TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

Similar documents
RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

SIGMADEK, LTD. FIRE TEST REPORT

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

FUNDERMAX GMBH FIRE TEST REPORT

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

We Identify and S.T.O.P. Your Noise Problems

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

ENGINEERING EVALUATION

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

Refrigerating Appliance DOE Test Report

Fire Performance of Translucent Systems

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

January 26, Mr. Larry Sunshine Bentax USA 418 Meadow Street Fairfield CT Dear Mr. Sunshine:

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK 13045

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

Acoustical Surfaces, Inc.

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report of Surface Burning Characteristics Test on Acoustical Panel

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

Declaration of Conformity

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

REPORT Dialight, 1501 Route 34 South, Farmingdale, NJ 07727

Refrigerating Appliance ErP Test Report

Abrasion Resistance of Fluoropolymer and polyester Coatings

GUARDIAN FIRE TESTING LABORATORIES, INC.

Materials Testing by Gregory Havel

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

BCTC CARPET TECHNICAL CENTRE

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Classification of Fire Performance of Wall and Ceiling Lining Materials

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

Public Comment No. 2-NFPA [ Section No ]

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

FLASHLIGHT ANSI STANDARDS

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

NF X : Parts 1, 2, 3, 4 & 5

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

Food Service Technology Center

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

BS EN : 2001 & IEC :2000

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles

TEST REPORT IEC Safety of laser products - Part 1: Equipment classification and requirements

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

Review Fire Test Report

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.


Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

This document is a preview generated by EVS

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

SECTION SECURITY TESTING AND COMMISSIONING

Transcription:

REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc. 8302 Espresso Drive, Suite 130 Bakersfield, CA 93312 PRODUCT EVALUATED: CT-XXXX Ceiling Tiles EVALUATION PROPERTY: Surface Burning Characteristics Report of testing CT-XXXX Antique Finish Ceiling Tiles for compliance with the applicable requirements of the following criteria: ASTM E84-12c, Standard Test Method for Surface Burning Characteristics of Materials. This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. 1

Report No. 101145164COQ-005 Page 2 of 10 1 Table of Contents PAGE 1 Table of Contents...2 2 Introduction...3 3 Test Samples...3 3.1 SAMPLE SELECTION...3 3.2 SAMPLE AND ASSEMBLY DESCRIPTION...3 4 Testing and Evaluation Methods...4 4.1 TEST STANDARD...4 5 Testing and Evaluation Results...5 5.1 RESULTS AND OBSERVATIONS...5 6 Conclusion...6 APPENDIX A Data Sheets...2 Pages REVISION SUMMARY

Report No. 101145164COQ-005 Page 3 of 10 2 Introduction Intertek Testing Services NA Ltd. (Intertek) has conducted testing for udecor Inc., to evaluate the surface burning characteristics of CT-XXXX Antique Finish Ceiling Tiles. Testing was conducted in accordance with the standard methods of ASTM E84-12c, Standard Test Method for Surface Burning Characteristics of Materials. This evaluation began April 25, 2013 and was completed the same day. 3 Test Samples 3.1. SAMPLE SELECTION Samples were submitted to Intertek directly from the client and were not independently selected for testing. The sample materials were received at the Evaluation Center on April 22, 2013. 3.2. SAMPLE AND ASSEMBLY DESCRIPTION Upon receipt of the samples at the Intertek Coquitlam laboratory, they were placed in a conditioning room where they remained in an atmosphere of 23 ± 3 C (73.4 ± 5 F) and 50 ± 5% relative humidity. The sample material consisted twelve 24 in. by 24 in. PVC ceiling tiles, and were identified by the client as CT-XXXX Antique Finish Ceiling Tiles. The tiles were brown in color. For this trial run, twelve 24 in. by 24 in. PVC ceiling tiles were placed on the upper ledge of the flame spread tunnel. The sample material was supported by ¼ in. steel rods spaced every 24 in. and 20 ga. 2 in x 2 in galvanized steel netting spanning the upper ledge of the flame spread tunnel. A layer of 6 mm reinforced cement board was placed over top of the samples, the tunnel lid was lowered into place, and the samples were then tested in accordance with ASTM E84-12c.

Report No. 101145164COQ-005 Page 4 of 10 4 Testing and Evaluation Methods 4.1. TEST STANDARD The results of the tests are expressed by indexes, which compare the characteristics of the sample under tests relative to that of select grade red oak flooring and inorganic-cement board. (A) Flame Spread Classification: This index relates to the rate of progression of a flame along a sample in the 25 foot tunnel. A natural gas flame is applied to the front of the sample at the start of the test and drawn along the sample by a draft kept constant for the duration of the test. An observer notes the progression of the flame front relative to time. This information is plotted on a graph (flame spread curve). The test apparatus is calibrated such that the flame front for red oak flooring passes out the end of the tunnel in five minutes, thirty seconds (plus or minus 15 seconds). (B) Smoke Developed: A photocell is used to measure the amount of light, which is obscured by the smoke passing down the tunnel duct. When the smoke from a burning sample obscures the light beam, the output from the photocell decreases. This decrease with time is recorded and compared to the results obtained for red oak, which is defined to be 100.

Report No. 101145164COQ-005 Page 5 of 10 5 Testing and Evaluation Results 5.1. RESULTS AND OBSERVATIONS (A) Flame Spread The resultant flame spread classifications are as follows: (Classification rounded to nearest 5) Sample Material Flame Spread Flame Spread Classification CT-XXXX Antique Finish Ceiling Tiles 1 0 (B) Smoke Developed The areas beneath the smoke developed curve and the related classifications are as follows: (For smoke developed indexes 200 or more, classification is rounded to the nearest 50. For smoke developed indexes less than 200, classification is rounded to nearest 5) Sample Material Smoke Developed Smoked Developed Classification CT-XXXX Antique Finish Ceiling Tiles 192 190 (C) Observations During the test, the sample surface ignited at approximately 59 seconds; the flame began to progress along the sample until it reached the maximum flame spread.

Report No. 101145164COQ-005 Page 6 of 10 6 Conclusion The samples of CT-XXXX Antique Finish Ceiling Tiles, submitted by udecor Inc, exhibited the following flame spread characteristics when tested in accordance with ASTM E84-12c, Standard Test Method for Surface Burning Characteristics of Materials. Sample Material Flame Spread Classification Smoke Developed Classification CT-XXXX Antique Finish Ceiling Tiles 0 190 The conclusions of this test report may not be used as part of the requirements for Intertek product certification. Authority to Mark must be issued for a product to become certified. INTERTEK TESTING SERVICES NA LTD. Tested and Reported by: Greg Philp Technician Building Products Reviewed by: Scott Leduc, EIT Test Engineer Building Products

Report No. 101145164COQ-005 Page 7 of 10 APPENDIX A DATA SHEETS

Report No. 101145164COQ-005 Page 8 of 10 ASTM E84-12c DATA SHEETS

Report No. 101145164COQ-005 Page 9 of 10 ASTM E84-12c DATA SHEETS

Report No. 101145164COQ-005 Page 10 of 10 REVISION SUMMARY DATE PAGE SUMMARY April 25, 2013 All Original Issue Date