Heat Exchanger Earny Type

Similar documents
MagixX-B exhaust air cleaning system

MagixX & StuffNix. Exhaust air treatment systems for efficient reduction of emissions from poultry houses

Test Report. about laboratory tests for. Determining technical parameters using carrier compound for air-cooling with water intake

CombiTunnel-Ventilation

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

MagixX & StuffNix. Exhaust air treatment for pig and poultry houses

Fresh air supply systems

CombiTunnel ventilation

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY

SHS AS A TECHNOLOGY PLATFORM FOR SUSTAINABLE & COMPETETIV ADVANTAGE

ViperTouch. The flexible climate and production computer for your poultry house

Sugarbeets Enjoy Warm Winter

Axial fans The right fan for every house

Heat recovery systems. For hot air and hot water applications.

Both regulations are due to be reviewed by Key topics to be assessed during the reviews include:

Heat pump supplemental heating system for motor vehicles

Operating Instructions

Wall fans. High air performance and low energy consumption

307pro. The computer for optimal climate control in every pig house

Filter cleaning in hot gas applications PENTAIR 1

Laboratory exercise 3: Condensing water heater

Certified Passive House Component For cool, temperate climates, valid until 31 December 2017

Heat pump and energy recovery systems

Heating Systems. An ideal temperature in every pig house

The computer for optimum climate in every pig house

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

HEAT RECOVERY WITH AERZEN TURBOS, BLOWERS AND COMPRESSORS. Reduce costs for compressed air generation

Operating instructions

PRODUCT CONFORMITY CERTIFICATE

ErP. The ErP Directive. New values for fans

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

Heat Pumps and Public Swimming Pools, a Perfect Match

Evaluation Report 324

Others ( 50Hz areas ) ADVANCED SUBJECT DATE: May-08 PRODUCT NEWS. Advanced Product News: Launching of New KPI-(502~2002)E1E & KPI-3002H1E units

This summarises results from our inspection of the Rendering Plant air extraction system at the Imlay meat works on 12 December 2013.

VULKAN. Stationary Powder-Filling Machines

Systems engineering Slide 1

AIR CONDITIONING UNIT WITH AN INTEGRATED HEAT PUMP

l i nda b we si mpl i f y c onstr u ction Conforms ErP Ecodesign Lot 6 Residential and non-residential air handling units

Operating Instructions

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

Ceiling air diffuser INDULTHERM INDULTHERM-e

Hoval series Plate Heat Exchangers for Heat Recovery in Ventilation Systems. Hoval

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

Possibilities of Heat Exchanger Use in Pigsty Ventilation Systems

AirUnit. Operating manual. mfh systems modern floor heating. Decentralised domestic ventilation

CI/SfB X. DF / IDF Series GAS FIRED COMBINED HEATING AND VENTILATION

Further Development of an Ion current Combustion Control System (ICCS)

Portable sample gas conditioning PCS.smart+

PERFORMANCE DATA Type Delivery Vacuum atm. Pressure Weight (l/min) (mbar absolute) Press (bar g) (kg)

Electronically controlled instantaneous water heater. DEX: C models. Instructions for the user

Energy consumption in properties

Fume extraction system FEC.

Boiler Venting. Definitions, Theory and Applications. Presented by: Jason Geagan, National Sales Manager US Draft Co Fort Worth, TX

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

Induction Billet Heaters with Enthalpy Controlled Zone Heating

LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD

Livestock heating. Infrared brooders KROMS 1 - KROMS 1.5 Infrared brooders KROMS 5 - KROMS 10 Temperature control systems

Heat Recovery Systems PTG, SWT Series.

Vallox Oy. manufactures. over LOW POWER EFFICIENCY Specific electrical

COATING WATER HEATERS BY POWDERING, SPRAYING OR FLOODING ON OVERHEAD CONVEYOR CHAIN

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

2 OZONFILT And Bono Zon Ozone Plants

Room sealed circuit appliance sold without the terminal or the combustion air supply and exhausted gas ducts. TYPE C 63 TYPE B TYPE B 23

Performance Report 2009 Chimfex

Supply air unit VEKA Installation & Maintenance

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

Decentralised ventilation units

Decentralised comfort ventilation unit Zehnder ComfoSpot 50

Self-recuperative burner for gas

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Rotors overview. Quick guide GOST VDI 6022

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

The products covered by the Regulation can be classified as follows:

Product overview Suction Guns, suction machines, Vac-Blast Cleaners

HRV Brochure. Heat Recovery Ventilation

Adding More Fan Power Can Be a Good Thing

VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER

Milling ing and Mixing Systems

MFP14 Automatic pumps. for condensate and other industrial fluids

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Masters in energy efficiency

MFP14 Automatic pumps for condensate and other industrial fluids

Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods

Vallox Oy. manufactures ventilation units Vallox TSK Multi 80 MC. over Vallox TSK Multi 80 MC

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

CI/SfB X. RHeco Series CONDENSING GAS FIRED UNIT HEATERS

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings

ErP. ErP READY. The Eco-Design Directive ErP for refrigerator systems and heat pumps. READY

Reduced Order WECC Modeling for Frequency Response and Energy Storage Integration

Equipment Information

SolarWall Fan Units. Introduction. Features. By Conserval Engineering Inc.

For greater protection Workplaces handling hazardous materials

FLIGHT UNLOADING IN ROTARY SUGAR DRYERS. P.F. BRITTON, P.A. SCHNEIDER and M.E. SHEEHAN. James Cook University

Operating manual for Steam Injectors / Mixing Nozzles

Developing OALCF Apprenticeship Tasks for the Competency Use Digital Tasks (2014/2015)

CAIRplus ECOTWINcool SUPPLEMENT TO OPERATION MANUAL

ROOFMASTER STEF-HT ROOF FAN

Transcription:

Big Dutchman International GmbH Heat Exchanger Earny Type 4. Efficiency of heat recovery under practical conditions DLG Test Report 614 F Revision 1: Amendment(s) see page 1 Assessment summary The DLG Focus Test "Efficiency of heat recovery" of the Big Dutchman air-air heat exchanger Earny Type 4. for use in broiler houses was conducted as a practical test in accordance with DIN EN 38, delivering the following results: Manufacturer/applicant Big Dutchman International GmbH Auf der Lage 2 D-49377 Vechta Germany Tel.: +49 ()4447 81- Fax: +49 ()4447 81-237 big@bigdutchman.de www.bigdutchman.de Test result Evaluation* Efficiency of heat recovery Average temperature-transfer efficiency: 57 % at T = 12,6 C + + Heat output Average output under winter conditions: 23.8 kw (see Operating conditions, p. 4) DLG evaluation standard for recuperative heat exchangers in practical agricultural use: Assessment + + + Temperature-transfer efficiency [%] > 5 > 4 to 5 > 3 to 4 > 2 to 3 < 2 N/A DLG e.v. Test Center Technology and Farm Inputs * Evaluation range: ++ / + / / / ( = standard) / N/A = Not Assessed DLG Test Report 614 F Page 1 of 12

Main technical data (manufacturer's data) Construction The Big Dutchman heat exchanger Earny Type 4. is used to recover heat from the return air in broiler houses. Experience shows that the heat exchanger has a positive influence on the broiler house's climate and on the litter quality. This reduces emissions of ammonia and odours. The Earny Type 4. works as a recuperative 1 cross flow heat exchanger (Fig. 2). This heat exchanger therefore falls under Category I. This means that warm poultry-house air 1 and cold ambient air 2 are fed simultaneously through exchanger bundles and that the air flows do not come into contact with one another during this process; only heat is exchanged. The clean ambient air is separated from the contaminated poultry-house return air in a hygienic manner. Only clean ambient air is fed back into the poultry house 3. A filter unit 4 ensures that only clean return air enters the heat exchanger. The automatic cleaning 5 of the filter cartridges is a prerequisite for ensuring that there is no drop in the heat ex changer's performance during the fattening cycle. The heat exchanger's exhaust air 7 is therefore almost completely cleared of dust and particulate-matter emissions. The exchanger element 6 is made of coated aluminium and has a ribbed structure in order to ensure a high rate of heat transfer. Axial fans convey the inlet and return air. Planning data Air flow 2, m³/h for use in a fattening house with approx. 4, birds Heat-recovery performance 17 kw (when V. return = 13,1 m 3 /h, T return = 3 C, Φ return = 6 %, V. inlet = 18,6 m³/h, T inlet = -1 C, Φ inlet = 6 %) Dimensions Length / width / height 2 5,2 mm / 2,3 mm / 2,3 mm 7 3 1 6 4 5 2 Figure 2: Functional principle 1 The term recuperation is generally used in relation to technical processes for energy recovery. In recuperative heat exchangers (cross- and counter-flow), exhaust and ambient air pass alongside one another without exchange of air and/or moisture. 2 Value for height of heat exchanger without diffusor DLG Test Report 614 F Page 2 of 12

Test results The tested Big Dutchman heat exchanger Earny Type 4. worked reliably throughout the test period. Measurement in a broiler house The Big Dutchman heat exchanger Earny Type 4. was tested on an existing broiler house with a floor area of 18 m². Measurements were recorded over three fattening periods from 1 December 212 to 29 April 213. In the tested winter months, the Big Dutchman heat exchanger Earny Type 4. achieved an average temperature-transfer efficiency of 57 % (Fig. 4, page 4). This means that 57 % of the maximum achievable inlet-air temperature was achieved. The efficiency of heat recovery is therefore better than the current definition of a standard level of > 3 % to 4 %. In addition, the temperature-transfer efficiency varied only slightly, by ± 3.5 %. The heat exchanger raised the temperature of ambient air by 12.6 C on average. However, this temperature increase depends very strongly on the weather conditions: the greater the temperature difference between the poultry-house air and the outside air, the greater the heating effect, and vice versa. Using the heat exchanger also avoids passing on and strongly attenuates the sometimes very large variations in the ambient-air temperature, which varies with the outside temperature. If the poultry-house ventilation system is operated in combination with a heat exchanger, the thermal energy gained from heat recovery is offset by an increased demand for electrical energy on the part of the fans. This arises due to the additional pressure losses in the heat exchanger that must be overcome. This increased consumption of electrical energy is many times lower than the recovered thermal energy. The ratio is approximately 1:2. This means that for one kilowatt-hour of electrical energy (electricity), approx. 2 kilowatthours of thermal energy (heat) can be recovered. Figure 5 (page 7) and Figure 6 (page 8) show the variations in temperature-transfer efficiency, inlet-air temperature increase, ambient-air temperature, heat output and inlet-air volume flow rate. Because of the large volume of data, not all data points are visualised. Occasionally, measurements were taken that exceed the scale. Temperature [ C] 3 25 2 15 1 5-5 Ambient air/ outside air Efficiency of heat recovery The temperature-transfer efficiency represents a key quality parameter for evaluating a heat-recovery system. Overview 2 (page 5) provides an explanation of correlations and calculations for heat exchangers. The following results relate exclusively to operating conditions. Inlet air December January February March April Exhaust air Figure 3: Bar chart of temperatures showing measured range (standard deviation) Table of supplementary data for Figure 3: Average temperature [ C] Ambient air/outside air Inlet air Exhaust air December 6.1 2.9 17. January 4.1 15.1 11.2 February 2.8 16. 9.5 March 2.2 19.3 1.3 April 6.5 13.9 8. Minimum and maximum values of ambient-air temperature [ C] December January February March April Minimum -2-7 -5-4 -3 Maximum 12 13 1 16 19 DLG Test Report 614 F Page 3 of 12

Temperature increase [K] Temperature-transfer efficiency [%] Heating output [kw] 8 7 6 5 4 3 2 1 Temperature increase of ambient air ( T) due to heat exchanger Temperaturetransfer efficiency of heat exchanger Figure 4: Bar chart of performance parameters showing measured range (standard deviation) December January February March April Heat output of heat exchanger Operating mode (according to manufacturer's information) The heat exchanger was controlled by the AMACS climate-control computer during the testing phase. The air volume flow rate passing through the heat exchanger was regulated by the minimum ventilation. Starting with a minimum ventilation or with the additional humidity control, the heat exchanger's ventilation requirement increased as the number of days of fattening increased (see Fig. 6). After 14 to 18 days of fattening, in order to achieve energy-optimised operation, the heat exchanger is automatically switched to a stand-by mode in which the exchanger operated at a reduced level of ventilation. Table of supplementary data for Figure 4*: Temperature increase of ambient air ( T) due to heat exchanger [K] Temperature-transfer efficiency of heat exchanger [ %] Heat output achieved by heat exchanger [kw] December 14.8 ± 5.5 53 ± 3 29.2 ± 7.8 January 11. ± 1.8 59 ± 5 15.7 ± 6.6 February 13.2 ± 3.4 6 ± 3 31.7 ± 11.4 March 17.1 ± 5.5 54 ± 2 32.4 ± 9.9 April 7. ± 1.8 56 ± 6 13.1 ± 7.2 Mean 12.6 ± 3.6 57 ± 4 23.8 ± 8.9 Overview 1: Operating states during the measurement period Condensation arising [kg/h] from December to March December 12.3 ± 4.3 January 15.5 ± 5.2 February 8.4 ± 1.4 March 11.6 ± 4.2 Mean 12. ± 3.8 Mean air volume flow rates for the heat exchanger over the entire measurement period Inlet air [m 3 /h] 5,8 ± 2,375 Return air [m 3 /h] 5,25 ± 2,36 Temperature [ C] of the return air over the entire measurement period 26.2 ± 5.2 * Explanation of numerical values: mean ± standard deviation DLG Test Report 614 F Page 4 of 12

Overview 2: Heat exchanger diagram and calculations Exhaust air (t 12 ) Ambient air (t 21 ) Inlet air (t 22 ) Return air (t 11 ) t 22 - t 21 Φ = t 11 - t 21 benefit of the recovered heat Φ = potential of the recovered heat or with regard to the "poultry-house ventilation" application: achieved temperature increase of the ambient air ( T) Φ = theoretically possible temperature increase of the ambient air Symbol Description Unit Φ Temperature-transfer efficiency indicates the thermal efficiency of heat transfer. % Other terms used to mean the same in technical contexts: heat-recovery efficiency, thermal-transfer efficiency t 11 Temperature of return air C t 12 Temperature of exhaust air C t 21 Temperature of ambient air C t 22 Temperature of inlet air C T Temperature difference = inlet air (t22) - ambient air (t21) K V. Inlet/return-air volume flow rate m 3 /h Indices First number: 1 = return air 2 = inlet air Second number: 1 = before the heat exchanger 2 = after the heat exchanger The temperature-transfer efficiency can take values between and 1 %. For example, in the field of air conditioning for buildings*, heat-recovery systems are classified with regard to temperature-transfer efficiency into six heat-recovery classes over the range of Φ = 37 % to 75 %. Because of the different mass flow rates (inlet and return air), the following interrelation was used in accordance with DIN EN 1353, page 29: q return Φ,4 t = Φ Φ t t 1:1 rearranged to: Φ t 1:1 = q inlet q,4 return q inlet where Φ t = temperature-transfer efficiency without taking account of mass flow rates [%] Φ t 1:1 = temperature-transfer efficiency, mass-specific [%] q inlet = inlet-air mass flow rate [kg/s] q return = return-air mass flow rate [kg/s] * DIN EN 1353 "Ventilation for buildings Air handling units Rating and performance for units, components and sections"; 11:27 DLG Test Report 614 F Page 5 of 12

Table 1: Operating conditions 1. Operating conditions Housing techniques Poultry fattening Prolonged fattening with early removal from housing Housing on litter Poultry-house building (manufacturer and operator information) Approved places for 41,8 birds Poultry-house floor space 2 m x 9 m, constructed in 29 Solid construction with thermally insulated gable roof Heated with gas heaters with flue-gas extraction Ambient-air supply via inlet-air valves in the poultry house's side wall, return air via gable fans (forced ventilation) Heat exchanger Erected on a metal platform on the side of the poultry house Ventilation system Inlet air Inlet air is sucked in from the outside and through the heat exchanger by the inlet-air fan and fed into the poultry-house area. Adjustable nozzles allow the inlet air to be dosed and directed (see Fig. 2, page 2). The air is distributed inside the poultry house with the adjustable nozzle and by the airflow within the poultry house that is produced by gas heaters and circulation fans. Return air The return air is extracted by a return-air fan and discharged to the outdoors via the heat exchanger. In the process, the return air from the poultry house is cleared of dust by air-filter cartridges. The filters are cleaned regularly with compressed air. Climate computer AMACS climate and production computer from Big Dutchman 2. Measuring equipment The temperatures were recorded in accordance with DIN EN 38. Temperature sensors Type T thermocouples Heat exchangers: 21 units in total, distributed over the inlet- and return-air sides Outside temperature/ambient-air temperature: 2 units Humidity sensors Dol 114 4 units in total, 1 unit before and after the heat exchanger on both the inlet- and return-air sides Measuring fans LMU-82 for the inlet-air volume flow rate (diameter = 82 mm) LMU-71 for the return-air volume flow rate (diameter = 71 mm) Data acquisition Recording and storage of all sensor measurements at a sampling interval of 1 minute 3. Test execution Total observation period: 1 December 212 to 29 April 213 Calibration: temperature and humidity sensors at start and end of measurement DLG Test Report 614 F Page 6 of 12

Fattening period 1 Fattening period 2 Fattening period 3 1 Temperature-transfer efficiency [%] 9 8 7 6 5 4 3 2 1 35 Inlet-air temperature increase [K] 3 25 2 15 1 5 2 Ambient-air temperature [ C] 15 1 5-5 -1 11.12.212 31.12.212 2.1.213 9.2.213 1.3.213 21.3.213 1.4.213 Figure 5: Temperature-transfer efficiency, inlet-air temperature increase and ambient-air temperature over time DLG Test Report 614 F Page 7 of 12

Fattening period 1 Fattening period 2 Fattening period 3 7 6 Heat output [kw] 5 4 3 2 1 2 Inlet-air volume flow rate [m 3 /h] 18 16 14 12 1 8 6 4 2 11.12.212 31.12.212 2.1.213 9.2.213 1.3.213 21.3.213 1.4.213 FATTEning DATA 1st fattening cycle Placed in poultry house on 1 Dec 212 Early harvest on 29th day of fattening (9 Jan 213) Removed from poultry house on 42nd day of fattening (22 Jan 213) 2nd fattening cycle Placed in poultry house on 28 Jan 213 Early harvest on 29th day of fattening (27 Feb 213) Removed from poultry house on 41st day of fattening (11 Mar 213) 3rd fattening cycle Placed in poultry house on 16 Mar 213 Early harvest on 3th day of fattening (16 Apr 213) Early harvest on 38th day of fattening (24 Apr 213) Removed from poultry house on 43rd day of fattening (29 Apr 213) Figure 6: Heat output and inlet-air volume flow rate over time DLG Test Report 614 F Page 8 of 12

Temperature-transfer efficiency 1 % 9 % 8 % 7 % 6 % 5 % 4 % 3 % 2 % -4-2 2 4 6 8 1 12 14 Outside temperature [ C] Figure 7: Dependence of temperature-transfer efficiency on ambient-air/outside temperature Characterisation of the heat exchanger Earny Type 4. according to DIN EN 38 Determination of the nominal air mass flow rate Inlet-air fan at 1 % output = 18,639 m³/h ^= 6.26 kg/s Return-air fan at 1 % output = 13,58 m³/h ^= 4.39 kg/s Analysis of leak tightness external leakage External leakage is leakage be - tween the air flowing through the heat exchanger and the environment. In accordance with DIN EN 38, the airtightness of external leakage is determined at 4 Pa of excess and negative pressure. For systems with static pressures of up to 25 Pa, DIN EN 38 allows testing of the system to be performed at 25 Pa instead of 4 Pa. The heat exchanger from Big Dutchman was tested at both pressure options (Table 2). Analysis of leak tightness internal leakage or internal air leakage Internal leakage is leakage of air between primary and secondary airflows of a heat-recovery system. According to DIN EN 38, internal return-air leakage is defined as leakage from the return-air side to the inlet-air side (Table 3). The internal leakage is measured at an excess pressure of 25 Pa on the Table 2: Analysis of leak tightness external leakage External leakage Pressure [Pa] Leakage volume Leakage mass flow rate [m³/h] flow rate [kg/s] Excess pressure 25 131.44 4 177.57 Negative pressure 25 125.42 4 165.56 Calculation for leak tightness of external leakage: q mep/ q mn 1 % =.7 % at 25 Pa excess pressure q men /q mn 1 % =.67 % at 25 Pa negative pressure Average air density over the entire measurement period = 1.21 kg m -3 q mn measured nominal air mass flow rate for inlet air [kg s -1 ] q mep external-leakage mass flow rate at excess pressure [kg s -1 ] q men external-leakage mass flow rate at negative pressure [kg s -1 ] Table 3: Analysis of leak tightness internal leakage Excess pressure on return-air side: 1 Pa; inlet-air side: Pa Calculation for leak tightness for internal air leakage: q mil /q mn 1 % =.83 % at 1 Pa pressure difference q mil internal-leakage mass flow rate [kg s -1 ] return-air side and Pa on the inletair side in accordance with DIN EN 38. For systems that are only designed for pressures of up to 25 Pa, DIN EN 38 allows testing of the Leakage volume flow rate [m³/h] Internal leakage Leakage mass flow rate [kg/s] 156.52 system to be performed at 1 Pa, instead of 25 Pa, on the returnair side. The measurements were conducted at an excess pressure of 1 Pa on the return-air side. DLG Test Report 614 F Page 9 of 12

Heat balance The change in enthalpy flow between the two flowing media was calculated as follows (for one measurement point as an example): P inlet = c p inlet q Zu Δt 22-21 = 1,6 [kj kg -1 K -1 ] 1,78 [kg s -1 ] 14,4 [K] [6] = 25,74 [kj s -1 ] P return = c p return q Ab Δt 11-12 = 1,7 [kj kg -1 K -1 ] 1,6 [kg s -1 ] 15,4 [K] [7] = 24,73 [kj s -1 ] P inlet = 1,4 P return c p spec. heat capacity of air [kj kg -1 K -1 ] t 21 ambient-air temperature [K] t 12 exhaust-air temperature [K] t 22 inlet-air temperature [K] t 11 return-air temperature [K] q inlet inlet-air mass flow rate [kg/s] q return return-air mass flow rate [kg/s] Table 4: Drop in pressure on the inlet-air side as a function of the percentage of nominal air mass flow rate Air mass flow rate [m³/h] Pressure [mbar] 1 %* 18,639 > 2.4 8 % 14,911 2.25 6 % 11,183 1.81 4 % 7,455.83 2 % 3,728.36 Table 5: Drop in pressure on the return-air side as a function of the percentage of nominal air mass flow rate Air mass flow rate [m³/h] Pressure [mbar] 1 %* 13,58 > 2.4 8 % 1,446 2.29 6 % 7,835 1.6 4 % 5,223.9 2 % 2,612.31 Table 6: Results of the dust measurements Period Drop in pressure The total drop in pressure is determined from the measurements in front of and behind the fan (see Tables 4 and 5). The drop in pressure is the pressure difference along the length of a pipeline section. Other results Power consumption The heat exchanger's average power consumption over the entire measurement period was 34.45 kwh per day. This figure also includes the DLG's measurement technology and the heating for the condensate tank. Humidity The relative humidity of the am - bient air varied between 3 and Weight of dust [kg] 1st fattening period 11 Dec 212 to 21 Jan 213 4.1 3rd fattening period 17 Mar 213 to 13 Apr 213 7. 1 % over the measurement period. The inlet air fed into the poultry house had a humidity value of between 1 and 8 %, and the value for the return air from the poultry house rose from approximately 5 % to 8 % during a fattening period. It was not possible to reliably measure the humidity in the vent stack (exhaust air) until March (due to condensation effects and icing up). From April onwards, the exhaust-air humidity predominantly measured just over 9 %. Dust The amount of dust arising in the heat exchanger per fattening period was also investigated. For this purpose, the first and third fattening periods were analysed (Table 6). The dust samples had an average moisture content of approximately 18 % after the respective fattening period. Cleaning (operator information) To allow safe and functional operation of the heat exchanger Earny Type 4., the appliance is to be cleaned after each fattening period. For this purpose, the filter compartment is first to be opened and the dust in the base area dispersed in water; after approx. 1 hour, the dust is to be scrubbed off, and the walls are also to be scrubbed. The filters can be rinsed with a conventional garden hose. The stopper in the filter compartment's outlet is to be removed, allowing the rinsed-off dust to escape from the area of the heat exchanger. Care must be taken to ensure that the stopper is reinserted after cleaning. The side of the heat exchanger behind the filters is also to be checked and cleaned if necessary. Twice a year, the entire heat exchanger should be rinsed. Clean tap water is to be used to clean the heat exchanger and the components. * For technical reasons (the measurement range was exceeded), the drop in pressure could only be reliably measured for up to approximately 8 % of the nominal air mass flow rate. Amendment for: [6] " 1,6 [kj kg -1 K -1 ] 1,78 [kg -1 s -1 ] 14,4 [K]" [7] " 1,7 [kj kg -1 K -1 ] 1,6 [kg -1 s -1 ] 15,4 [K]" DLG Test Report 614 F Page 1 of 12

Summary In conclusion, the heat exchanger Earny Type 4. from Big Dutchman operated reliably over the measurement period. Three full fattening periods were measured. The measurement period ran from December 212 to April 213. In this period, an average temperature-transfer efficiency of 57 % was achieved. The nominal volume flow rate was 18,639 m³/h for the inlet-air flow and 13,58 m³/h for the return-air flow. Furthermore, the heat exchanger was tested according to DIN EN 38 during the measurement period. The heat exchanger passed all of the tests. The Big Dutchman heat exchanger Earny Type 4. is suitable for heat recovery in prolonged broiler production with litter for up to approx. 4, birds. DLG Test Report 614 F Page 11 of 12

Test This test report was prepared based on DIN EN 38, which is the basis for testing heat-recovery systems for HVAC (Heating, Venti lation and Air Conditioning) appliances. The test was conducted at a broiler house in Emsland. No survey was conducted. Other criteria were not tested. Test Execution DLG e.v., Test Center Technology and Farm Inputs, Max-Eyth-Weg 1, D-64823 Groß-Umstadt Technology Dipl.-Ing. T. Pfeifer Project Manager Dipl.-Ing. J. Drmić ENTAM European Network for Testing of Agricultural Machines, is the association of European test centres. ENTAM's objective is the Europe-wide distribution of test results for farmers, agricultural equipment dealers, and producers. More information about the Network is available at www.entam.com or by writing to ENTAM at the email address: info@entam.com 212-735 March 214 DLG DLG e.v. Test Center Technology and Farm Inputs Max-Eyth-Weg 1, D-64823 Groß-Umstadt, Tel.: 69 24788-6, Fax: 69 24788-69 E-Mail: tech@dlg.org, Internet: www.dlg-test.de Download all DLG test reports free of charge at: www.dlg-test.de! DLG Test Report 614 F Page 12 of 12