POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Similar documents
WATER MIST CONVENTION AND EXHIBITION

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

The Science Behind Water Mist Protection of Typical Building Hazards

An Overview of Extinguishing Systems for Computer Equipment

WAS STARTED BY CARLOS BAHAMONDES MASAFIERRO

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

Emergency shutdown systems. Procedures for bypassing ESD s

Fireward Fixed Fire Fighting System. For Open Areas & Enclosed Risks fireward.co.uk

w-fog RG-SYSTEMS W-FOG WATER MIST CO-OPERATI

Water Mist System. Principle of Water mist evolves from combination of 3 main effects:

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

(Material correct at 1/11/2011)

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

CO2 COCO GAS FLOODING SYSTEM

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

ODS & SGG Alternatives for the Fire Protection Industry 2018

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

& Fire Extinguisher Training

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

Facility Safety Rules Hazard Communication Emergency Procedures Fire Safety. Safety Orientation

Water Mist Fire Suppression

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

CERTIFICATE OF FIRE APPROVAL

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

Directories. B.1 Keyword Directory B.2 Tables B.3 Figures B.4 End Notes Fire Safety Guide / Siemens Switzerland Ltd

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS

Engineering Simulation in Built Environment and Civil Engineering Projects

Element C3.4 Fire Fighting Equipment

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

FOREFRONT AT THE OF PROTECTION

Foam Products ENGLISH

WILLIAM HICKS. MSc, CFEI, CFPS, IAAI-CFI, MIFireE, EFO, CFOD, F-IAFI. Associate Professor Eastern Kentucky University

AUTOMATIC FIRE SUPPRESSION SYSTEMS

Fire Suppression Systems

Material Safety Data Sheet

automatic FiReFighTing SYSTeMS in PainT booths

GAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen

MIST FIRES AND EXPLOSIONS: FACT OR MYTH? Introduction

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990

Dust Explosions. by Clive de Salis. Telephone: +44 (0)

2. Gas B. The column of hot gases, flames, and smoke rising above a fire; also called convection column, thermal updraft, or thermal column

White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications

Water Spray Systems: NFPA 15

Guidance on Video Smoke Detection Technology (VSD)

Making sense of risk Risk engineering. Metalworking operations

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Safety Engineering. Fire Protection Systems and Life Safety Systems

An experimental study of the impact of tunnel suppression on tunnel ventilation

TECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland

WATER SPRAY EXTINGUISHING SYSTEMS

Fire protection for buildings

contents iii Drilling Tools 27 Adjustable Choke 27 Automatic Drillers 29 MWD and LWD Tools 30 How They Work 30 Uses 30

High-pressure water mist systems and fire testing. Max Lakkonen IFAB Institute for Applied Fire Safety Research

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010

PRESSGUARD PDF-VERSION (ADJUSTED FROM BROCHURE) PRESS & HOT OIL PUMPS PROTECTION

PHIREX AUSTRALIA. FOGEX & MISTEX WATER MIST FIRE PROTECTION

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

Safety Data Sheet 1. PRODUCT AND COMPANY IDENTIFICATION. Product name: Product Number:

Watermist Fire Protection of Plant Rooms

MODULE 2. Water-Based Suppression System Basics

Nessie High Pressure Water Mist Components for Fire Fighting

Explosion Protection Engineering Principles

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

Environmental emergency preparedness and response

SEMICONDUCTOR FABRICATION FACILITIES

What is HI-FOG? The natural enemy of fire

7 Fire Protection Systems Synopsis

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

Level 2 Award in Fire Safety (QCF) (SCQF Level 5 in Scotland) Unit 1 title: Fire safety principles

IFE Level 4 Certificate in Fire Science and Fire Safety

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring)

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

SEMICONDUCTOR FABRICATION FACILITIES

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

SEMICONDUCTOR FABRICATION FACILITIES

Fire is No Accident Fire is No Accident It can be prevented.

GAS EXTINGUISHING SYSTEMS INERT GAS. Argon Extinguishing Systems. Fire Protection Systems

Official Journal of the European Union

Saving lives with coatings

Aspirating Gas Detection CFD Modelling Predicts Application Performance

STANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd

Smoke detection in hazardous areas:

(Publication of titles and references of harmonised standards under Union harmonisation legislation) (Text with EEA relevance) (2015/C 335/02)

CHAPTER 8 OCCUPATIONAL HEALTH AND SAFETY

FIRE SUPPRESSION SYSTEM

JET-X HIGH-EXPANSION FOAM GENERATORS Data/Specifications

Rick Seidel Fike Corporation Regional Sales Manager

KD Innovative extinguishing with Novec TM 1230 by 3M TM

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES

Transcription:

FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0

Eurofeu position paper on water mist for fire fighting applications 1 Scope The purpose of this document is to provide basic information to non-specialists that need to evaluate the applicability of water mist in fire protection systems. It sets out both the principle benefits of water mist and the known limitations or disadvantages, when compared to alternative protection methodologies. The guidance provided is generic and may not be applicable to a particular system or to future product developments. Eurofeu has representation from suppliers of water mist systems, CO2 systems, fluorocarbon systems, inert gas systems, sprinkler systems, water spray systems, foam systems and dry powder systems. This position paper seeks to provide unbiased advice without the influence of commercial interest. 2 Introduction Water mist fire fighting systems provide fire protection for life and property without any adverse impact on the environment. It is important to recognise in categorising the efficacy, and thus applicability, of any water mist system that a distinction should be made between: Fire Control: where the design purpose of the system is to restrict and reduce fire propagation until other mitigating measures are taken, and Fire Extinguishing: where the design purpose is to ensure complete suppression and extinction of all combustion. It is a further characteristic of water mist systems that the resultant fire protection is dependent on the location of the distribution nozzles relative to the fire. There are many other effective fire fighting systems which use water, gaseous and other media. Gaseous extinguishing agents are discussed in a separate paper entitled Eurofeu position paper on gaseous alternatives to Halons in fire fighting. Water mist systems have been used since the mid 19 th century, and may also be known as water fog systems, fine water spray systems, and other synonyms. Water mist systems are usually classified based on three nozzle pressure ratings: low, medium and high. Each pressure rating has its technical characteristics and benefits, but the effects of water in mist form on the fire and on materials are essentially the same. The differences between water mist systems of each class are of a more commercial nature and Version 1 29-09-04 1

are not discussed in this paper. Water mist systems are defined as water based systems in which at least 90% by volume of the water is distributed in droplets of less than 1000 microns. Performance is critically dependent on the droplet size distribution, and on the temporal and spatial deployment of the water mist from each of the nozzles. 3 Protection of equipment Water mist may be suitable for applications such as combustible liquids where rapid fire development is expected. It is however necessary to take into account the details of the application which are crucial for the system engineering. The effectiveness of water mist systems in particular applications should be demonstrated by accredited third party testing. It is important to understand the scope and limitations of such testing in order not to make unjustified extrapolations regarding its validity when applied to real hazards. Before engineering a system a number of aspects have to be dealt with very carefully, each of which could influence system performance. 3.1 General conditions of use Water mist systems are usually applied to protect specific equipment (local application) or selected areas within enclosures, but not necessarily the total enclosure, unlike a gaseous system. See Clause 4, Use and Limitations, for further information. 3.2 Enclosure Pressurisation considerations The predominant suppression mechanism of water mist is flame cooling. The initial steam produced upon contact with the heat of fire will result in a pressure increase, followed by a subsequent pressure decrease, which can result in negative pressure in the closure. Consideration must be given to the need for properly engineered pressure relief. 3.3 Ventilation considerations Water mist is usually only discharged in areas with low air flow, in order to achieve reliable control, suppression or extinguishment, unless the system is specifically designed to provide an adequate spray coverage taking the flow of air into consideration, e.g. in such a way that it assists in carrying the water droplets into the fire. Openings in the protected enclosure may also be critical to the effectiveness of the system, and should be avoided or taken into account in the system design. This is particularly important where Version 1 29-09-04 2

the protection depends on limiting the supply of oxygen to the fire. 3.4 Flammability considerations Most fires involve the reaction of oxygen with a hydrocarbon or other combustible material. The reaction generally takes place when the combustible material is in the vapour phase, i.e. not in the liquid or solid phase. The amount of fuel vapour released from light liquid hydrocarbons is usually more than that from distillates or heavier fuels under the same thermal and pressure conditions. In fact if spilled gasoline is not vented immediately or ignited very soon after the spill, an explosive mixture is liable to form. This is not the case with heavier fuels (such as diesel, lube oils, transformer oils, etc.). Extrapolation from test results with one type of fuel may not necessarily be valid for other fuels. 3.5 Types of Fires Three main types of liquid fuel fires involving heavier fuels are considered; these are 2- dimensional pool fires, 3-dimensional jet or spray fires, and the combination of the two types. For Class A fires (solid materials), water mist usually only provides control; if extinguishment is achieved there is a risk of subsequent re-ignition. In either case the duration of the water supply is a critical factor. Water mist is not appropriate where deep seated fires are likely to occur. Liquid fuel pool fires which are large relative to the enclosures size are often powerful enough to generate large amounts of steam from the water mist. This has the effect of diluting the oxygen throughout the enclosure and, thus assists in extinguishment of the flames. Fires which are small relative to the enclosure size do not generate enough steam to dilute the oxygen to an adequate level for extinguishment. To accomplish extinguishment water needs to be discharged directly onto the flame. This is why small fires are often much more challenging to a water mist system than larger ones. If the target fire is in its earliest stages the objective of the protection should be control, since suppression cannot be guaranteed. 3.6 Water Quality Considerations The water normally used in a water mist installation must be very clean water completely free of solids in order to prevent the nozzles from blocking during discharge. This is especially true for high pressure nozzles with very small orifices. If seawater is used, additional means of cleaning, filtering and flushing after use may be needed. Potable, distilled, de-mineralised and de-ionised water may be used, with consideration given to the use of biocide. Version 1 29-09-04 3

3.7 Water mist with foam additives The extinguishing properties of foam, including the ability to spread readily over pool fires, may contribute to the effectiveness of a water mist system. The use of water-foam mixtures may improve the effectiveness of the system and minimise re-ignition potential. Foam may be considered in applications where: there are obstructions between the mist source and the fire (e.g. pool fires under open floors) and / or the probability of re-ignition needs to be minimised. Foam should only be added when the equipment protected is not likely to be affected by the corrosive degreasing properties of foam and appropriate cleaning is scheduled after a discharge. The system must have been fully fire tested in combination with this foam additive. 3.8 Detection and Control System: The detection and control system is of paramount importance for correct and efficient system functioning. It should always be designed and carried out by specialists in accordance with the relevant standards. Only detection and control systems should be used which ensure response characteristics similar to the conditions under which the water mist system was fire tested. 3.9 System Reliability The reliability of a water mist system and its components should be demonstrated by accredited third party testing. 3.10 Water supply Consideration should be given to the duration and availability of the water supply, especially where rapid suppression cannot be guaranteed or reignition is likely to occur. 4 Use and limitations 4.1 Use Here are some typical examples where water mist has been successfully used: Rotating machinery Liquid hydrocarbon process risks Version 1 29-09-04 4

Machinery spaces Gas turbines Chipboard machines Fully enclosed conveyors Painting equipment Steam turbines Diesel generators Engine test cells Cable tunnels Indoor transformers However, even in some of these cases, water mist may not be suitable, e.g. if there is also an explosion hazard or where parameters such as size, ventilation, geometry etc. are different from the tested scenarios. Water mist protection systems should only be designed and installed for applications for which they have been properly tested. The characteristics of the specific application should be consistent with the testing. It is dangerous to extrapolate from test data for water mist systems. The efficiency of a system is very sensitive to many variables, including: Fire position and size; Water droplet size and droplet size distribution; Nozzle positioning; Droplet momentum. Obstructions to water distribution; Enclosure openings and ventilation. 4.2 Limitations Water mist should not be used on fires in materials that are incompatible with water. Risks involving gases and airborne powders are not appropriate for protection by a water mist system. Risks involving light hydrocarbons would normally require an additive. Water mist is transient in nature. It does not produce a lasting inert atmosphere, nor does it maintain a total flooding concentration in an enclosed space once the discharge has finished. Consequently, permanent extinguishment may not be attained if re-ignition sources, such as open flame or electric arcing are present. Fuel sources should be fitted with automatic shut off devices. Watermist systems should not be used outdoors unless fully fire tested in representative environmental conditions. 5 Physical behaviour The main principles governing fire control, suppression or extinguishment, with water mist, are Version 1 29-09-04 5

cooling and inerting. The water droplets offer a significant surface-to-volume ratio, which results in a high heat absorption capacity. The cooling action is often sufficient for fire control, suppression or extinguishment. Inerting is achieved when the droplets evaporate as they approach the fire source. The expansion of water to steam helps to limit the supply of oxygen to the seat of the fire and its immediate surrounding area. Water mist often controls, suppresses or extinguishes fire rapidly and efficiently. Discharge of the water mist onto a fire significantly reduces the surrounding temperatures and blocks radiation produced by the fire. The mist also helps to strip smoke and other particles from the air and absorbs some of the soluble gases. The absorption of acid gases in water may lead to increased risk of corrosion. 6 Safety for people 6.1 General Human safety relating to the deployment of water mist in manned areas has been addressed by the US Environmental Protection Agency (E.P.A). A Medical Health Panel evaluated the water mist under the Significant New Alternatives Policy (SNAP) and the results were published in August 1995. The overall conclusion was that water mist using potable water is benign to nature and does not present a toxicological or physiological hazard to human beings and is thus safe for use in occupied areas. The use of additives or blends in the systems should be assessed on a case by case basis. 6.2 Exposure in case of fire Hypoxic atmospheres can be produced when an inert gas is used as a propellant for the water and in extreme cases when steam generation is significant. Areas protected by a water mist system should be evacuated in the event of a fire alarm, not because of the application of mist itself but in order to prevent harm to personnel due to exposure to the fire and its combustion products. 6.3 Visibility during and after discharge Water mist can significantly reduce visibility in the protected areas during discharge. It dissipates fairly rapidly afterwards, depending on factors such as air temperature and humidity. Version 1 29-09-04 6

7 Environmental impact Water mist using potable water is benign to nature and does not present an environmental hazard unless the water absorbs dangerous substances from the fuel or fire. In such cases careful consideration should be given to preventing water entering the drainage system or the ground 8 Conclusions Water mist provides industry with a valuable fire protection option. This paper has set out generic guidance on its applicability and limitations of use. Specialist advice should always be sought to attest to the appropriateness of a water mist application for a specific purpose, and provide comparison with other fire protection options. Version 1 29-09-04 7