Fan Arrangements, Rotation, Discharge and Motor Position

Similar documents
Selecting the Correct Fan

MXI Mixed Flow Inline Fan

Twin City Fan & Blower

Centrifugal Fans, Non-Overloading, Backward Inclined

Introduction to Fans. The Basics of Fan Principles and Terminology

CENTRIFUGAL BLOWERS & FANS TM MITTAL ENGINEERING

DAE Systems. Fan Selection Guide. Section 1: Terminology

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

LN series STERLING PUMPS. Horizontal Split Case Pumps. Double Volute. Single Stage.

MACHINERY BLOCKING RECOMMENDATIONS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

Fans: Features and Analysis

Glossary of Terms Laboratory & Fume Exhaust Fans

7697 Snider Road, Mason, OH Telephone:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

FAN ENGINEERING. Sealing of Fan Housings

Centrifugal Pumps acc. to EN / ISO 2858 with Shaft Sealing Type NCL

Air Make-Up Units. Product Line Overview & Capabilities

Rich Knoelke. Questions or Comments: Mulcahy Shaw Water.

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

MLR SERIES MODULAR AIR HANDLING UNITS

Installation and Maintenance Manual IM 782-8

Centrifugal Pumps acc. to DIN EN ISO 2858 with Shaft Sealing Type NCL

Evase Vaneaxial Fans 500mm to 1400mm Diameter Bulletin ECA 10-07

WIDEST RANGE OF INDUSTRIAL & AIR CONDITIONER PACKAGED FAN!

MODEL 652A MODEL 654A MODEL 652A MODEL 653A MODEL 651A AURORA. 650 Series SINGLE STAGE SOLIDS HANDLING PUMPS

JM Aerofoil Fans Bulletin JMA60-05

MCV - MCH - MCHZ Multistage pumps

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

McQuay. Roofpak Roof Mounted Air Handler Draw- Through. RDS Size: 900 Vintage: B. Last Manufactured: 1998

Catalog Destiny Indoor Air Handler. Models Horizontal Configuration. Vertical Configuration

N N O V A T I O N E F F I C I E N C Y Q U A L I T Y. In-Line Pumps IIL / IVP / IVP-CC

RSIB Power Venter

SECTION (15833) - HVAC POWER VENTILATORS

SECTION STEAM CONDENSATE PUMPS

ECO-ANT21 Corporation

BULLETIN G-99. March 2005 CONDENSED CATALOG. Air Moving Products

VRD. Sump pump for polluted liquids

IPVB EC inline power venter

HTM Circulation Pumps acc. to DIN EN 733 Type NKX

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

SPIRAL FREEZING & CHILLING SYSTEMS

FAN ENGINEERING. Fan Installation, Operation & Maintenance

ENERVEX IPVB INLINE POWER VENTER

AIR COMPACT. Air handling units. Ultra high performance USE RANGE DESCRIPTION

Twin City Fan & Blower

COMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Fans in VAV Systems

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Codes and Standards that are Standard at the University:

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

CAP SERIES SEWAGE AND WASTE WATER PUMPS

Fan Array Systems WHITE PAPER. Rad Ganesh, PhD, P.E. Director, R&D / Applications Twin City Fan Companies, Ltd. Minneapolis, MN, United States

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

ENERVEX RSV CHIMNEY FAN

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

Industrial Fans & Blowers

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

Stulz CyberMOD EC Fan Retrofit Kit Switch & Save


RSV Chimney Fan USA CAN. Start Up and Configuration. ... Chapter 5. Maintenance and Troubleshooting... Chapter 6. Job Name: Installer:

English CNA-CNB. Centrifugal fans Installation and maintenance

Centrifugal Blower. Backward/Aerofoil Curved.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Understanding Fan System Effects

PART 1 - GENERAL 1.1 WORK INCLUDED

Modular Supply Make-Up Air Unit

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

AGN 088 Air Flow and Cooling

ENVIRO UNIT ENGINEERING MANUAL KES SERIES

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)

This label warns for risk of electrical shock when failing to observe.

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

Plenum Fans. Model HPA. Direct Drive

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

Horizontal Split Case Pumps Type U

SAM TURBO INDUSTRY LIMITED

With the world-renowned SIGMA PROFILE

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

Product Introduction...D85. Benefits...D87. Construction Details...D89. Custom Features & Options...D91. Accessories...D93. Engineering Data...

Specially Designed Waste Water & Sewage Pumps

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

CPO N N O V A T I O N E F F I C I E N C Y Q U A L I T Y. ASME/ANSI B73.1 Chemical Process Pump. Springer Pumps, LLC

FAN ENGINEERING. Fan Installation, Operation & Maintenance

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

MAGNETIC DRIVE PUMPS AMERICA S MOST VERSATILE LINE OF CENTRIFUGAL PUMPS THINK QUALITY...THINK DELIVERY...THINK PRICE

SUMY Catalogue. Product Line. Centrifugal Pumps СУМЫ SUMY ENGINEERING WORKS Ltd PUMPING EQUIPMENT DESIGN, MANUFACTURE AND SALE

The Experts in Vacuum Solutions

N N O V A T I O N E F F I C I E N C Y Q U A L I T Y CPO. Open Impeller ASME (ANSI) B73.1 Pump for continuous use in Chemical Process Services

ENGINEERING LETTER 4

1 1/8 Inch Centrifugal Pump Operation and Maintenance Guide

Transcription:

FAN ENGINEERING Information and Recommendations for the Engineer Fan Arrangements, Rotation, Discharge and otor Position FE-3900 Introduction Fan arrangements and classes are industry standards that have been determined by ACA (Air ovement and Control Association) to communicate the operating condition that a fan is capable of, the location of the bearings, and drive configurations. Drive Arrangements for Centrifugal Fans Adapted from ACA Standard 99-2404-03, with written permission from Air ovement and Control Association Description Fan Configuration Alternative Fan Configuration Arrangement 1 SWSI overhung on shaft, two bearings mounted on pedestal base. independent pedestals, with or without inlet box. Arrangement 2 SWSI overhung on shaft, bearings mounted in bracket supported by the fan casing. Alternative: With inlet box. Arrangement 3 SWSI mounted on shaft between bearings supported by the fan casing. independent pedestals with inlet box and designated as Arr. 3 SI. Arrangement 3 DWDI mounted on shaft between bearings supported by the fan casing. independent pedestals with inlet box and designated as Arr. 3 DI. 2006 Twin City Fan Companies, Ltd.

Drive Arrangements for Centrifugal Fans (continued) Description Fan Configuration Alternative Fan Configuration Arrangement 4 SWSI For direct drive. Impeller overhung on motor shaft. No bearings on fan. otor mounted on base. Alternative: With inlet box. Arrangement 7 SWSI For coupling drive. Generally the same as Arrangement 3, with base for the prime mover. independent pedestals with inlet box and designated as Arr. 7 SI. Arrangement 7 DWDI For coupling drive. Generally the same as Arrangement 3, with base for the prime mover. independent pedestals with inlet box and designated as Arr. 7 DI. Arrangement 8 SWSI For direct drive. Generally the same as Arrangement 1, with base for the prime mover. independent pedestals, with or without inlet box. Arrangement 9 SWSI For belt drive. Impeller overhung on shaft, two bearings mounted on pedestal base. otor mounted on the outside of the bearing base. Alternative: With inlet box. Arrangement 10 SWSI For belt drive. Generally the same as Arrangement 9 with motor mounted inside of the bearing pedestal. Alternative: With inlet box. 2 Engineering Data 3900

Drive Arrangements for Tubular Centrifugal Fans Adapted from ACA Standard 99-2410-03, with written permission from Air ovement and Control Association Description Arrangement 1 For belt drive. Impeller overhung on a shaft supported by bearings mounted within casing. otor mounted independent of casing. Horizontal discharge. otor Left View Facing Outlet Arrangement 3 For belt drive. Impeller center-hung on a shaft supported by bearings mounted within casing. Designed for mounting of motor on outside of casing in one of the standard locations shown. For horizontal and vertical discharge. Duct mounting shown. View Facing Outlet Arrangement 4 For direct drive. Impeller overhung on motor shaft. otor supported within casing. For horizontal or vertical discharge. Duct mounting shown. View Facing Outlet Arrangement 9 For belt drive. Impeller overhung on a shaft supported by bearings mounted within casing. Designed for mounting of motor on outside of casing in one of the standard locations shown. For horizontal and vertical discharge. Duct mounting shown. otor Shown in Position 360 360 315 45 270 90 225 135 180 View Facing Outlet Arrow designates the direction of airflow. Rotation of fans is determined by viewing from the fan outlet end. Specify either upblast or downblast discharge for vertically-mounted fans. The locations of motors, supports, access doors, etc., are determined by viewing the outlet of the fan and resting location 180 on the floor as shown for Arrangement 9. Arrangements 4 and 9 can be furnished with supports for floor, wall, or ceiling mounting. The position of these supports determines which motor locations are available for motor placement. Generally, motor locations 135, 180, and 225 are not available on floor, wall, or inverted ceiling-mounted fans and motor locations 45, 90, 270, and 315 may not be available for ceiling-hung fans. Another method of mounting vertical fans is shown in the view on the right. Specify fan to be furnished with ceiling-mounting brackets, floor mounting brackets, or both. Vertical ounting Ceiling-ounting Brackets Floor-ounting Brackets 3 Engineering Data 3900

Drive Arrangements for Axial Fans Adapted from ACA Standard 99-3404-03, with written permission from Air ovement and Control Association Description Fan Configuration Alternative Fan Configuration Arrangement 1 overhung on shaft, two bearings mounted either upstream or downstream of the impeller. Alternative: Single stage or two stage fans can be supplied with inlet box and/or discharge evase. Arrangement 3 mounted on shaft between bearings on internal supports. Alternative: Fan can be supplied with inlet box and/or discharge evase. Arrangement 4 For direct drive. Impeller overhung on motor shaft. No bearings on fan. otor mounted on base or integrally mounted. Alternative: With inlet box and/or discharge evase. Arrangement 7 For direct drive. Generally the same as Arrangement 3 with base for the prime mover. Alternative: With inlet box and/or discharge evase. Arrangement 8 For direct drive. Generally the same as Arrangement 1 with base for the prime mover. Alternative: Single stage or two stage fans can be supplied with inlet box and/or discharge evase. Arrangement 9 For belt drive. Generally the same as Arrangement 1 with motor mounted on fan casing, and/or an integral base. Alternative: With inlet box and/or discharge evase. 4 Engineering Data 3900

Non-ACA Specified Arrangements Arrangement 3F DWDI or SWSI Standard arrangement 3 DWDI/SWSI fan with integral floor motor mount. Additional convenience of motor mounted on integral sub-base, for mounting on vibration isolators, generally springs. Arrangement 9F Standard arrangement 9 SWSI fan with integral floor motor mount. Additional convenience of motor mounted on integral sub-base. Intended for rigid floor mounting. Advantages and Disadvantages of Fan Arrangements Arrangement 1 Allows versatility, can be direct or belt driven with the motor mounted on a separate pedestal. Bearings out of the airstream allow for high temperature operation. The option of using belt drives allows for speed adjustment in case of a performance deficit. The motor must be mounted separately or a unitary base is provided. Arrangement 2 Same as Arrangement 1, as far as direct or belt driven and speed adjustment through drive change. In addition, the pedestal bearing is shorter, which makes a smaller assembly. A shorter pedestal is less robust at high fan speeds, therefore Arrangement 2 should be used for low speed fans only. The motor must be mounted separately or a unitary base is provided. Arrangement 3 Does not have a pedestal. Bearings are mounted in the inlet and drive, usually on a bearing bar, so it has a small footprint. Can be direct or belt driven. Bearings in the airstream restrict the airstream temperature to about 130 F. The motor must be mounted separately or a unitary base is provided. Bearings may be moved out of the airstream by using inlet boxes but this increases the size of the footprint. Arrangement 4 ounting the impeller on the motor makes a compact assembly, but restricts airstream temperature to about 180 F. (The airstream temperature will be passed directly to the motor shaft and bearings.) Generally, Arrangement 4 must only be used with small fan wheels. Arrangement 7 Similar to the Arrangement 3, Arrangement 7 does not have a bearing pedestal, small footprint, or direct drive, so speed up must be achieved by using a variable speed device (ie. VFD). Limited to 130 F unless inlet boxes are used. A motor pedestal may be incorporated in the fan structure. Arrangement 8 Offers the same benefits regarding high temperature as Arrangement 1. The motor pedestal is incorporated into the fan structure. Arrangement 9 Speed changes are possible since a belt drive is used. The motor is mounted on the side of the pedestal to make the fan and driver a compact unit. Larger motors cannot be mounted in this arrangement or special provisions must be made. Arrangement 10 Provides the benefits of belt driven units. The fan and motor are mounted as a compact unit with the motor inside the bearing pedestal. This arrangement is usually used with small- to mid-sized fans and motors. 5 Engineering Data 3900

Special Considerations Impeller Rotation - Axial Products Impeller rotation is always observed from the discharge regardless of where the impeller is mounted, which could be either at the inlet or the discharge. Fan Discharge Connections - Downblast Discharge (DBD) Connections to the discharge of DBD fans can be difficult, since the flange is usually located at the foundation bolting level. Some methods of dealing with this include: 1. Using a flex connection to go through a floor or base 2. Changing the centerline height of the fan to raise the discharge flange off of the floor 3. Incorporating discharge flange bolting into the base or floor on which the fan is mounted Inlet Box Positions for Centrifugal Fans Adapted from ACA Standard 99-2405-03, with written permission from Air ovement and Control Association Notes: 1. Position of inlet box and air entry to inlet box is determined from the drive side as defined below: a. On single inlet fans: The drive side is that side which is opposite of the fan inlet. b. On double inlet fans: 1. With a single driver: That side with the driver is considered as the drive side. 2. With multiple drivers: That side with the higher total power is considered as the drive side. If the total power on each side is equal, then the side that has the fixed (non-expansion) bearing is considered as the drive side. 2. Position of inlet box is determined in accordance with diagrams. Angle of air entry to box is referred to the top vertical axis of fan in degrees as measured in the direction of fan rotation. Angle of air entry to box may be any intermediate angle as required. 3. Positions 135 to 225 in some cases may interfere with floor structure. 6 Engineering Data 3900

Designation for Rotation and Discharge of Centrifugal Fans Adapted from ACA Standard 99-2406-03, with written permission from Air ovement and Control Association Up Blast CW 360 Top Angular Up CW 45 Top Horizontal CW 90 Top Angular Down CW 135 Down Blast CW 180 Bottom Angular Down CW 225 Bottom Horizontal CW 270 Bottom Angular Up XW 315 Up Blast CCW 360 Top Angular Up CCW 45 Top Horizontal CCW 90 Top Angular Down CCW 135 Down Blast CCW 180 Bottom Angular Down CCW 225 Bottom Horizontal CCW 270 Bottom Angular Up CCW 315 Notes: 1. Direction of rotation and angular reference is determined from the drive side as defined below: a. On single inlet fans: The drive side is that side which is opposite of the fan inlet. b. On double inlet fans: 1. With a single driver: That side with the driver is considered as the drive side. 2. With multiple drivers: That side with the higher total power is considered as the drive side. If the total power on each side is equal, then the side that has the fixed (non-expansion) bearing is considered as the drive side. 2. Direction of discharge is determined in accordance with diagrams. Angle of discharge is referred to the top vertical axis of fan and designated in degrees as measured in the direction of fan rotation. Angle of discharge may be any intermediate angle as required. 3. A fan inverted for ceiling suspension or rotated for side wall mounting will have its direction of rotation and angle of discharge determined when fan is located as if floor mounted. 4. This standard is in harmony with ISO 13349. In ISO 13349, CCW fans are referred to as LG, i.e. Left or Gauche, while CW fans are referred to as RD, i.e. Right or Droit-handed rotation. ethods of Designation of the Angular Position of Component Parts of a Centrifugal Fan 360 0 360 0 315 0 45 0 45 0 315 0 90 0 270 0 270 0 90 0 135 0 225 0 225 0 135 0 180 0 180 0 CCW Example 1 CW Example 2 Outlet CCW 315 Inspection door CCW 135 Inlet box CCW 45 otor CCW 360 Outlet CW 360 Inspection door CW 45 Inlet box CW 360 otor CW 135 7 Engineering Data 3900

Uncommon Inlet/Discharge Angles Inlet boxes and fan discharges may be provided at odd angles if requested. For example, a 30 inlet box position for a clockwise rotation fan with fan discharge at 330. 0 30 330 DRIVE END OF FAN otor Positions for Belt Driven Centrifugal Fans Adapted from ACA Standard 99-2407-03, with written permission from Air ovement and Control Association Location of motor is determined by facing the drive side of the fan and designating the motor position by letters W, X, Y, or Z as the case may be. Aerovent www.aerovent.com 5959 Trenton Lane N inneapolis, N 55442 Phone: 763-551-7500 Fax: 763-551-7501