/sq.cm. (250 PSI) Grooved - Standard supply Flanged is optional. POTTER, UL Listed (Optional) POTTER, UL Listed LOW PRESSURE ALARM SWITCH SOLENOID VALVE AUTOMATIC AIR SUPPLY MANUAL SYSTEM SHUT OFF VALVE POTTER, UL Listed UL Listed Oil Less Riser Mount Compressor (Optional) Butterfly Valve, UL Listed (With Tamper Switch) TYPE Single Interlock - Wet Pilot Single Interlock - Dry Pilot Single Interlock - Electric Double Interlock- Electric/Electric Double Interlock- Electric/ Pneumatic CABINET SWG, Red Finish (RAL 3001) APPROVAL DESCRIPTION UL Listed HD Pre-Pack is a pre-assembled Pre-Action System enclosed in cabinet. Pre-action systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping. HD Pre-Pack is with grooved ends to provide minimum installation time. It comes in a compact, space saving, self-standing cabinet while providing an aesthetically pleasing appearance. FEATURES Professionally pre-assembled and factory tested Internally wired Quick and convenient installation Compact, space savng and asthetically pleasing appearance Custom manufactured All sides & door removable for ease of maintenance UL Listed CONSTRUCTION Pre-Pack is pre-assembled, Pre-Action System enclosed, in free standing cabinet. The cabinet is pre-wired and requires water inlet, outlet valve riser and drain. All connections are groove-type to provide minimal installation time. Pre-Pack includes Deluge Valve, Riser Check Valve, Water Supply Stop Valve, Water Flow Supervisory Switch, Pressure Gauges, Built-in Air Compressor and Control Panel with battery backup. The cabinet comes with windows for viewing the release panel function and pressure gauges. The cabinet is constructed of gauge steel and standard finish is red. The front door is hinged and removable. All four sides of the cabinet can be removed for ease of maintenance. Cabinet base plate comes with pre-drilled holes, which provide an anchor point for the cabinet for securing to the floor. All internal valves and major components are individually tagged for identification. The water motor gong bell is supplied loose and a connection is provided for field installation. If required, the water motor gong bell can be pre-assembled with inlet & drain connection to the left side of the cabinet. A hard piped funnel drain is connected through swing check valve to the main drain line. The funnel is provided with flash proof cap so that water does not splash into the cabinet during flow. It is fail-safe feature allowing water to overflow in the event the drain is blocked. A cable entry is provided at bottom of the cabinet. Pre-Pack is also available without Releasing/ Control Panel and Air Compressor. JANUARY, 2018 PAGE 1 OF 8

OPERATION System comprises mainly of two configurations: 1. Double Interlock Double Interlock configuration is more commonly used in industry and it comes with two options: 1. Electric/Pneumatic and 2. Electric/Electric. Both these options have been specified in individual datasheets: HD 128 and HD 127 2. Single Interlock Single Interlock configuration comes in three options: 1. Wet Pilot 2. Dry Pilot 3. Electric All these options have been specified in individual datasheets: HD 126, HD 125 and HD 124 Double Interlock Pre-Action System with Electric/Pneumatic Actuation: This is most commonly used system. This system utilizes a Deluge Valve H3 and Riser Check Valve model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 5 psi (0,34 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. The releasing trim for Deluge Valve utilizes a Solenoid Valve and a Dry Pilot Actuator in a series configuration. The system air pressure holds the Dry Pilot Actuator closed, whereas the Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated by either a fire detection device or manual electric pull station. In order for the Double Interlock Pre-Action System to automatically actuate, two independent events must occur. The Deluge Valve Releasing Panel must operate and open the Solenoid Valve upon automatic operation of the electric fire detection initiating circuit and the sprinkler system piping must lose air pressure due to operation of one or more sprinklers. The Double Interlock Pre-Action System will automatically actuate only when both the Dry Pilot Actuator and the Solenoid Valve are open at the same time. Unintended opening of just the Dry Pilot Actuator or the Solenoid Valve will only cause an alarm and not actuate the system or flood the sprinkler system piping. Double Interlock Pre-Action System with Electric/Electric Actuation This system utilizes a Deluge Valve H3 and Riser Check Valve model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 6 psi (0,42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. The releasing trim for the Deluge Valve utilizes a Solenoid Valve that is energized with cross-zone releasing circuit of release panel. The system air pressure holds the Dry Plot Actuator closed, whereas the Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated by either a fire detection device or manual electric pull station. In order for the Double Interlock Pre-action System to automatically actuate, two independent events must occur. Zone 1 of the Releasing Panel must operate upon automatic operation of the electric fire detection initiating circuit or operation of the electric-manual pull initiating circuit, and Zone 2 of the Releasing Panel must operate via the Low Air Pressure Alarm Switch upon loss of air pressure from the sprinkler system piping, due to operation of one or more sprinklers. The Double Interlock Preaction System will automatically actuate only when both Zone 1 and Zone 2 of the Releasing Panel have operated, energizing the Solenoid Valve. Single Interlock Pre-Action System with Wet Pilot Actuation This system utilizes a Deluge Valve H3 and Riser Check Valve model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 6 psi (0,42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. System actuation is carried out by Wet Pilot Line, consisting of Wet Pilot Sprinklers for detection. Actuation of Wet Pilot Line releases Deluge Valve, which allows water to flow into sprinkler line. JANUARY, 2018 PAGE 2 OF 8

Single Interlock Pre-Action System with Dry Pilot Actuation This system utilizes a Deluge Valve H3 and Riser Check Valve model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 6 psi (0,42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. System actuation is carried out by Dry Pilot Line, consisting of Dry Pilot Sprinklers for detection. Actuation of Dry Pilot Line releases Deluge Valve, which allows water to flow into sprinkler line. Single Interlock Pre-Action System with Electric Actuation This system utilizes a Deluge Valve H3 and Riser Check Valve model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 6 psi (0,42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. System actuation is carried out by supplemental detection system, which typically comprises of 24 VDC heat detectors, smoke detectors, manual pull stations, etc. Actuation of the detection system automatically operates the Deluge Valve, allowing water to flow into the sprinkler piping system, to be discharged from any sprinklers that are open. INSTALLATION REQUIREMENT The Pre-Pack Cabinet and all interconnecting piping must be located indoors in a readily visible and accessible location and in an area having minimum temperature of 4 o C (40 o F). Heat tracing is not permitted. The automatic sprinklers, releasing devices, fire detection devices, must be UL Listed. SYSTEM AIR/NITROGEN PRESSURE REQUIREMENT A suitable sized water supply to the water supply header, common drain piping, system piping including automatic sprinkler/ nozzles and a detection system piping need to be installed connecting to Pre-Pack. If the Supervisory Compressor is not taken with Pre- Pack, then a suitable compressor/ plant air supply/ N 2 connection to be provided with Air Maintenance Device. The selection of compressor shall be as given in Table-1. HYDROTESTING As required by NFPA13, Fire Sprinkler System must be hydrotested and pressure need to be maintained without loss, for two hours. The test pressure shall be as per NFPA 13. In addition to the hydrostatic testing, dry pipe and double interlock pre-action system requires an additional low pressure air test. INSPECTION AND MAINTENANCE Inspection and testing is to be carried out only by authorized and trained personnel. DO NOT TURN OFF the water supply or close any valve to make repair(s) or test the valve, without placing a roving fire patrol in the area covered by the system. Also inform the local security personal and central alarm station, so that there is no false alarm signal. It is recommended to carry out physical inspection of the system at least twice a week. The inspection should verify that no damage has taken place to any components and check for following normal condition of the system. Inspection, Testing and Maintenance must be performed in accordance with NFPA and or authority having jurisdiction. NOTE: The Pressure Gauges standard supply is 300 PSI for water gauge for system pressure upto 175 PSI. If system pressure is more than 175 PSI, then order for 600 PSI water pressure gauges. JANUARY, 2018 PAGE 3 OF 8

HD FIRE PROTECT SYSTEM TYPICAL PRE-PACK ASSEMBLY ARRANGEMENT SYSTEM WITH COMPRESSOR AND RELEASE PANEL 2 18 19 6 10 5 13 7 8 17 9 4 15 12 16 3 11 SUPPLY DRAIN 1 SYSTEM TYPICAL PRE-PACK ASSEMBLY ARRANGEMENT SYSTEM WITHOUT COMPRESSOR AND RELEASE PANEL 6 10 5 13 7 8 17 9 4 15 12 16 3 11 SUPPLY 2 DRAIN 1 1 BASE FRAME 7 ANTI RESET VALVE 13 TRIM FITTINGS 2 CABINET 8 DRY PILOT ACTUATOR PRESSURE SWITCH 3 BUTTERFLY VALVE WITH TAMPER SWITCH 9 EMERGENCY RELEASE STATION 15 SOLENOID VALVE 4 DELUGE VALVE 10 ANGLE VALVE 16 SPLASH PROOF FUNNEL 5 CHECK VALVE 11 PRIMING VALVE 17 SPRINKLER ALARM 6 PRESSURE GAUGE 12 RESTRICTED CHECK VALVE JANUARY, 2018 PAGE 4 OF 8

FRICTION LOSS Friction loss expressed in equivalent length of Schedule 40 pipe and based on Hazen-Williams Formula with C=120 and a flowing velocity of 4.6 mtrs. (15 ft/sec) is as under. The friction loss is with Deluge Valve, Check Valve, Supply Manifold and System Shutoff Valve. Valve Size Equivalent Length in metres 50 mm (2 ) 8.0 80 mm (3 ) 17.5 100 mm (4 ) 20.0 150 mm (6 ) 46.2 200 mm (8 ) 72.0 GROOVED END DIMENSIONS Valve Size Outer Diameter Groove Diameter Groove Width Outlet face to Groove 50 mm (2 ) 60mm (2.357 ) 57mm (2.250 ) 8mm (5/16 ) 16mm (5/8 ) 80 mm (3 ) 89mm (3.5 ) 85mm (3.344 ) 8mm (5/16 ) 16mm (5/8 ) 100 mm (4 ) 1mm (4.5 ) 110mm (4.334 ) 10mm (3/8 ) 16mm (5/8 ) 150 mm (6 ) 168mm (6.625 ) 164mm (6.455 ) 10mm (3/8 ) 16mm (5/8 ) 200 mm (8 ) 219mm (8.625 ) 2mm (8.441 ) 11mm (7/16 ) 19mm (3/4 ) PRINCIPAL COMPONENT Description Make Approval Data Sheet No 1. Deluge Valve HD Fire UL Listed HD 235 2. Check Valve HD Fire UL Listed with Pre-action system HD 104 3. Single Interlock, Electric Actuation HD Fire UL Listed HD 124 4. Single Interlock, Dry Pilot Actuation HD Fire UL Listed HD 125 5. Single Interlock, Wet Pilot Actuation HD Fire UL Listed HD 126 6. Double Interlock, Electric /Pneumatic Actuation HD Fire UL Listed HD 128 7. Double Interlock, Electric /Electric Actuation HD Fire UL Listed HD 127 8. Release Panel Potter UL Listed # 9. Pressure Alarm Switch Potter UL Listed # 10. Pressure Alarm Switch Potter UL Listed # 11. Butterfly Valve (System Shutoff Valve) HD Fire UL Listed HD 282 12. Automatic Supervisory Air Supply (Compressor) General Air Product 13. Air Pressure Maintenance Device HD Fire CE or UL Listed -- UL Listed with Pre-action System. Nitrogen Maintenance Device HD Fire -- -- HD 129 NOTE: # Refer www.pottersignal.com PFC-4410RC JANUARY, 2018 PAGE 5 OF 8

DIAPHRAGM CHAMBER DIAPHRAGM CHAMBER SUPERVISORY AIR SUPERVISORY AIR WATER SUPPLY WATER SUPPLY RELEASING PANEL HD FIRE PROTECT PRE-ACTION CABINET OVERALL DIMENSION (WITH COMPRESSOR & DV RELEASING PANEL) HD FIRE PROTECT PRE-PACK INTEGRATED PRE-ACTION SYSTEM H J M L H J K G E F D C B A F G PRE-ACTION CABINET OVERALL DIMENSION (WITHOUT COMPRESSOR & DV RELEASING PANEL) HD FIRE PROTECT PRE-PACK INTEGRATED PRE-ACTION SYSTEM L H J M1 K H J G E F D C B A F G DIMENSIONS SIZE A B C D E F G H J K L M M1 200 NB 930 80 385 385 850 476 259 190 340 1170 86 2275 1770 150 NB 930 80 385 385 750 420 215 190 315 1061 86 2035 1540 100 NB 870 90 345 345 730 420 187 185 275 937 86 1895 00 80 NB 800 152 248 248 690 407.5 171 185 275 800.5 86 1785 1325 50 NB 800 152 248 248 690 407.5 171 185 275 800.5 86 1785 1325 NOTE: Cabinet material Carbon steel Painted RAL 3001 (SS Optional) Dimensions of Cabinet may change as per client s requirement ** Optional Drain opening on right side of Cabinet Dimensions are approximate All dimensions are in mm OPTIONAL SUPPLY: (i) A lock for cabinet. (ii) Water Motor Gong Bell is optional supply, Pre-mounted or loose supply for field connection. (iii) Air Maintenance Device or Nitrogen Maintenance Device. (iv) Pre-mounted Water Motor Gong Bell can be supplied on left side of Cabinet only. JANUARY, 2018 PAGE 6 OF 8

Pre-Pack SYSTEM AIR (NITROGEN) PRESSURE Supervisory Air Pressure (PSI) Dry Pilot Trim (PSI) Nominal Pressure Low Pressure Alarm Nominal Pressure Low Pressure Alarm Single Interlock - Electric - Wet Pilot - Dry Pilot 35 (+/ 2) 20 (+/ 2) Double Interlock - Electric/ Pneumatic - Electric/ Electric - Dry Pilot 35 (+/ 2) 20 (+/ 2) Pre-Pack SYSTEM ORDERING INFORMATION TABLE 1 Pre-Pack - X XX X X X Size Actuation Device Air Maintenance Device Control Panel Compressor 1 50 2 65 3 80 4 100 5 150 6 200 SE SD SW Single Interlock Pre-action with Electric Actuation Single Interlock Pre-action with Dry Pilot Actuation Single Interlock Pre-actiob with Wet Pilot Actuation N None 1 Air Maintenance Device Model PMD-1 2 Nitrogen Air Maintenance Device N A None Included N None 1 1/6 HP 2 1/3 HP 3 1/2 HP 4 3/4 HP 5 1 HP 6 1-1/2 HP DE Double Interlock Pre-action with Electric/ Electric Actuation DP Double Interlock Pre-action with Electric/ Pneumatic Actuation JANUARY, 2018 PAGE 7 OF 8

LIMITED WARRANTY HD FIRE PROTECT hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer s warranty. No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained. HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer s representatives. HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire s product liability exceed an amount equal to the sale price. The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled. NOTICE : The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherever applicable. The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product. Product development is a continuous programme of HD FIRE PROTECT and hence the right to modify any specification without prior notice is reserved with the company. HD FIRE PROTECT Protecting What Matters Most to You D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA. TEL: + (91) 22 2158 2600 FAX: +(91) 22 2158 2602 EMAIL: info@hdfire.com WEB: www.hdfire.com JANUARY, 2018 PAGE 8 OF 8