Performance Improvement of Window Air Conditioner by using Bottle Neck Arrangement

Similar documents
Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Economical and Energy Efficient Air Conditioner Using Calcium Liquid as a Secondary Refrigerant.

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

UNIT - 3 Refrigeration and Air - Conditioning

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

CHAPTER 1 INTRODUCTION

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

REFRIGERATION TUTOR. OBJECTIVE: To perform test on the refrigeration tutor to determine different COPs and other performance parameters.

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Refrigeration and Air Conditioning

Chapter 10. Refrigeration and Heat Pump Systems

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

CHAPTER 1 INTRODUCTION

(ME-225) HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Numerical Simulation of Window Air Conditioner

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Use this Construction/HVAC Glossary to answer the questions below.

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Thermodynamics I. Refrigeration and Heat Pump Cycles

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Design of LPG Refrigeration System

Energy Use in Refrigeration Systems

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

R07. Answer any FIVE Questions All Questions carry equal marks *****

Sarthak Thakar, 2 R.P.Prajapati 1

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Scientific Journal Impact Factor: (ISRA), Impact Factor: Methodology. [Yadav, 3(9): September, 2014] ISSN:

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

Oyelami S., Bolaji B. O.

Design and Fabrication of Water Refrigeration System by Creating Vacuum

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

Performance Assessment of Water Cooled Condenser Refrigeration System

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

LISTOF EXPERIMENTS. S. No. NAME OF EXPERIMENTS PAGE No.

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Chapter 2. Alternatives to HCFCs and their Characteristics

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

A Comparison Between Refrigerants Used In Air Conditioning

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Design & Fabrication of Hybrid Cooler

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Low GWP Refrigerants for Air Conditioning Applications

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Pressure Enthalpy Charts

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

η second law = Second law efficiency

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

UNIT-III PSYCHROMETRY. Though there are many psychometric terms, yet the following are important from the subject point of view :

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers


EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

INSTITUTE OF AERONAUTICAL ENGINEERING

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

HVAC Fundamentals & Refrigeration Cycle

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Modified Air Cooler with Split Cooling Unit

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

ENERSAVE Hydrocarbon Scroll Water Cooled Chiller

Transcription:

International Journal of Thermal Technologies E-ISSN 2277 4114 2017 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Performance Improvement of Window Air Conditioner by using Bottle Neck Arrangement U Satish Naidu *, R Sam Sukumar and M Venakata Rao Mechanical Engineering Department, BVC Engineering College, Amalapuram Andhra Pradesh State, India Mechanical Engineering Department, Swarnandhra Engineering College, Sitaramapuram, Andhra Pradesh State, India Received 02 July, Accepted 0 Sept 2017, Available online 12 Sept 2017, Vol.7, No.3 (Sept 2017) Abstract In present scenario human comfort is the main criteria. For that purpose many Air conditioners are introduced in the market like window AC, split AC and central AC. Not only for human purpose it is become an essential need for Industrial purpose for both small scale and large scale industries. For common household purposes maximum we use Window AC. But during actual use it is not possible to evaluate the performance of an AC with all the parameters like coefficient of performance and cooling effect. Since these are the main parameters for an air conditioner. Without these calculations it is also not possible to know the factors that affecting on the performance of an air conditioner. So in this thesis main concentration is on investigation on performance parameters of air conditioner, for this purpose window AC test rig is prepared. By using this test rig easy to find out the Actual COP. By adding Bottle Neck Arrangement, in order to improve the performance of air conditioner without any extra amount by using of this simple arrangement, with this theses we save the power improve the cooling effect of wind air conditioner especially in summer user can feel more comfort with this type of air conditioner. Keywords: Air Conditioner, COP, Performance Improvement, Bottle Neck set up. 1. Introduction Air Conditioning 1 Air conditioning is a combined process that performs many functions simultaneously. It conditions the air and transports it and introduces it to the conditioned space. It provides heating and cooling from its central plant or rooftop units. It also controls and maintains the temperature, humidity, air movement, air cleanliness, sound level, and pressure differential in a space within predetermined limits for the comfort and health of the occupants of the conditioned space or for the purpose of product processing. The term HVAC&R is an abbreviation of heating, ventilating, air conditioning, and refrigerating. The combination of processes in this commonly adopted term is equivalent to the current definition of air conditioning. Because all these individual component processes were developed prior to the more complete concept of air conditioning, the term HVAC&R is often used by the industry. 2. Refrigerant development The first air conditioners and refrigerators employed toxic or flammable gases like ammonia, methyl *Corresponding author s ORCID ID: 0000-0002-416-9948 chloride, and propane which could result in fatal accidents when they leaked. Thomas Mid gley, Jr. created the first chlorofluorocarbon gas, Freon, in 1928. The refrigerant was much safer for humans but was later found to be harmful to the atmosphere's ozone layer. Freon is a trademark name of DuPont for any Chlorofluorocarbon (CFC), Hydrogenated CFC (HCFC), or Hydro fluorocarbon (HFC) refrigerant, the name of each including a number indicating molecular composition (R-11, R-12, R-22, R-134). The blend most used in direct-expansion comfort cooling is an HCFC known as R-22. It is to be phased out for use in new equipment by 2010 and completely discontinued by 2020. R-11 and R-12 are no longer manufactured in the US, the only source for purchase being the cleaned and purified gas recovered from other air conditioner systems. Several non-ozone depleting refrigerants have been developed as alternatives, including R-410A, known by the brand name Puron. Innovation in air conditioning technologies continue, with much recent emphasis placed on energy efficiency and improving indoor air quality. As an alternative to conventional refrigerants, natural alternatives like COR-744) have been proposed. The Carrier Air Conditioning Company of America was formed to meet rising demand. Over time air conditioning came to be used to improve comfort in homes and automobiles. Residential sales expanded dramatically in the 190s. 1 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)

U Satish Naidu and R Sam Sukumar 3. Factors affecting Comfort air conditioning The four important factors for comfort air conditioning are discussed as below: 1) Temperature of air: In air conditioning the control of temperature means the maintenance of any desired temperature with in an enclosed space even though the temperature of the outside air is above or below the desired room temperature. This is accomplished either by the addition or removal of heat from the enclosed space has and when demanded. 2) Humidity of air : The control of humidity of air means the decreasing or increasing moisture contents of air during summer or winter respectively in order to produce comfortable and healthy conditions. 3) Purity of air: It is an important factor for the comfort of a human body. It has been noticed that people do not feel comfortable when breathing contaminated air, even if it is within acceptable temperature and humidity ranges. 4) Motion of air: The motion or circulation of air is another important factor which should be controlled, in order to keep constant temperature throughout the conditioned space. It is, therefore, necessary that there should be equip-distribution of air throughout the space to be air conditioned. 4. Window AC These types of AC are designed to be fitted in window sills. A single unit of Window Air Conditioner houses all the necessary components, namely the compressor, condenser, expansion valve or coil, evaporator and cooling coil enclosed in a single box. Since a window AC is a single unit, it takes less effort to install as well as for maintenance. increase the relative humidity of the air, so humidification is not usually built into these systems. If it is necessary, the usual method is to inject steam from electrically boiled water. Fig.2 Window Air Conditioner Working That is all there is to the part of the system in the room. The bit that is more difficult to understand, or at least unfamiliar to most people, is how the cooling fluid is produced and controlled. That is the part on the right of the diagram. The cooling fluid used to be a chlorofluorocarbon compound, and often still is, though they all more or less ravage the earth's ozone layer.. Bottle Necks Fig 1 Wind Air Conditioner Working: A fan draws air from the room first through a cooling device, consisting of metal fins extending from a pipe through which cooling fluid circulates, at a rate determined by the thermostat or by the humidistat. The air next passes over a heater, usually electrical, which is energized on instructions from the room thermostat. Air conditioning has in the past been used where the climate is too hot for comfort. Cooling will Fig. 3 Bottle Necks attached to Thermocol Sheet A nozzle is a device that changes the cross-sectional area of a flow from a large area to a smaller area. With the change in area comes an increase in the flow velocity due to conservation of mass. When the hot air passes through the bottle the air gets compressed, for example blow with your mouth open and feel the air. The compressed air gets cooled instantly. Now blow with your lips pursed and feel the air. The change in temperature using an Bottle Necks is at least 2 degrees Celsius. That may not seem like much, but when in the summer, it makes some of the difference using with air conditioner. 16 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)

U Satish Naidu and R Sam Sukumar 6. Experimentation and Calculation 6.1 Design of air conditioner = (240 X ) X 3.4 = 1200 X 3.4 = 4080 Btu In order to design Air Conditioner we must calculate Heat Load for room which is to be conditioned. Heat Load Amount of heat required to be removed within a certain period, usually 24 hours. Usually measured in British Thermal Unit (BTU) or watts. Heat load calculation Step -1 Calculate the area in square feet of the space to be cooled and multiply by 31.2. Area BTU = length (ft.) X width (ft.) X 31.2 Step - Calculate heat generated by lighting. Find the total wattage for all lighting and multiply by 4.2. Lighting BTU = total lighting watts X 4.2 = (36+36) X 4.2 = 306 Step -6 Total heat load BTU = Area BTU + total window BTU + occupants BTU + equipment BTU + lighting BTU = 8000 + 16 + 1200 + 4080 + 306 = 18742 / 12000 =1.6 Ton = 16 X 16 X 31.2 = 8,000 Btu Step -2 Calculate the heat gain through the windows don t have shading multiply the result by 1.4. North window BTU = area of north facing windows (m 2 ) X 164 = (2 X 2) X 164 = 66 Btu If no shading Btu = North window BTU X 1.4 South window Btu = area of south facing windows (m 2 ) X 868 = 4 X 868 = 3,472 Btu If no shading BTU = south window BTU X 1.4 = 3,472 X 1.4 = 4,860 Total window BTU = north window + south window = 66 + 4860 =,16.8 Btu Step -3 Calculate the heat generated by occupants, allow 600 BTU / person = 4 X 600 = 2400 Btu Step- 4 Calculate the heat generated by each item of machinery copiers, computers, ovens etc. find the power in watts for each item, add them together and multiply by 3.4. Equipment BTU = total equipment watts in X 3.4 Step-7 Divide the heat load by the cooling capacity of the air conditioning unit in BTU, to determine how many air conditioners are needed. Number of a/c units required = total heat load BTU /cooling capacity BTU =1.6 /1. =1.04 ~ 1 Conversion of BTU/hr. to Ton of Refrigeration To convert BTUs to tons, find the BTU capacity of the air conditioner, and divide the BTUs by 12000. Twelve thousand BTUs equals the amount of heat removed by an air conditioner that would melt 1 ton of ice in 24hours, which is called the chiller refrigeration ton, according to the engineering tool box. 6.2 Product Specifications Air conditioner: Specification Nominal capacity: 1. TR at rated test conditions Compressor: Hermetically sealed, Condenser: Forced convection air cooled Evaporator: Forced convection air cooled Expansion device: Capillary tube Thermostat: On panel Energy meter: For compressor provided Pressure gauges: 1 no for suction pressure, 1 no for discharge pressure Temperature indicator: Digital temperature indicator, 6 no s Dry bulb temperature and wet bulb temperature measurement: By sling psychrometer 6.3 Principle of Operation The Air Conditioning Trainer works on Vapour compression Refrigeration cycle using R 22 (HCFC-22) 17 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)

Sl. No. Time Hrs WBT before bottle necks after bottle necks WBT Voltmeter U Satish Naidu and R Sam Sukumar as a refrigerant. The Trainer is having a hermetically sealed compressor, which sucks cold refrigerant vapour from the evaporator. The vapour is compressed to higher pressure and consequently to higher temperature in the compressor. The high pressure and high temperature refrigerant then enters the condenser, where its latent heat is removed by rejecting the heat to the air passing over the forced convection condenser. 7. Relative Humidity: It is the ratio of actual mass of water vapour in given volume of moist air to the mass of water vapour in same volume of saturated air. 8. Dew Point Temperature: It is the temperature of air recorded by the thermometer when the moisture present in it begins to condense. Table 1: Observation Table for Actual C.O.P Inlet Air Temp. o c Outlet air Temp. o c 1. 10:00 33.9 26.1 2.9 24.9 21. 220 10 2. 11:00 33. 27. 2.1 23.2 20. 220 10 3. 12:00 33.3 27. 24.9 23.1 21 220 10 4. 13:00 33.1 27. 2.2 23. 21 220 10. 14:00 32. 26.8 24.7 22.8 19. 220 10 Fig. Window Air Conditioner Test rig The liquefied refrigerant passes through drier (where any residual moisture is absorbed) and enters the expansion device. In the expansion device, (a capillary tube) the refrigerant is throttled to a lower pressure and as a result, the temperature of the refrigerant also reduced. This low temperature wet vapour flows through the evaporator, which is a forced convection air cooled evaporator. Here, the refrigerant picks up heat from air passing over it and gains heat; it evaporates and enters the compressor. This cycle repeats. For measurement of pressures dial type pressure gauges are fitted and to record temperatures digital temperature scanner is incorporate. 6.4 Psychometric Term Experimentation Connect the supply cable to regulated or stabilized power supply. Switch ON the main switch. Put ON the AC. Let the AC run at least for 20 minutes before taking first set of readings. Record the & WBT at the inlet and at the outlet of the air passage. Record the volt meter and ammeter reading. Table 2: Observation Table for Theoretical C.O.P. Sl. No Time Hrs Inlet Air Temp. 0 C Outlet air Temp. 0 C Voltmeter WBT WBT 1. Dry Air: The pure dry air is mixture of number of gases such as Nitrogen, Oxygen, Carbon Dioxide, Hydrogen, Argon and Helium. 2. Moisture Air: It is the mixture of dry air and water vapour. 3. Saturated Vapour: It is mixture of dry air and water vapour when the air has diffused the maximum amount of water vapour in it. 4. Degree of Saturation: It is the ratio of actual mass of water vapour in a unit mass of dry air to the mass of water vapour is same mass of dry air when it is (saturated) at the same temperature.. Humidity: It is the mass of the vapour present in 1 kg of water and generally expressed in terms of grams per kg of dry air. 6. Absolute Humidity: It is the mass of water vapour present in 1 m 3 of dry air and is generally expressed in terms of gm / m3. 1. 10:00 33 27 26 23 220 10 2. 11:00 32. 26. 2. 23 220 10 3. 12:00 32 26. 2 22 220 10 4. 13:00 32 26 2. 21. 220 10. 14:00 31. 2 24 20. 220 10 Table 3: Actual C.O.P. Calculation with Bottle Necks S. No. Time Hrs Pressure Gauge Reading R-22 Refrigerant Temp. 0 C LP HP T3 T4 T T6 1. 10:00 70 320 31.8 90.1 8.3.2 2. 11:00 70 320 31.4 90. 8.7.8 3. 12:00 70 320 31.1 90.3 9.2 6.1 4. 13:00 70 320 30. 91.2 9.6 6.6. 14:00 70 320 31.6 91. 60.3 7.1 18 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)

Sl.No. Volt meter Power (watts) Mass flow rate of air kg/sec Refrigeration Effect (watts) Refrig Effect (H1-H4) Compre ssor I\P (H2-H1) U Satish Naidu and R Sam Sukumar 7. Calculation Calculations Actual C.O.P. 4. Locate these pressures on Y axis of P-H chart. Draw two horizontal lines, one for low pressure and one for high pressure.. Locate particular temperatures on these lines and mark 1,2,3,4. Inlet conditions Inlet Dry Bulb Temperature = 33 0 C Inlet Wet Bulb Temperature = 27 0 C Outlet conditions Outlet Dry Bulb Temperature = 26 0 C Outlet Wet Bulb Temperature = 23 0 C Inlet air enthalpy h 1 = 8. kj/kg (Using Psychometric Chart) Outlet air enthalpy h 2 = 68. kj/kg Enthalpy difference = (H 1-H 2) = 17 kj/kg Mass flow rate of air m = 0.223 kg/s (Constant Value) Refrigeration effect (actual), N = Mass flow rate x enthalpy difference = m X (H1-H2) = 3792.36 w Power input to compressor V = volts from voltmeter = 240 V I = current in amps from ammeter = 9 A W= (VI/1000) = 2200 w Actual Coefficient of Performance C.O.P.=N/W=Refrigeration Effect/Compressor input = 1.72 Table 4: Actual C.O.P. Calculation Actual Pressure Enthalpy Chart for R-22 Refrigerant 6. Find out enthalpies at salient points by referring to X axis of P-H chart. H 1 = 406.8 kj/kg; H 2 = 473.4 kj/kg; H 3 = 274.2 kj/kg ; H 4 = 274.2 kj/kg. (Using R-22 Pressure-Enthalpy Chart ) 7. N= refrigeration effect = H1-H4 = 132.6 kj/kg 8. W= Compressor Work = H2-H1 = 66.6 kj/kg 9. Theoretical C.O.P. = N / W = (H1-H4) / (H2-H1) = 1.99 Sl. No. Table : Theoretical C.O.P. Calculation Enthalpy kj/kg H1 H2 H3 H4 Enthalpy kj/kg H1 H2 1. 406.8 473.4 274.3 274.2 132.6 66.8 2. 404.9 472.1 271.8 271.8 133.1 67.2 3. 402. 469.4 269.7 269.7 132.8 66.9 4. 404. 472.1 271.3 271.3 133.2 67.. 40.2 473.4 271.6 271.6 133.6 67.8 1 220 10 2200 8. 68. 0.22308 3792.36 2 220 10 2200 86.2 69.1 0.22308 3793 3 220 10 2200 87.3 70.3 0.22308 3792. 4 220 10 2200 86. 69.4 0.22308 3793. 220 10 2200 86.8 69.7 0.22308 3793.7 Theoretical C.O.P. Calculation To evaluate theoretical C.O.P. of the system, carry out following procedure. 1. For any set of readings at a particular time, note suction and discharge pressures in psi. 2. Divide these pressures by 14. to convert them into bar. 3. Add barometric pressure of the present location to obtain absolute pressures in bar. Actual COP with Bottle Necks Inlet conditions Inlet Dry Bulb Temperature = 33.9 0 C Inlet Wet Bulb Temperature = 26. 0 C Outlet conditions Outlet Dry Bulb Temperature after bottle necks = 24.9 0 C Outlet Wet Bulb Temperature = 21. 0 C Inlet air enthalpy h1 = 64. kj/kg (Using Psychometric Chart) Outlet air enthalpy h2 = 8. kj/kg Enthalpy difference = (H 1-H 2) = 21 kj/kg Mass flow rate of air m = 0.223 kg/s (Constant Value) Refrigeration effect (actual), N = Mass flow rate x enthalpy difference = m X (H1-H2) X 1000 = 0.22308 X 21 X 1000 = 401.44 w 19 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)

Sl. No. ( 0 C) WBT ( 0 C) RH (%) DP ( 0 C) Hg) V (m 3 kg) H (kj/kg) w (kg/kg of dry air) Sl.No. Volt meter Power (watts) Mass flow rate of air kg/sec Refrigera tion Effect (watts) U Satish Naidu and R Sam Sukumar Power input to compressor V = volts from voltmeter = 220 V I = current in amps from ammeter = 10 A W = (VI/1000) = 2200 w Actual Coefficient of Performance C.O.P. = N/W = Refrigeration Effect / Compressor input = 1.82 Table 6: Actual C.O.P. Calculation with Bottle necks Enthalpy kj/kg 1 220 10 2200 8. 64. 0.22 401 2 220 10 2200 86.2 67.9 0.22 4074 3 220 10 2200 86.6 68.6 0.22 400 4 220 10 2200 8.9 67.9 0.22 4010 220 10 2200 87.1 69 0.22 4033 Table 7: Psychrometric Properties for Actual C.O.P. Inlet 33.9 o\l with B.N Conclusion 24.9 26. 21. H1 PV (mm of 78 23 28 60 14 17. H2 0.9 0 0.8 4 64. 8. 0.023 0.01 For the experimental purpose on the window air conditioner, a test rig have been prepared with all the required accessories. Through this test rig the performance analysis on window air conditioner has done i.e.; Both Theoretical COP and actual COP is calculated. In order to increase the COP of the given window air conditioner a bottle neck arrangement is fitted to the test rig. Through this experiment we found that the COP obtained without bottle neck arrangement is 1.72 and after introducing the bottle neck arrangement it changes to 1.8. References Hamlin S, Hunt R, Tassou SA (1998), Enhancing the performance of evaporative spray-cooling in air-cycle refrigeration & air-conditioning technology, Applied Thermal Engineering,18(11):1139 1148. Giles G R (1998-1999), Environmentally friendly air cycle air conditioning. Proceedings of the Institute of Refrigeration,1-10. Verschoor MJE, editor(2001). Guidelines for the application and design of air cycle systems for heating, ventilating and air conditioning in buildings. Apeldoorn, The Netherlands: TNOMEP; Spence S.W.T, Doran W.J, Artt D.W(2004), Design, construction and testing of an air-cycle refrigeration system for road transport. International Journal of Refrigeration, 27(): 03-10. Spence S.W.T, Doran W.J, Artt D.W (200), Performance analysis of a feasible air-cycle refrigeration system for road transport. International Journal of Refrigeration, 28(): 381 388. S.Klein, F.Alvarado(2000), Engineering equation solver. F- chart software, Middleton,WI M.Huber, J.Gallagher, M.McLinden, G.Morrison(1998), NIST Thermodynamic Properties of Refigerants and Refrigerant Mixtures Version.0. National Insititute of Standards and Technology,USA,. J.E. Braun, P.K. Bansal, E.A. Groll(2002), Energy efficiency analysis of air cycle heat pump dryers. International Journal of Refrigeration (2): 94 96. Mahakdeep Singh, Sandeep Kumar, Manoj Kumar(May 2016) Experimental analysis on window air conditioner with R22 and R407c refrigerants. International Journal of Engineering Research and Development Volume 12, Issue. 160 International Journal of Thermal Technologies, Vol.7, No.3 (Sept 2017)