Performance Study of Triple Concentric Pipe Heat Exchanger

Similar documents
Keywords: Triple tube heat exchanger (TTHE), hot water, cold water, CFD simulation.

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

2. HEAT EXCHANGERS MESA

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

DESIGN AND ANALYSIS OF PIPE HEAT EXANGERS WITH INSIDE FINS

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

CHAPTER 7 COMPARISON OF HEAT EXCHANGERS

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ]

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

American International Journal of Research in Science, Technology, Engineering & Mathematics

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Experimental analysis of condensation heat transfer enhancement of steam at low pressures using modified twisted tape insert

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Global Journal of Engineering Science and Research Management

International Journal of Engineering Research & Technology (IJERT) ISSN: Vol. 2 Issue 10, October

ANALYSING THE EFFECTIVENESS OF THE HEAT EXCHANGER BY INCREASING OVERALL HEAT TRANSFER COEFFICIENT

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Sant Gadge Baba Amravati University. Amravati, Maharashtra, India, Maharashtra 2

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Design, Development and Experimental Investigation of Volumetric Air Receiver

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Effects of Volute Tongue Clearance and Rotational Speed on Performance of Centrifugal Blower Nitin S. Jadhav *, S. R. Patil

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Adsorption refrigeration system using waste heat

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Compression of Fins pipe and simple Heat pipe Using CFD

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Enhancement of COP in Vapour Compression Refrigeration System

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Performance investigation of Air-conditioning system using ejector as expansion device

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Simulation Of Pneumatic Drying: Influence Of Particle Diameter And Solid Loading Ratio

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Design & Development of Tube in Tube Helical Coil Heat Exchanger

Investigation and Optimization of Air Cooled Condenser of Chillers by Replacing Cu to Al Tubes

Experimentation of Heat Pipe Used In Nano-Fluids

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

a Heat Exchanger using FEA Tool

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Pressure drop analysis of Condenser using refrigerants R-134a, R-407C

Heat Exchanger Joule-Thomson Transient Cryogenic Refrigeration. Iranian Journal of Chemical Engineering Vol. 14, No. 3 (Summer 2017), IAChE

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

ENSC 388: Engineering Thermodynamics and Heat Transfer

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Java Development Program on Parallel and Counter Flow Heat Exchanger

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

Transcription:

Performance Study of Triple Concentric Pipe Heat Exchanger #1 Pravin M. Linge, #2 A. B. Korane, #3 V. N. Kapatkar #123 Mechanical Engineering Department, Sinhgad College of Engineering, SPPU, Pune, India Abstract In present study, triple concentric pipe heat exchanger is designed and developed for thermodynamic and hydrodynamic analysis. Researchers have shown that three pipe heat exchanger transfers heat at a higher rate as compared to double pipe heat exchanger. Experimental setup is fabricated to study the two different flow arrangements, called N-H-C and C-H-N. In this paper, three fluids have been considered are hot water, cold water and normal tap water. Flow arrangements are tested for various flow rates of hot and normal water keeping cold water flow rate constant. Overall heat transfer coefficients for cold and normal side are obtained by LMTD method. Objective of this paper is to study heat transfer and pressure drop characteristics for triple concentric pipe heat exchanger with counter flow configuration. Keywords: Triple Concentric Pipe Heat Exchanger, overall heat transfer coefficient I. INTRODUCTION Heat exchangers have several industrial and engineering applications. Heat exchangers are classified in many different types because the equipment type, field of application and design techniques generally differ. The type of heat exchanger to be used is determined by the process and product specifications. Concentric tube heat exchanger plays a major role in fulfilling the needs of heat exchanger in food industry. The most commonly used heat exchanger is double pipe heat exchanger which consists of one pipe inside another pipe placed concentrically. It is used in different products such as dairy, food, beverage and pharmaceutical industries. There are some disadvantages of this exchanger and to overcome this, there is need to enhance the performance of double pipe heat exchanger. Adding an intermediate tube to a double pipe heat exchanger converts it to a triple pipe heat exchanger. Triple concentric pipe heat exchanger has better heat transfer efficiencies and performs better as compared to double pipe heat exchanger. It has larger area per unit length for heat transfer and better overall heat transfer coefficient due to higher fluid velocities in the annular regions. Some researchers have been studied the thermal performance of triple pipe heat exchanger. G. A. Quadir [1] studied the performance of triple concentric pipe heat exchanger numerically using finite volume method. They carried out parametric analysis which shows the effect of one parameter on the heat exchanger keeping other parameters constant. Experimentation of triple pipe heat exchanger is carried out under steady state condition and results are expressed in terms of temperature distribution along the length of heat exchanger by G. A. Quadir [2]. They concluded that N-H-C arrangement is better for heat transfer than C-H-N. Ahmet Unal [3,4,7] carried out theoretical study and case studies on triple pipe heat exchanger and derived the effectiveness-ntu relations. It has been shown that the performance of heat exchanger depends on the relative sizes of three tubes. A basic procedure for calculating overall heat transfer coefficient and length is given by T. M. Ghiwala et al [5]. This study is useful for calculating the dimensions for required temperature drop. O. Garcia-Valladares [6] developed a numerical model considering realistic situations which may be used to optimize the efficiency of triple concentric tube heat exchanger. A set of analytical equations for fluid temperatures along the length of heat exchanger for both parallel and counter flow arrangement was developed by C. A. Zuritz [8]. Simulation shows that by creating annular region in the pipe increases the overall heat transfer efficiency and reduces the length requirement by 25%. Ediz Batmaz [9] concluded that overall heat transfer coefficients and temperature profiles are useful for designing the heat exchanger. V. M. Behera [10] carried out simulation and presented temperature distribution using ANSYS 14 which shows that the better results are obtained with counter flow N-H-C arrangement. An algorithm for the calculation of partial coefficient of heat transfer and correlation for the design purpose of heat exchanger was developed by Sinziana Radulescu [11]. Abdalla Gomma [12] carried out experimental and numerical investigation of triple concentric tube heat exchanger with reference to double pipe heat exchanger and developed CFD model using finite volume discretization method. He concluded that triple tube heat exchanger contributes higher effectiveness and more energy saving per unit length compared with double tube heat exchanger. II. EXPERIMENTAL SETUP A triple concentric pipe heat exchanger is fabricated to carry out experiments. Three pipes of different diameters and lengths are used in the fabrication of the heat exchanger. Outer pipe is made up of stainless steel, middle and inner pipes are of copper. Outside diameters of the three pipes are 0.0254 m, 0.0381 m and 0.0508 m respectively with thickness of each pipe as 1.5 mm only. Length of innermost pipe is 170 cm, middle pipe is 138 cm and that of outer pipe is 101 cm. Baffles are inserted in the middle tube in which hot water flows. In this experiment, three fluids are used namely hot water, normal water and cold water. 2015, IERJ All Rights Reserved Page 1

There are two different flow arrangements namely N-H-C and C-H-N. In N-H-C arrangement, normal water flows through the innermost pipe, hot water flows through the inner annulus formed between 0.0254 m pipe and 0.0381 m pipe and the cold water flows through the outer annulus formed between 0.0381 m pipe and 0.0508 m pipe. This arrangement is called N-H-C configuration of heat exchanger as shown in fig. 1. Fig. 1 Flow directions of three fluids for N H C and C H N arrangements [2] In C-H-N arrangement, cold water flows in the innermost pipe, hot water flows through the inner annulus and the normal water flows through the outer annulus. Outer surface of the heat exchanger in both arrangements is insulated to avoid heat exchange with the surroundings. Two thermostatic heaters of each 3KW are used to heat the water. Hot water is taken at 60 to 65. Normal water is taken from tap water which is available at 29 to 32 and cold water from cooler at 19 to 23. Hot water starts flowing from the tank through the pump then it passes through rotameter measuring the volume flow rate and enters the heat exchanger inlet. Outlet of hot water is collected in another tank and is heated with the help of heater having capacity of 1.5 KW. Similarly, normal and cold water are passed through rotameter measuring the volume flow rate to respective heat exchanger inlet. Two thermocouples are placed at entry and exit of each fluid stream to measure the inlet and outlet temperature. These six thermocouples are connected to digital multipoint temperature indicator. 2.1 Experimental Procedure Fig. 2 Schematic diagram of the experimental setup First of all water is filled in the tank up to certain level and electric heaters having capacity 3 KW are switched on. As thermostatic heaters are used and set to 65, it maintains the constant temperature in the tank. This hot water is pumped by pump and it passes through the rotameter of range 100 to 1000 LPH measuring the flow rate. The mass flow rate of hot water is controlled by flow control valve (FCV) and is supplied at inlet of middle tube. Hot water outlet is collected in another tank having heater of capacity of 1.5 KW. Normal water which is tap water pumped and passed through another rotameter having range 1 to 10 LPM. Similarly cold water is taken form water cooler and supplied to respective exchanger inlet through rotameter of range 0 to 10 LPM. The test is conducted for both N-H-C and C-H-N arrangement with counter flow configuration. The readings are taken in two sets. Cold water is kept constant at 20 LPH for both the sets. In first set, for different constant mass flow rate of normal water from 60 to 195 LPH, hot water is varied from 100 LPH to 400 LPH. In second set, normal water flow rate is varied from 60 to 195 LPH for different flow rates of hot water keeping constant from 100 to 400 LPH. For each fluid, two T type thermocouples are placed at entry and exit. For steady state condition 7-8 min are required. The pressure drop along the heat exchanger is measured by U tube manometer which shows the differences in pressure at inlet and exit of heat exchanger. Pressure drop readings are also taken at various flow rates similar to that of temperature readings. 2015, IERJ All Rights Reserved Page 2

2.2 Mathematical Formulation Fig. 3 Actual experimental setup The basic equations used to describe the thermal characteristics of the triple tube heat exchanger are summarized as follows: The heat transfer rate of the hot water through the inner annulus is calculated as follows: The heat transfer rate of the cold water in the inner tube is calculated as: The heat transfer rate of the normal water in the outer annulus is calculated as: (1) (2) (3) The heat transfer rate between the cold, normal and hot water for the triple concentric-tube heat exchanger is as follows: (4) The average heat transfer rate, is determined between the three fluid sides as: Where is the aggregate of the cold and normal tap water heat transfer rate as: The heat transfer coefficient of the inner annulus is calculated from: The average log-mean temperature difference between the three fluids is calculated from: (8) (5) (6) (7) Where is the log-mean temperature difference between hot and cold water while is the log-mean temperature difference between hot and normal tap water. Nusselt number is determined from: The effectiveness of the triple tube heat exchanger is calculated as: (10) (9) The friction factor of the inner annulus of the triple concentric-tube is calculated as: (11) 2015, IERJ All Rights Reserved Page 3

III. RESULTS AND DISCUSSION In this section, triple pipe heat exchanger is analyzed for temperature variation, heat transfer rate and pressure drop. Various test were performed to determine heat transfer in triple pipe having counter flow arrangement with normal water flowing through inner pipe, hot water through inner annulus and cold water through outer annulus. 3.1 Overall Heat Transfer Coefficients Fig. 4 represents the comparison between cold side overall heat transfer coefficient with hot water Reynolds number when normal water mass flow rate is kept constant at 60, 120 & 180 LPH and cold water flow rate at 20 LPH. As seen from the graph, overall heat transfer coefficient increases with increase in Reynold number when normal and cold water flow rate kept constant. If mass flow rate of normal water is increased from 60 to 120 LPH keeping constant, overall heat transfer coefficient is decreased to some extent. Similarly, it is decreased for constant flow rate 180 LPH because heat transfer rate is more for normal side and less for cold side. Fig. 4 Variation of cold side overall heat transfer coefficient with hot water Reynold number Fig. 5 shows the variation of overall heat transfer coefficient for normal side with hot water Reynold number when normal and cold water mass flow rate kept constant. From Fig. 5, it is observed that overall heat transfer coefficient is increased when Reynold number is increased while keeping normal water mass flow rate at 60 LPH and cold water at 20 LPH. When mass flow rate of normal water is increased from 60 to 120 LPH, overall heat transfer coefficient is increased as compared to that at 60 LPH. When normal water mass flow rate is at 180 LPH, it is again increased because more heat is transferred to normal side as compared to cold side. Experimental values of cold side and Normal side heat transfer coefficient are found in well agreement with literature, with a percentage deviation of 10-15%. Fig. 5 Variation of normal side overall heat transfer coefficient with hot water Reynold number 2015, IERJ All Rights Reserved Page 4

3.2 Average Heat Transfer Rate Fig. 6 shows the variation of average heat transfer rate with hot water Reynold number for constant cold and normal water mass flow rate. Fig. 6 Variation of average heat transfer rate with hot water Reynold number It is clear that, average heat transfer rate increases with increase in hot water Reynold number when normal and cold water flow rate remains constant. As mass flow rate of normal water increases average heat transfer rate also increases. Average heat transfer rate is more for 180 LPH as that of 60 and 120 LPH. 3.3 Pressure Drop Fig. 7 shows the variation of hot water pressure drop with hot water Reynolds number. It is observed from the figure that pressure drop is continuously increasing with hot water Reynolds number. Large pressure drop is observed because baffles are placed in the inner annulus through which hot water flows. A baffle increases the pressure drop. The pressure drop is 666.65 Pa at Reynolds number 2508 and it is 5199.87 Pa at Reynolds number 10034. Fig. 7 Variation of hot water pressure drop with hot water Reynolds number Fig. 8 shows the variation of normal water pressure drop with normal water Reynolds number. From the figure, it is clear that pressure drop of normal water increases with normal water Reynolds number. Less pressure drop is observed as compared to hot water because in the inner pipe (normal water) no baffles are used. Pressure drop is increased from 333 Pa to 519 Pa when Reynolds number is increased from 1193 to 3513. Also it is clear from the graph that, testing of the heat exchanger is done, for the maximum value of pressure drop. Results of pressure drop agree considerably with that of the literature values, with a percentage deviation of 10-15%. 2015, IERJ All Rights Reserved Page 5

Fig. 8 Variation of normal water pressure drop with normal water Reynolds number IV. CONCLUSIONS An experimental study has been carried out to investigate the heat transfer performance and pressure drop of triple concentric pipe heat exchanger. The mass flow rate of hot water in the inner annulus and normal water in the inner pipe are varied during experiment. Effect of mass flow rate on heat transfer characteristics and pressure drop are considered. With increase in hot water Reynolds number, both normal and cold side overall heat transfer coefficient increases. But with increase in normal water mass flow rate, normal side overall heat transfer coefficient increases and cold side heat transfer coefficient decreases. Average heat transfer rate increases with hot water Reynolds number and normal water mass flow rate. Hot water pressure drop is more than normal water pressure drop because of baffles in the inner annulus and higher values of mass flow rate. Also the heat transfer coefficients pressure drop agrees considerably, with that of the literature values with percentage deviation of about 10-15%. REFERENCES 1. G.A. Quadir, Irfan Anjum Badruddin, N.J. Salman Ahmed, (2014), Numerical investigation of the performance of a triple concentric pipe heat exchanger, International Journal of Heat and Mass Transfer, 75, 165-172. 2. G.A. Quadir, Saqab S. Jarallah, N.J. Salman Ahmed, Irfan Anjum Badruddin, (2013), Experimental investigation of the performance of a triple concentric pipe heat exchanger, International Journal of Heat and Mass Transfer, 62, 562-566. 3. Ahmet Unal, (1998), Theoretical analysis of triple concentric tube heat exchangers Part 1: Mathematical Modelling, Int. Comm. Heat Mass Transfer, Vol. 25, No. 7, 949-958. 4. Ahmet Unal, (2001), Theoretical analysis of triple concentric tube heat exchangers Part 2: Case Studies, Int. Comm. Heat Mass Transfer, Vol. 28, No. 2, 243-256. 5. Tejas M. Ghiwala, Dr. V. K. Matawala, (2014), Sizing of triple concentric pipe heat exchanger, International Journal of Engineering Development and Research, Vol. 2, 1683-1692. 6. O. Garcia- Valladares, (2004), Numerical simulation of triple concentric tube heat exchangers, International Journal of Thermal Sciences, 43, 979-991. 7. Ahmet Unal, (2003), Effectiveness-NTU relations for triple concentric tube heat exchangers, Int. Comm. Heat Mass Transfer, Vol. 30, No. 2, 261-272. 8. Carlos A. Zuritz, (1990), On the design of triple concentric tube heat exchangers, Journal of Food Process Engineering, 12, 113-130. 9. Ediz Batmaz, K.P. Sandeep, (2005), Calculation of overall heat transfer coefficients in a triple tube heat exchanger, Heat Mass Transfer, 41, 271-279. 10. Vishwa Mohan Behera, D. H. Das, Ayusman Nayak, Numerical Analysis of triple tube heat exchanger using Ansys, International Journal of Scientific & Engineering Research, Vol. 5, 1226-1231. 2015, IERJ All Rights Reserved Page 6