Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Similar documents
Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

A/C Cooling Load calculation and measurement

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Alpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018

Air Conditioning Clinic

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

RT-OA TM Rooftop Outdoor-Air (DOAS)

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

2. In areas of the world where outdoor temperatures are low enough to drop the interior building temperature below setpoint.

Dehumidification for Industrial Coating Applications. By: Jay Kranker Munters MCS

Department of Mechanical Engineering ME 322 Mechanical Engineering Thermodynamics

Designing Energy Efficient Outdoor Air Systems

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

CE311 Fall 2016 Mid-Term Exam 1

LOW COST FOOD STORAGE TECHNOLOGY: ENERGY SAVINGS AND PRODUCE STORAGE QUALITY. Ben Weil Luke Doody University of Massachusetts Amherst

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Chapter 8 Balances on Nonreactive Processes PSYCHROMETRIC CHART

Air Conditioning Clinic. Psychrometry One of the Fundamental Series TRG-TRC001-EN

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Pharmaceutical Facility Design

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Technical Development Program

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

RT-OA TM Rooftop Outdoor-Air (DOAS)

CE311 Fall 2016 Mid-Term Exam 1

Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1

Thermo-physical properties found on most psychrometric charts

HVAC Psychrometric Analysis to Avoid Moisture Problems

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Trane CDQ Desiccant Dehumidification

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

Chapter 14, Problem 27.

Energy Recovery Ventilators

EarthWise System Seminar

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Munters Heat Exchangers

100% Outdoor Air Dehumidification Methods

UTAH ASHRAE CHAPTER ENERGY EFFICIENCY

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Energy Use in Refrigeration Systems

FIELD TEST OF HYBRID ROOFTOP UNIT PHASE 1

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Humidity Control & Psychrometrics

Pressure Enthalpy Charts

When Duct Sealing Kills HVAC Equipment and Efficiency

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Company Acme HVAC Inc. Customer James Allen Preparer J White Address 3652 Shady LaneAnywhere, Earth Phone

To Keep Docs Cool, Dry and Happy

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Optimizing Electric Humidifier Operation with an Air Side Economizer

MANUAL J/S Summary One summary sheet for each system

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Psychrometric Engineering Applications

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

UNIT-III PSYCHROMETRY. Though there are many psychometric terms, yet the following are important from the subject point of view :

Managing HVAC in High Performance Buildings

Relative Humidity in Schools Jim Cummings and Chuck Withers

Adding More Fan Power Can Be a Good Thing

ECONOMIZER CONTROLLER ET-858

Armstrong Cool-Fog Systems

In Search of Indoor Comfort

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

Dehumidification: Energy Efficiency Comparisons

ERVB ENERGY RECOVERY VENTILATORS. Form No. PDS ERV.64.1

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Use this Construction/HVAC Glossary to answer the questions below.

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Product Data ERVC. Energy Recovery Ventilators. Features

HVAC Fundamentals & Refrigeration Cycle

HVAC Myths and Realities Trane Engineers Newsletter Live Series

Building Systems: HVAC

FACTORY INSTALLATION (CW-160) Indirect evaporative air conditioner 100% outside air

ELECTRICAL QUANTITY WEIGHT (LB)

There are (at least) four reasons why you need to understand moisture and humidity in building physics:

Transcription:

Fundamentals of Psychrometrics By James L. Murphy, Colorado Building Environments Sales Engineer

Let s s Start with Air Air is Made up of Two Main Gases Nitrogen (77%) Oxygen (23%) If that is all there was HVAC Calculations would be easy Cooling BTU s s = (T 2 -T 1 )*1.085*CFM But there is One other element Water Vapor How do we account for Water Vapor? Psychrometric Chart

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Dry Bulb Temperature Lines 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Wet Bulb Temperature Lines 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Relative Humidity Lines 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Saturation Temperature 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Grains Of Moisture Lines 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

Enthalpy What Is Enthalpy The Total Heat Content of the air and water Vapor Why is it Important? The more Heat Content in the air the Harder it is to cool The Less Heat Content in the air the easier it is to cool

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Enthalpy Lines 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

Plotting Points On the Psychrometric Chart Only need two of the following to Plot a point DB Temp, WB Temp, RH%, Grains Of Moisture Once the Point is plotted, You can find all the other information

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

Mixed Air Temperatures Plot both Outdoor air and Return Air on Chart Draw a line between the two Points What ever the percentage of RA is, it is the same percentage down the line from RA to OA

¾ B A ¼ D ½ C ½ AIR MIXING PROCESS

Heating and Cooling Sensible Heating, Cooling No moisture in the air Gained or Lost Sensible Heat= 1.085*CFM(dT) OR Sensible Heat = 4.5*CFM*(Enthalpy 1 -Enthalpy 2 ) Enthalpy = H

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Sensible Cooling 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

Air Flow 0 DB B A DB WB h A h B 54 WB DP DP Heating Coil SENSIBLE HEATING A B

A 0 DB Air Flow WB DB 54 WB B h B h A DP DP Cooling Coil B A SENSIBLE COOLING

Latent Heat Occurs when Water is evaporated or Condensed and the dry bulb temperature does not change Adds to cooling needed to produce the dry bulb

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Latent Cooling 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

Total Heating, Cooling Sensible + Latent = Total Total = 4.5*CFM*(H 1 -H 2 )

SATURATION TEMPERATURE - F 75 85 90 95 0 5 1 Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - F.0.024.023.022.021.0.019 HUMIDITY RATIO - POUNDS OF MOISTURE PER POUND OF DRY AIR Total Cooling 1 1 1 1 1 1 1 0 90.018.017.016.0.014.013.012.011.0.009.008.007.006.005.004.003.002.001.000 17.5 75 WET BULB TEMPERATURE - F PSYCHROMETRIC CHART Normal Temperature I-P Units 00 FEET BAROMETRIC PRESSURE: 24.896 in. HG 75 90% % % % % % HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR 17.0 16.5 VOLUME-CU.FT. PER LB. DRY AIR % % % RELATIVE HUMIDITY.0 16.0.5

q t q s q D A E SHF = 0.67 B C Total Cooling

Why is the Psychrometric Chart useful Let s s Say an Engineer s s Schedule calls for a cooling coil to cool 00 CFM from degrees dry bulb and 67 degrees wet bulb to db degrees and wants 42 MBH Total Cooling at 00 Altitude. Why is this a problem? Total Cooling=(/16.5)*00*(- 24.6)=38.4 MBH

Why is the Psychrometric Chart useful Let s s Say an Engineer wants to put a humidifier in the duct work of a VAV unit down stream of the VAV box. The air is supplied at degrees and the space needs to be kept at degrees and % RH Why is this a problem? At degrees the max grains of moisture per lb of dry air is grains. At degrees at % RH the air has 93 Grains/Lb of Dry air

Real world applications Cooling coil Total CFM =,000 OA =% At 95/63 RA = 75% at 75/58 LA = Find Mixed air Temp Find LAT WB, RH%, LA Enthalpy Find Sensible and Latent Load

Real World Aplication Direct Evap Cooling Unit 1 is 0% OA in Denver, at 00 CFM with a temperature of 95/63 and is 90% effective Find LAT Unit 2 is 0% OA in Nashville, at 00 CFM with a Temperature of 95/77 and is 90% effective Find LAT

A 95 DB Air Flow B B C % R.H. 73 WB 74.1 DB D E 73 WB 63.3 DP Sprays Complete Saturation A Humidifier Direct Evap Cooling B' D' A'

Real World Applications Indirect/Direct Evap Cooling How can you get colder Temperatures out of this system Lets do a rough plot to see