COMPATIBILITY OF REFRIGERANTS AND LUBRICANTS WITH MOTOR MATERIALS UNDER RETROFIT CONDITIONS. Final Report

Similar documents
Why Thermostats Matter

Electronic Refrigerant Leak Detector DE-FG36-98G Micronic, Inc. Elie Talamas, Jr. Period: 10/1/99 to 12/31/99

Food Service Technology Center

Title Page. Report Title: Downhole Power Generation and Wireless Communications. for Intelligent Completions Applications

FINAL ABSTRACT. CRADA TITLE. Miniature Transducers for Flight Test Unit Instrumentation - Magnetic Field Detector CRADA NUMBER: LA98C10367.

Calculated Energy Savings for Disabling Anti- Sweat Door Heat on Glass Display Case Doors

Report on the Suitability of Class 6, U.S. Government Security Repositories for the Storage of Small Quantities of High Explosives

Food Service Technology Center

SN5446A, 47A, 48, SN54LS47, LS48, LS49 SN7446A, 47A, 48, SN74LS47, LS48, LS49 BCD-TO-SEVEN-SEGMENT DECODERS/DRIVERS

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

Southern California Gas Company Customer Programs Department

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

Sunglo Heater Model A270 Patio Heater Performance Test

PlateScrape Plate Pre-Scrapper Test Report

W. T. Roybal J. T. Bradley III D. E. Rees P. Torrez D. K. Warner J. Debaca. LINAC 2000 Monterey, CA August ,2000

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

SIGMADEK, LTD. FIRE TEST REPORT

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

ISO 2896 INTERNATIONAL STANDARD. Rigid cellular plastics Determination of water absorption

A Cost Effective Multi-Spectral Scanner for Natural Gas Detection

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Condensate Induced Water Hammer in a Steam Distribution System Results in Fatality

Food Service Technology Center

FUNDERMAX GMBH FIRE TEST REPORT

NATURAL CONVECTION HEAT EXCHANGERS FOR SOLAR WATER HEATING SYSTEMS. Technical Progress Report April 1,1995 to May 31,1995

F Prepared by: Kong Sham. Prepared for: PO Box Technology Center

p?:uam SYSTEMS Technical Progress Report Jane H. Davidson NAllJRAL CONVECTION HEAT EXCHANGERS FOR SOLAR WATER HEATING February 1,1996 to March 31,1996

BOP Ram Sensing and Interface Concept Rationale Intelligent BOP RAM Actuation Sensor System

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

polyurethane & polyisocyanurate foam Six Steps for

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles

A FIRST RESPONDERS GUIDE TO PURCHASING RADIATION PAGERS

HEATING AND COOLING REBATES

ALABAMA Propane Gas Association

HEATING AND COOLING REBATES

HEATING AND COOLING REBATES

EMERGENCY PHONE: or (651) (24 hours)

CHAPTER Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 973

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

ISO 7491 INTERNATIONAL STANDARD. Dental materials Determination of colour stability. Produits dentaires Détermination de la stabilité de couleur

MATERIAL SAFETY DATA SHEET 3M Tapes: 3900, 3939, 6969, 2929, 5959, 8979, 8979N, and /19/13

n/a SN74LS47N BCD TO 7 SEG DECOCDER (RC)

Pavement Evaluation of the Concrete Tie-bars and Dowel Baskets on Irvin Cobb Drive, US 60, McCracken County, KY

Horizontal Bottle Cooler Installation and Operation Manual

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

BID PROPOSAL-REVISED

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

Authority - City Engineer Effective August 2, 2011 Amended November 1, 2011, November 1, 2012 and December 11, 2013

Funding is available to applicants on a first come, first served basis, and applications will be considered in the order they are received.

STER 1981 ANNUAL INDUSTRIAL SUMMARY OF FIRE AND PROPERTY DAMAGE EXPERIENCE. Monsanto. MOUND FACILITY Miemisburg. Ohio MLM.ML

INSTRUCTIONS PARTS LIST For President, Monark, Standard, and Fast-Flo Pumps, and Agitator

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Food Service Technology Center

EMERGENCY PHONE: or (651) (24 hours)

COLD WEATHER START KIT Ceiling Mount 4000

Energy Consumption Data Analysis Phase II Final Report

EMERGENCY PHONE: or (651) (24 hours)

Platinum Split 4000 & Platinum Split 4000 Fully Ducted COLD WEATHER START KIT Installation Manual

ISO INTERNATIONAL STANDARD. Fluid power systems O-rings Part 5: Suitability of elastomeric materials for industrial applications

EMERGENCY PHONE: or (651) (24 hours)

Sunpak Heater Model S25 Patio Heater Performance Test

CITY OF EAU CLAIRE, WISCONSIN REQUEST FOR PROPOSALS

AVIATION TECHNOLOGY SERVICES: PIPELINE LEAK DETECTION

Model 5190-F Temperature/Humidity Probe

ISO 3999 INTERNATIONAL STANDARD. Radiation protection Apparatus for industrial gamma radiography Specifications for performance, design and tests

Refrigerant changeover guidelines

Model 5190-E Temperature/Humidity Probe

lmprovin Industrial Refrigeration -!nergy Efficiency

Sýnishorn ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

2017 Commercial & Industrial Program C&I Lighting Prescriptive Rebate Application

Food Service Technology Center

Official Journal of the European Union. (Non-legislative acts) REGULATIONS

3M MATERIAL SAFETY DATA SHEET 3M(TM) Transpore(TM) Surgical Tape Cat. # 1527 series, 1527S-1, 1527S-2 04/07/2006

ISO 2411 INTERNATIONAL STANDARD. Rubber- or plastics-coated fabrics Determination of coating adhesion

PALARRE, ROCHELLE WATER-GUARD VITREOUS CHINA SIPHON JET TOILET

Form DOT F (8-72) Technical Report Documentation Page 2. Government Accession No. 3. Recipient's Catalog No.

TENANT FLOOR WARDEN GUIDELINES

ISO INTERNATIONAL STANDARD

Scale 0: 10 k Scale 50: 10 k (see note 2)

ISO INTERNATIONAL STANDARD. Footwear Test methods for uppers and lining Water vapour permeability and absorption

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

Understanding Applications for Alternative Refrigerants

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

EMERGENCY PHONE: or (651) (24 hours)

Development of a High Pressure Gas Gun for H 2 S and CO 2 Service

Laboratory Evaluation of Residential Furnace Blower Performance

Refrigerant Standards

APR DESIGN FOR RECYCLABILITY GUIDELINES:

ISO INTERNATIONAL STANDARD. Graphical symbols Safety colours and safety signs Part 2: Design principles for product safety labels

Nestlé Central America Region El Salvador

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10

ISO INTERNATIONAL STANDARD. Fire-fighting hoses Rubber and plastics suction hoses and hose assemblies

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

WELLWORTH /HIGHLINE WITH PEACEKEEPER VITREOUS CHINA TOILET

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

Transcription:

DOE/CE/23810-63 COMPATIBILITY OF REFRIGERANTS AND LUBRICANTS WITH MOTOR MATERIALS UNDER RETROFIT CONDITIONS Final Report Volume IV PICTURES Robert G. Doerr and Todd D. Waite The Trane Company 3600 Pammel Creek Road La Crosse, Wisconsin 54601-7599 October 1996 Prepared for The Air-Conditioning and Refrigeration Technology Institute Under ARTI MCLR Project Number 655-50400 This research project is supported, in whole or in part, by U.S. Department of Energy grant DE-FG02-91CE23810: Materials Compatibility and Lubricants Research (MCLR) on CFC-Refrigerant Substitutes. Federal funding supporting this project constitutes 93.57% of allowable costs. Funding from non-government sources supporting this project consists of direct cost sharing of 6.43% of allowable costs; and in-kind contributions from the air-conditioning and refrigeration industry.

DISCLAIMER The U.S. Department of Energy's and the air-conditioning industry's support for the Materials Compatibility and Lubricants Research (MCLR) program does not constitute an endorsement by the U.S Department of Energy, nor by the airconditioning and refrigeration industry, of the views expressed herein. NOTICE This report was prepared as an account of work sponsored by the United States Government. Neither the United States nor the Department of Energy, nor the Air-Conditioning and Refrigeration Technology Institute, nor any of their employees, nor any of their contractors, subcontractors, or their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product or process disclosed or represents that its use would not infringe privately-owned rights. COPYRIGHT NOTICE (for journal publication submissions) By acceptance of this article, the publisher and/or recipient acknowledges the rights of the U.S. Government and the Air-Conditioning and Refrigeration Technology Institute, Inc. (ARTI) rights to retain a non-exclusive, royalty-free license in and to any copyrights covering this paper.

FORMAT FOR THE FINAL REPORT Because of the large scope of this project and the large amount of data recorded, the final report is divided into four volumes. Volume I (148 pages) contains the abstract, introduction, significant results, conclusions, material identification, experimental procedures and summary data tables. This volume provides the results of the study and other information of interest to most readers. The other volumes are necessary only if the reader is interested in the individual data measurements rather than summaries or averages of the data sets. Volume II (250 pages) contains the measurements from tests on the three high pressure refrigerant-lubricant combinations and their alternatives. Original Refrigerant Alternative Refrigerant Exposure Temperature R-12/Mineral Oil R-134a/Polyol Ester 127 C (260 F) R-22/Mineral Oil R-407C/Polyol Ester 127 C (260 F) R-502/Mineral Oil R-404A/Polyol Ester 127 C (260 F) Volume III (155 pages) contains the measurements from tests on the three low pressure refrigerant-lubricant combinations and their alternatives. Original Refrigerant Alternative Refrigerant Exposure Temperature R-11/Mineral Oil R-123/Mineral Oil 100 C (212 F) R-11/Mineral Oil R-245ca/Polyol Ester 100 C (212 F) R-123/Mineral Oil R-245ca/Polyol Ester 100 C (212 F) Volume IV (44 pages) contains the photographs of the motor materials after exposure to the six refrigerant-lubricant combinations and their alternatives.

COMPATIBILITY OF REFRIGERANTS AND LUBRICANTS WITH MOTOR MATERIALS UNDER RETROFIT CONDITIONS Robert G. Doerr and Todd D. Waite The Trane Company ABSTRACT Compatibility tests were conducted on motor materials to determine if exposure to the original refrigerant/mineral oil would affect compatibility of the motor materials after retrofit to the alternative refrigerant/lubricant. The motor materials were exposed at elevated temperature to the original refrigerant and mineral oil for 500 hours, followed by exposure to the alternative refrigerant and lubricant for 500 hours. Measurements were also taken after 168 and 336 hours. As a control, some samples were exposed to the original refrigerant/mineral oil for a total of 1000 hours. The original refrigerants and the alternatives tested for retrofit were as follows: Original Refrigerant Alternative Refrigerant Exposure Temperature R-12/Mineral Oil R-134a/Polyol Ester 127 C (260 F) R-22/Mineral Oil R-407C/Polyol Ester 127 C (260 F) R-502/Mineral Oil R-404A/Polyol Ester 127 C (260 F) R-11/Mineral Oil R-123/Mineral Oil 100 C (212 F) R-11/Mineral Oil R-245ca/Polyol Ester 100 C (212 F) R-123/Mineral Oil R-245ca/Polyol Ester 100 C (212 F) Most motor materials exposed to the alternative refrigerant and lubricant (after an initial exposure to the original refrigerant and mineral oil) were compatible with the alternative refrigerant and lubricant. The only concern was delamination and blistering of the sheet insulation containing Nomex, especially after removal of absorbed refrigerant. This was attributed to solution of the adhesive and not to the Nomex itself. Embrittlement of the polyethylene terephthalate (PET) found in Mylar and Melinex sheet and sleeving insulations was initially observed, but subsequent tests under dry conditions showed that embrittlement of the PET materials was caused by moisture present during the exposure. Compatibility tests of elastomers with R-245ca, retrofitted from R-11 and R-123, showed that the nitrile was compatible with both R-11 and R-245ca, but not with R-123. The neoprene was unsatisfactory because of shrinkage in the R-245ca.

TABLE OF CONTENTS PICTURES, VOLUME IV PICTURES OF PROCEDURES AND UNEXPOSED MATERIALS 1 R-12/MINERAL OIL TO R-134a/POLYOLESTER PICTURES 2 R-22/MINERAL OIL TO R-407C/POLYOLESTER PICTURES 3 Section PICTURES OF SHEET INSULATION EXPOSED TO R-12/R-134a AND R-22/R-407C UNDER DRY CONDITIONS 4 R-502/MINERAL OIL TO R-404A/POLYOLESTER PICTURES 5 R-11/MINERAL OIL TO R-123/MINERAL OIL PICTURES 6 R-11/MINERAL OIL TO R-245ca/POLYOLESTER PICTURES 7 R-123/MINERAL OIL TO R-245ca/POLYOLESTER PICTURES 8 NUMBERING ORDER FOR ALL PICTURES Upper Left: 1, 5, 9, 13 Lower Left: 2, 6, 10, 14 Upper Right: 3, 7, 11, 15 Lower Right: 4, 8, 12, 16 1, 5, 3, 7, 2, 6, 4, 8,

PICTURES SECTION 1 PROCEDURES AND UNEXPOSED MATERIALS

PROCEDURES AND UNEXPOSED MATERIALS PICTURE PROCEDURES 1. Dipping Helical Coils 2. Reclaiming Refrigerant 3. Removing Lubricant From Parr Bombs After Exposures UNEXPOSED MATERIALS 4. Bomb 1: Unexposed Motorettes, Tapes, Tie Cords and Lead Wires 5. Bomb 2: Unexposed Helical Coils and Three Sheet Insulations 6. Bomb 3: Unexposed Helical Coils and Three Sheet Insulations 7. Bomb 4: Unexposed Twisted Pairs 8. Bomb 5: Unexposed Motorettes, Varnish Disks, and Sleeving

PICTURES SECTION 2 R-12/Mineral Oil to R-134a/Polyolester

R-12/MINERAL OIL TO R-134a/POLYOLESTER PICTURES PICTURE R12/Mineral Oil 500 Hour Exposure. 1. Bomb 1: Motorettes, Tapes, Tie Cords and Lead Wires 2. Bomb 2: Helical Coils and Three Sheet Insulations 3. Bomb 3: Helical Coils and Three Sheet Insulations 4. Bomb 4: Twisted Pairs 5. Bomb 5: Motorettes, Varnish Disks, and Sleeving 6. Sleeving Showing Brittleness. R12/Mineral Oil 500 Hour plus R-134a/Polyolester 168 hour Exposure 7. All Materials Except Motorettes 8. Nomex-Mylar-Nomex (NMN), Blistered. R12/Mineral Oil 500 Hour plus R-134a/Polyolester 336 hour Exposure 9. All Materials Except Motorettes.

PICTURES SECTION 3 R-22/Mineral Oil to R-407C/Polyolester

R-22/MINERAL OIL TO R-407C/POLYOLESTER PICTURES PICTURE R22/Mineral Oil 500 Hour Exposure. 1. Bomb 1: Motorettes, Tapes, Tie Cords and Lead Wires 2. Bomb 2: Helical Coils and Three Sheet Insulations 3. Bomb 3: Helical Coils and Three Sheet Insulations 4. Bomb 5: Motorettes, Varnish Disks, and Sleeving 5. Sheet Insulation and Varnish 6. Sheet Insulation and Varnish 7. Parr Bomb Cover Showing Polyethylene Terephthalate (PET) Precipitate 8. Parr Bomb Cover Showing Polyethylene Terephthalate (PET) Precipitate R22/Mineral Oil 1000 Hour Exposure. 9. All Materials Except Motorettes 10. Magnet Wire with PET Residue 11. Nomex-Mylar-Nomex (NMN) showing blistering 12. Delamination of NMN Sheet Insulation 13. Blisters in NMN Sheet Insulation R22/Mineral Oil 500 Hour plus R-407C/Polyolester 168 hour Exposure 14. All Materials Except Motorettes R22/Mineral Oil 500 Hour plus R-407C/Polyolester 336 hour Exposure 15. All Materials Except Motorettes. R22/Mineral Oil 500 Hour plus R-407C/Polyolester 500 hour Exposure 16. All Materials Except Motorettes.

PICTURES SECTION 4 SHEET INSULATION UNDER DRY CONDITIONS

SHEET INSULATION EXPOSED UNDER DRY CONDITIONS R-22/MINERAL OIL TO R-407C/POLYOLESTER PICTURES PICTURE R22/Mineral Oil 500 Hour Exposure. 1. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered R22/Mineral Oil 500 Hour plus R-407C/Polyolester 168 hour Exposure 2. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered 3. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered 4. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered R22/Mineral Oil 500 Hour plus R-407C/Polyolester 336 hour Exposure 5. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered 6. Nomex Sheet Insulation, Blistered R22/Mineral Oil 500 Hour plus R-407C/Polyolester 500 hour Exposure 7. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered 8. Nomex-Mylar-Nomex (NMN) Sheet Insulation, Blistered, Compared to 1000 Hour Exposure to R-22/Mineral Oil. R-12/MINERAL OIL, 500 HOURS TO R-134A/POLYOLESTER 1. Nomex-Mylar-Nomex (NMN), R-134a 336 Hours, Blistered 2. Nomex, R-134a 336 Hours, Blistered 3. Nomex-Mylar-Nomex (NMN), R-134a 500 Hours, Blistered

PICTURES SECTION 5 R-502/Mineral Oil to R-404A/Polyolester

R-502/MINERAL OIL TO R-404A/POLYOLESTER PICTURES PICTURE R502/Mineral Oil 500 Hour Exposure. 1. Bomb 1: Motorettes, Tapes, Tie Cords and Lead Wires 2. Bomb 2: Helical Coils and Three Sheet Insulations 3. Bomb 3: Helical Coils and Three Sheet Insulations 4. Bomb 4: Twisted Pairs 5. Bomb 5: Motorettes, Varnish Disks, and Sleeving 6. Nomex Sheet Insulation, Blistered 7. Nomex Sheet Insulation, Blistered, Close-up 8. Nomex-Mylar-Nomex (NMN), Blistered 9. Nomex-Mica, Blistered 10. All Materials Except Motorettes R502/Mineral Oil 1000 Hour Exposure. R502/Mineral Oil 500 Hour plus R-404A/Polyolester 336 hour Exposure 11. All Materials Except Motorettes. 12. Nomex, Blistered 13. Nomex, Blistered, Side View 14. Nomex-Mylar-Nomex, Delaminated 15. Nomex-Mylar-Nomex, Delaminated, Close View R502/Mineral Oil 500 Hour plus R-404A/Polyolester 500 hour Exposure 16. All Materials Except Motorettes.

PICTURES SECTION 6 R-11/Mineral Oil to R-123/Mineral Oil

R-11/MINERAL OIL TO R-123/MINERAL OIL PICTURES PICTURE R11/Mineral Oil 500 Hour plus R-123/Mineral Oil, 168 hour Exposure 1. All Materials Except Motorettes 2. Permacel Tape 3. Motorettes, Showing Blistering of the Varnish on Steel. Note: Varnish blistering was not observed with additional exposures to R-123. R11/Mineral Oil 500 Hour plus R-123/Mineral Oil, 500 hour Exposure 4. All Materials Except Motorettes.

PICTURES SECTION 7 R-11/Mineral Oil to R-245ca/Polyolester

R-11/MINERAL OIL TO R-245ca/POLYOLESTER PICTURES PICTURE R11/Mineral Oil 500 Hour Exposure. 1. All Materials 2. Nomex-Mylar-Nomex (NMN). Blistered 3. Magnet Wire 4. Oil Sample 5. Motorettes. R11/Mineral Oil 1000 Hour Exposure. 6. All Materials Except Motorettes 7. Nomex-Mylar-Nomex (NMN), Blistered R11/Mineral Oil 500 Hour plus R-245ca/Polyolester 168 hour Exposure 8. All Materials Except Motorettes 9. Nomex-Mylar-Nomex (NMN), Blistered R11/Mineral Oil 500 Hour plus R-245ca/Polyolester 336 hour Exposure 10. All Materials Except Motorettes. 11. Nomex-Mylar-Nomex (NMN), Blistered R11/Mineral Oil 500 Hour plus R-245ca/Polyolester 500 hour Exposure 12. All Materials Except Motorettes. 13. Nomex-Mylar-Nomex (NMN), Blistered 14. Motorettes

PICTURES SECTION 8 R-123/Mineral Oil to R-245ca/Polyolester

R-123/MINERAL OIL TO R-245ca/POLYOLESTER PICTURES PICTURE R123/Mineral Oil 500 Hour Exposure. 1. Sheet Insulation, Sleeving, Tapes, Tie Cords and Lead Wires 2. Magnet Wire 3. Motorettes. R123/Mineral Oil 1000 Hour Exposure. 4. All Materials Except Motorettes 5. Nomex-Mylar-Nomex (NMN), Blistered R123/Mineral Oil 500 Hour plus R-245ca/Polyolester 168 hour Exposure 6. All Materials Except Motorettes 7. Nomex-Mylar-Nomex (NMN), Blistered R123/Mineral Oil 500 Hour plus R-245ca/Polyolester 336 hour Exposure 8. All Materials Except Motorettes. 9. Nomex-Mylar-Nomex (NMN), Blistered R123/Mineral Oil 500 Hour plus R-245ca/Polyolester 500 hour Exposure 10. All Materials Except Motorettes. 11. Nomex-Mylar-Nomex (NMN), Blistered 12. Distillation Apparatus to Recover low Pressure Refrigerants.